POWR-GARD® Relay Testing Equipment
(PGT Series)
PGT-0400 SERIES
Ground-Fault Relay Test Unit
Description
The PGT-0400 is a ground-fault-relay test unit designed to
test current pickup level, time-delay and coordination of
ground-fault protection.
The tester injects current through the window of installed
ground-fault current transformers to verify the operation of
ground-fault monitors and relays.
Used on substations, motor control centers (MCCs), central
distribution panels, switchboards, and test benches to verify
relay operation.
The PGT-0400 tests the entire ground-fault circuit including
current transformers, wiring, ground-fault relay and the
operation of the interrupting device. It is recommended to
test every relay and its current interrupting device annually.
Wiring Diagram
11
1
CONTROL
POWER
3
5
POWR-GARD®
GROUND-FAULT RELAY
TEST UNIT
PGT-0400
INSULATED CTs
TO BE TESTED
(Phase conductor
removal not necessary)
12
8
9
TEST
Features & Benefits
FEATURES BENEFITS
Adjustable Current
Setpoint
Adjustable Time
Duration Setpoint
Small Form Factor
Remote Test Input
Current range is 0.5 to 9.9 A
Duration range is 0.1 to 9.9 s, or continuous
output
Light weight and compact for portability
Allows test to be initiated from another
location
Ordering Information
CATALOG/ SYSTEM NUMBER
PGT-0400 120 Vac
CONTROL POWER
Specifications
Input Voltage 84–134 Vac, 50/ 60 Hz, 80 VA
Dimensions H 219 mm (8.6”);
W 99 mm (3.9”);
D 143 mm (5.6”)
Output Current Settings 0.5
Output Duration Settings 0.1
Output Voltage 5.0 Vac maximum
Conformally Coated Standard feature
Warranty 5 Year
Mounting Surface, Panel
–9.9 A
–9.9 s or continuous
RELAY TESTING EQUIPMENT
© 2010 Littelfuse POWR-GARD® Protection Relay Catalog
35
www.littelfuse.com/pgt-0400