Littelfuse PGT-0400 User Manual

POWR-GARD® Relay Testing Equipment
(PGT Series)
PGT-0400 SERIES
Ground-Fault Relay Test Unit
Description
The PGT-0400 is a ground-fault-relay test unit designed to test current pickup level, time-delay and coordination of ground-fault protection.
The tester injects current through the window of installed ground-fault current transformers to verify the operation of ground-fault monitors and relays.
Used on substations, motor control centers (MCCs), central distribution panels, switchboards, and test benches to verify relay operation.
The PGT-0400 tests the entire ground-fault circuit including current transformers, wiring, ground-fault relay and the operation of the interrupting device. It is recommended to test every relay and its current interrupting device annually.
Wiring Diagram
11
1
CONTROL
POWER
3
5
POWR-GARD®
GROUND-FAULT RELAY TEST UNIT
PGT-0400
INSULATED CTs TO BE TESTED
(Phase conductor removal not necessary)
12
8
9
TEST
Features & Benefits
FEATURES BENEFITS
Adjustable Current Setpoint
Adjustable Time Duration Setpoint
Small Form Factor
Remote Test Input
Current range is 0.5 to 9.9 A
Duration range is 0.1 to 9.9 s, or continuous output
Light weight and compact for portability Allows test to be initiated from another
location
Ordering Information
CATALOG/ SYSTEM NUMBER
PGT-0400 120 Vac
CONTROL POWER
Specifications
Input Voltage 84–134 Vac, 50/ 60 Hz, 80 VA Dimensions H 219 mm (8.6”);
W 99 mm (3.9”);
D 143 mm (5.6”) Output Current Settings 0.5 Output Duration Settings 0.1 Output Voltage 5.0 Vac maximum Conformally Coated Standard feature Warranty 5 Year Mounting Surface, Panel
9.9 A
9.9 s or continuous
RELAY TESTING EQUIPMENT
© 2010 Littelfuse POWR-GARD® Protection Relay Catalog
35
www.littelfuse.com/pgt-0400
Loading...