Littelfuse PPI-600V User Manual

3714 Kinnear Place Saskatoon, Saskatchewan Canada S7P 0A6 Ph: (306) 373-5505 Fx: (306) 374-2245 www.startco.ca
PPI-600V
PARALLEL PATH ISOLATOR
OCTOBER 13, 2011
REVISION 0
The PPI-600V is a ground-wire device that allows a trailing-cable ground to be monitored independently of the parallel ground path created when trailing-cable-fed equipment is in contact with the earth. It also allows a trailing-cable ground to be monitored in the presence of stray dc and it prevents inter-machine arcing caused by the voltages induced in the cables.
PPI-600V Parallel Path Isolator Rev. 0
TYPICAL APPLICATION
GROUND CHECK MONITOR SE134C, SE-135, SE-105 OR SE-125
INCOMING GROUND CHECK
GC
INCOMING GROUND
GROUND-CHECK
TERMINATION
G
INCOMING
CHASSIS GROUND BUS
CABLE
GROUND
G
CABLE
GROUND
GC
PPI-600V
NOTES:
1. PARALLEL PATH ISOLATOR IS NOT POLARIZED. EITHER FLANGE CAN BE CONNECTED TO CHASSIS.
2. THE OUTGOING GROUND MUST BE ISOLATED FROM THE CHASSIS GROUND BUS. IF A FLANGE-MOUNTED RECEPTACLE IS USED, VERIFY THAT THE FLANGE IS ISOLATED FROM THE GROUND PIN, AND
- USE A MATING PLUG WITH A NON-METALLIC HOUSING, OR
- ISOLATE THE FLANGE FROM THE CHASSIS IF THE MATING PLUG HAS A METALLIC HOUSING.
3. CABLE PLUGS AND RECEPTACLES WITH GROUNDED METAL HOUSINGS MUST BE ISOLATED FROM EARTH TO PREVENT PARALLEL GROUND PATHS.
4. FOR SYSTEMS ABOVE 600 VAC, CONNECT A V131DA40 MOV ACROSS THE PPI-60 0V.
GC
G
OUTGOING GROUND CHECK
OUTGOING GROUND
TECHNICAL SPECIFICATIONS
Dimensions:
Height ......................................... 102 mm (4.0”)
Width .......................................... 235 mm (9.3”)
Depth .......................................... 64 mm (2.5”)
Shipping Weight ........................ 11.5 lb (5.5 kg)
Off-State Resistance .................. >20 k @ 125°C
and V < 10.0 V
On-State Voltage ....................... < 2 V @ 25°C
and I<2000 A
Minimum Trigger Voltage ........ 20 V
Maximum Trigger Voltage ....... 25 V
Clamp Rating:
1 Cycle .................................. 15 kA
10 second .............................. 2.5 kA
Failure Mode .............................. Short Circuit
DISCLAIMER
Specifications are subject to change without notice. Littelfuse Startco is not liable for contingent or consequential damages, or for expenses sustained as a result of incorrect application, incorrect adjustment, or a malfunction.
OUTGOING GROUND CHECK TERMINATION
Oct. 13, 2011 PPI-600V Parallel Path Isolator Datasheet