Littelfuse T2800 User Manual

Protection Relays & Controls
Protection Relays
Earth-Fault Protection–Solidly-Grounded Systems
T2800 SERIES
Earth-Fault Relay
Simplified Circuit Diagram
12
SEC x 10
13
LATCHING
15
OFF
16
18
I x 10
N
19
7
8 9
10
1 2 3
T2800
(Earth-Fault Relay)
5
6
Description
The T2800 Earth Fault Relay is part of the T-Line series with modular units for protection, control and monitoring of generators. The T2800 detects the magnitude of the current and, if this exceeds the preset level (0.02-2 x I LED will indicate and the delay timer will be started. After the
), the pick-up
N
preset time (0.1-10 sec.) has expired the output relay and the corresponding LED will be activated, provided that the current level was exceeded for the entire delay time. The T2800 has a normally energized output relay. The relay is a latching relay which can be reset or disabled.
Features & Benefits
FEATURES BENEFITS
Accepts high supply voltage variation
Visual indication of power, pick-up, and output trip
Direct line-line or line­neutral voltage supply (up to 690 Vac)
Wide range of combined current and delay settings
Galvanic isolated inputs
DIN-rail or screw- mount & adjustment by potentiometers
Ensures correct operation in spite of voltage supply fluctuations (fulfils marine class requirement)
Provides quick and concise status information
Simplifies design and installation. No need for PTs
Enables versatile use as earth fault relay or standard overcurrent relay. Combining more units offers economic alternative to relays with inverse time response.
Protects the unit against high AC voltage and currents from the installation including spikes
Easy installation
Ordering Information
ORDERING NUMBER
T2800.00 230 V 5 A T2800.01 450 V 400 V 5 A T2800.02 127 V T2800.04 T2800.05 480 V T2800.08 230 V 1 A
Other combinations and voltages are availab le on request.
© 2013 Littelfuse Protection Relays & Controls Littelfuse.com/t2800
TERMINALS
1-3 2-3
120 V
24V DC+AC
415 V
I
N
5 A 5 A 5 A
Specifications
Trip Level 0.02-0.2 x IN or 0.2-2 x I Delay 0.1-1.0 sec. or 1.0-10 sec. Max. Voltage 660 V Voltage Range 60-110 %
Consumption
Voltage 5 VA at UN
Current 0.3 VA at I
Continuous Current 2 x I Frequency Range 45- 400 Hz
N
Output Relay Normally energized, latching, resetable Contact Rating AC: 400 V, 5 A, 2000 VA
DC: 150 V, 5 A, 150 W
Overall Accuracy ±5% Repeatability ±1% Operating Temperature
–20°C to + 70°C
Dielectric Test 2500 V EMC CE according to EN50081-1, EN50082-1, EN50081-2,
EN50082-2
Approvals Certified by major marine classification societies Burn-in 50 hours before final test Enclosure Material Polycarbonate. Flame retardant Weight 0.5 kg Dimensions H 70 mm (2.76”); W 100 mm (3.94”); D 115 mm (4.52”) Installation 35 mm DIN rail or 4 mm (
N
N
3
/16”) screws
Rev: 4-A-050213
Loading...