Littelfuse T3000 User Manual

Protection Relays & Controls
Generator & Single-Function Protection–Frequency
T3000 SERIES
Frequency Relay
Simplified Circuit Diagram
T3000
(Frequency Relay)
(L)
L
1
(N)
L
2
1 2 3
UNDERFREQUENCY
OVERFREQUENCY
ALARM
ALARM
Ordering Information
ORDERING NUMBER
1-3 2-3
T3000.0010 230 V T3000.0020 450 V 400 V T3000.0030 110 V 100 V T3000.0040 480 V 415 V T3000.0050 127 V 120 V
Other vo ltages are available o n request .
TERMINALS
10
9 8
7 6 5
Description
The T3000 Frequency Relay is designed for frequency monitoring on generators, bus bars or other distribution systems.
The T3000 consists of two circuits, one circuit for over frequency and one for under frequency monitoring. Each circuit has individual settings for frequency levels and time delays. The output relays are normally energized output relays. The output relay for under frequency is activated at frequencies higher than the preset value, while the output relay for over frequency is activated at frequencies lower than the preset value. This means that both output relays are activated at frequencies within the interval between the under and over frequency scale range.
Features & Benefits
FEATURES BENEFITS
Accepts high supply voltage variation
Visual indication of power, pick-up, and output trip
Direct line-line or line­neutral voltage supply (up to 690 Vac)
Combining 2 relays in same enclosure
Galvanic isolated inputs
DIN-rail or screw-mount & adjustment by potentiometers
Ensures correct operation in spite of voltage supply fluctuations (fulfills marine class requirement)
Provides quick and concise status information
Simplifies design and installation. No need for PTs.
Economic solution . Monitoring both underfrequency and overfrequency in same unit, and occupying less space in the switch panel
Protects the unit against high AC voltage and currents from the installation including spikes
Easy installation
Specifications
Overfrequency Level 45-65 Hz Delay 1-10 sec. Underfrequency Level 45-65 Hz Delay 1-10 sec. Max. Voltage 660 V Voltage Range 70 -110% Consumption Continuous Current 2 x I Frequency Range 40 -70 Hz Output Relay Normally energized Contact Rating AC: 250 V, 2 A, 250 VA; DC: 60 V, 2 A, 100 W Overall Accuracy ±3% of highest value Repeatability ±1% Operating Temperature Dielectric Test 2500 V, 50 Hz EMC CE according to EN50081-1, EN50082-1, EN50081-2,
EN50082-2
Approvals Certified by major marine classification societies Burn-in 50 hours before final test Enclosure Material Polycarbonate. Flame retardant Weight 0.5 kg Dimensions H 70 mm (2.76”); W 100 mm (3.94”); D 115 mm (4.52”) Installation 35 mm DIN rail or 4 mm (
5 VA at U
N
N
–20°C to + 70°C
3
/16”) screws
© 2013 Littelfuse Protection Relays & Controls Littelfuse.com/t3000
Rev: 4-A-050213