Littelfuse POWR-GARD Fuse Catalog Page

POWR-GARD® Fuse Datasheet
QP
L
UL Class RK5
FLNR_ID/FLSR_ID SERIES INDICATOR® FUSES
250/600 VAC • Dual Element • Time Delay • 1/10-600 Amperes
Specifications
Voltage Ratings: AC: 250 V (FLNR_ID); 600 V (FLSR_ID) DC: 125 V (FLNR 125 V (FLNR_ID 35 – 600 A); 300 V (FLSR_ID)
Interrupting Ratings: AC: 200 kA rms symmetrical 300 kA rms symmetrical (Littelfuse self-certified) DC: 20 kA
Ampere Range: Approvals: Standard 248-12, Class RK5
UL Listed (File No. E81895) CSA Certified (File No. LR29862) Federal Specification WF-1814 (Q P L- W-F -1814 )
1
/10 – 600 A
1
/10 – 30 A);
Description
Available in both Indicating and Non-Indicating versions, the FLNR/FLSR series of fuses sets the standard for general purpose fuses. The dual element design provides advanced short circuit and overload protection. FLSR series fuses provide excellent protection for all types of circuits especially those containing motors.
Applications
• Service entrance switches
• Switchboard mains and feeders
• Motor control central mains and motor branch circuits
• All general purpose circuits
Features/Benefits
• Indication
• Dual element design
• Available without indication
• Current limiting
Ordering Information
1
1
15
2
3
/10† 1 4/
4
*FLNR only. †F LNR, FLSR, FLSR_ID only. **FLNR, FLSR, FLSR_ ID only Note: For
6
/
/8*
/ /
1
/
1
10
100
10
/
10
/
10
/
8
10
/ 1 2 1/
1 1/82 1/25 6/
4
1 1/42 8/
10
1 1/23 2/
2
1 6/103 1/27 1/
1
/10 – 30A 250 volt fuses, order non-indicating FL NR series fuses.
TYPE VOLTAGE SERIES AMP
NON-INDICATING 600 V FLSR 15 FL SR 015 FLSR015.T INDICATING 600 V FLSR_ID 15 FLSR015ID FLSR015.TXID NON-INDICATING 250 V FLNR 60 FLNR060 FLNR 0 6 0.T INDICATING 250 V FLNR_ID 60 FLNR060ID FLNR060.TXID
AMPERE R ATINGS
10
1 8/
2 4 1/
4 8 30 80 225
2
4
5 10 40 10 0 300
10
6 15 50 125 400
9 35 90 250
10
12 45 110 350
3 6 1/417 1/260 150 450
10
7 20 70 175 500
2
25 75
**
CATALOG
NUMBER
200 600
SYSTEM
NUMBER
Web Resources
TC Curves, downloadable CAD drawings and other technical information: www.littelfuse.com/flsr
www.littelfuse.com/flnr
Recommended Fuseholders
LFR60 Series LFR25 Series
1
©June 2011 Littelfusewww.littelfuse.com
POWR-GARD® Fuse Datasheet
UL Class RK5
CLASS RK5 CURRENT-LIMITING EFFECTS
Current-Limiting Effects of FLNR and FLNR_ID (250V) Fuses
APPA RENT RMS SYMMETRICA L CURRE NT F OR VARIOUS FUSE R ATINGS
SHORT-CIRCUIT CURRENT*
30 A 60 A 100 A 20 0 A 400 A 600 A
5,000
10,000
15,000
20,000
25,000
30,000
35,000
40,000
50,000
60,000
80,000
100,000
150,000
200,000
1,4 00 2,10 0 3,10 0 5,000 5,000 5,000
1,5 5 0 2,500 3,900 6,500 9,500 10,000
2,000 3,15 0 4,400 7, 25 0 10,500 14,000
2,250 3,400 5,000 8,250 12,000 16,000
2,400 3,750 5,250 9,000 12,500 16,500
2,550 4,100 5,600 9,500 13,500 18,000
2,650 4,300 5,800 9,750 14,000 19,000
2,800 4,400 6,250 10,250 15,000 20,000
3,000 5,000 6,500 10,500 16,000 21,000
3,200 5,250 7,000 11,500 17,000 23,000
3,400 5,750 7,500 12,500 19,000 25,500
3,850 6,000 8,000 13,500 21,000 27,500
4,10 0 7,000 9,000 15,200 24,000 31,500
4,300 7,500 9,750 16,500 26,000 34,000
*Prospective RMS Symmetrical Amperes Shor t-Cir cuit Current
Note: Data Derived from Pe ak Let-Thru Curves
2
©June 2011 Littelfusewww.littelfuse.com
Loading...
+ 2 hidden pages