Littelfuse T2600 User Manual

Generator Control
Basic Generator Protection
T2600 SERIES
Dual-Current Relay
Simplified Circuit Diagram
L
1
L
2
L
3
1
CONTROL POWER
2 3
U
T2600
11
I
1
12 13
I
2
14 15
I
3
16
G6G4 G5
To check rel ay operation, check t hat the “PO WER” L ED is on, ensuring th at the supply is present. Mea sure the supply vol tage which m ust be compa tible wi th infor mation lab el on top of e nclosure. Measure the curren t circulat ing in term inals 11 -12, 13 -14 and 15-16 and observe that at least on e of the currents are ab ove setting. 0. 5 x I
2019
G1 G2
11
(Dual Current Relay)
I
1
12 13
I
2
14 15
I
3
16
G3
CIRCUIT
CIRCUIT
18
2019
17
= 2.5A; 2 x IN = 10A .
N
STAR T
STOP
Ordering Information
ORDERING NUMBER
T2600.0010 230 V 5 A 30 sec. or 1 sec.* T2600.0020 450 V 400 V 5 A 30 sec. or 1 sec.* T2600.0030 480 V 415 V 5 A 30 sec. or 1 sec.*
T2600.0040 450 V 400 V 5 A
T2600.0050 480 V 5 A
T2600.0060 110 V 100 V 5 A 30 sec. or 1 sec.*
T2600.0070 110 V 100 V 5 A
T2600.0080 230 V 5 A
T2600.0090 Extension Unit
*Pulse duration time for stop signal, bridge 17-18 = 1 sec.
TERMINALS
1-3 2-3
I
FUNCTION
N
30 sec.*, bridge 17-18 = stop current increased 34%
30 sec.*, bridge 17-18 = stop current increased 34%
30 sec. or 1 sec.*, start current delay 1.0-10 secs
30 sec. or 1 sec.*, normally de-energized start relay
Manual
G1
10
G1 G3
9
}
8 7
Manual
G1 G1
6
G3
5
}
4
Description
The T2600 Dual-Current Relay combines two current relays. The function of the unit is to start or stop the standby diesel generator according to the load situation. Current is measured as a single phase measurement in each of the generators. Both relays will respond to the highest of the currents, independent of phase angle.
Starting signal: The starting output relay is controlled by the high level start current relay (0.3-1.2 x I of 3-30 seconds. If one of the 3 input currents exceeds the
) with a time delay
N
current setting for a longer period than the time setting, the output relay will become deactivated.
Stopping signal: The low level current relay (0.2-0.8 x I controls a time delay (1-10 minutes) which again controls the stop output relay. If all input currents are lower than the current setting for a longer period than the time delay setting of 1-10 minutes, the output relay will be activated.
Features & Benefits
FEATURES BENEFITS
STAR T
Accepts high supply voltage variation
Visual indication of power,
STOP
pick-up, and output trip
Direct line-line or line-neutral voltage supply (up to 690 Vac)
Simultaneous monitoring of load level on 3 synchronous generators
Combining 2 trip outputs in same enclosure
Extension module available for monitoring of additional 3 generators
Galvanic isolated inputs
DIN-rail or screw-mount & adjustment by potentiometers
Ensures correct operation in spite of voltage supply fluctuations (fulfills marine class requirement)
Provides quick and concise status information
Simplifies design and installation. No need for PTs.
Economic solution for load depending start/ stop of generators in parallel operation
Providing both start signal to stand-by generator and stop signal of running generator from same unit
Economic and easy to install system enhancement
Protects the unit against high AC voltage and currents from the installation including spikes
Easy installation
Specifications
Start Level 30 -120% Delay 3-30 sec. Stop Level 20-80% Delay 1-10 min. Max. Voltage 660 V Voltage Range 60-110 % Consumption 5 VA at U Frequency Range 40-65 Hz Contact Rating AC: 400 V, 8 A, 2000 VA; DC: 35 V, 8 A, 150 W Overall Accuracy ±3% of highest value Repeatability ±1% Operating Temp. –20°C to +70°C EMC CE according to EN50081-1, EN50082-1, EN50081-2,
EN50082-2
Approvals Certified by major marine classification societies Burn-in 50 hours before final test Weight 0.5 kg Dimensions H 70 mm (2.76”); W 100 mm (3.94”); D 115 mm (4.52”) Installation 35 mm DIN rail or 4 mm (
N
3
/16”) screws
)
N
© 2013 Littelfuse Protection Relays & Controls www.littelfuse.com/t2600
Rev: 4-A-050313