Description
The T2800 Earth Fault Relay is part of the T-Line series with
modular units for protection, control and monitoring of
generators. The T2800 detects the magnitude of the current
and, if this exceeds the preset level (0.02-2 x I
LED will indicate and the delay timer will be started. After the
), the pick-up
N
preset time (0.1-10 sec.) has expired the output relay and the
corresponding LED will be activated, provided that the current
level was exceeded for the entire delay time. The T2800 has
a normally energized output relay. The relay is a latching relay
which can be reset or disabled.
Features & Benefits
FEATURES BENEFITS
Accepts high supply
voltage variation
Visual indication of power,
pick-up, and output trip
Direct line-line or lineneutral voltage supply
(up to 690 Vac)
Wide range of combined
current and delay
settings
Galvanic isolated inputs
DIN-rail or screw- mount
& adjustment by
potentiometers
Ensures correct operation in spite of voltage
supply fluctuations (fulfils marine class
requirement)
Provides quick and concise status information
Simplifies design and installation.
No need for PTs
Enables versatile use as earth fault relay or
standard overcurrent relay. Combining more units
offers economic alternative to relays with inverse
time response.
Protects the unit against high AC voltage and
currents from the installation including spikes
Easy installation
Ordering Information
ORDERING NUMBER
T2800.00 230 V 5 A
T2800.01 450 V 400 V 5 A
T2800.02 127 V
T2800.04
T2800.05 480 V
T2800.08 230 V 1 A
Other combinations and voltages are availab le on request.
© 2013 Littelfuse Protection Relays & Controls
Littelfuse.com/t2800
TERMINALS
1-3 2-3
120 V
24V DC+AC
415 V
I
N
5 A
5 A
5 A
Specifications
Trip Level 0.02-0.2 x IN or 0.2-2 x I
Delay 0.1-1.0 sec. or 1.0-10 sec.
Max. Voltage 660 V
Voltage Range 60-110 %
Consumption
Voltage 5 VA at UN
Current 0.3 VA at I
Continuous Current 2 x I
Frequency Range 45- 400 Hz
N
Output Relay Normally energized, latching, resetable
Contact Rating AC: 400 V, 5 A, 2000 VA
DC: 150 V, 5 A, 150 W
Overall Accuracy ±5%
Repeatability ±1%
Operating Temperature
–20°C to + 70°C
Dielectric Test 2500 V
EMC CE according to EN50081-1, EN50082-1, EN50081-2,
EN50082-2
Approvals Certified by major marine classification societies
Burn-in 50 hours before final test
Enclosure Material Polycarbonate. Flame retardant
Weight 0.5 kg
Dimensions H 70 mm (2.76”); W 100 mm (3.94”); D 115 mm (4.52”)
Installation 35 mm DIN rail or 4 mm (
N
N
3
/16”) screws
Rev: 4-A-050213