Littelfuse PGR-6800 User Manual

Protection Relays & Controls
Motor Protection–Pumps (PGR 6000 Family)
PGR-6800 SERIES
Pump Protection Relay
Simplified Circuit Diagram
PGR-6800 SERIES
L1
L2
(Pump Protection Relay)
M
Description
The PGR-6800 Pump Protection Relay provides protection for pumps with three-phase motors up to 1,000 Vac. No current transformers are required for currents up to 91 A. The protective functions include overload, phase unbalance, phase loss, phase sequence and undercurrent. The PGR-6800 Pump Protection Relay is ideally suited for applications where operating without load can induce failure. Motor current is monitored and an undercurrent trip occurs when the current drops below a preset level. No additional level detectors are required.
Features & Benefits
FEATURES BENEFITS
No CTs required
Adjustable trip settings
Output contacts
Remote indication
Overload
Phase loss/Phase sequence
Unbalance (current) Prevents overheating due to unbalanced phases
Undercurrent Detects low level or no-load conditions
No current transformers required for currents up to 91 A
Adjustable overload trip class setting from 5 to 15 for use with a wide variety of pumps
Form A and Form B ground-fault output contacts for operation of separate annunciation and trip circuits
Cause-of-trip indication and reset button Prevents insulation failures and fires; extends
motor life
Detects unhealthy supply conditions
PGB-6800
(Remote Indication and Reset Assembly)
A
Ordering Information
ORDERING NUMBER CONTROL POWER FULL-LOAD CURRENT
PGR-6801-24 24 Vdc 7-19.6 A
PGR-6801-120 120 Vac 7-19.6 A
PGR-6801-240 240 Vac 7-19.6 A
PGR-6802-24 24 Vdc 19-44.2 A
PGR-6802-120 120 Vac 19-44.2 A
PGR-6802-240 240 Vac 19-44.2 A
PGR-6803-24 24 Vdc 40-90.4 A
PGR-6803-120 120 Vac 40-90.4 A
PGR-6803-240 240 Vac 40-90.4 A
ACCESSORIES REQUIREMENT
PGB-6800 Optional
Accessories
A
PGB-6800 Remote Indication and Reset Assembly
Optional remote indication of overload, undercurrent, phase unbalance, phase loss, and phase sequence. Remote reset included.
Specifications
Protective Functions (IEEE Device Numbers)
Input Voltage See ordering information Frequency 50, 60 Hz Dimensions H 83 mm (3.3”); W 78 mm (3.1”); D 99 mm (3.9”) Tes t Bu t ton Standard feature Reset Button Standard feature Output Contacts Isolated form A and Form B Approvals UL Listed (E343314) Warranty 5 years Mounting DIN
Overload (49, 51) Phase sequence (46) Undercurrent (37)
Unbalance (current) (46) Phase loss (current) (46)
© 2013 Littelfuse Protection Relays & Controls Littelfuse.com/pgr-6800
Rev: 4-A-050213
Based on Manual Rev 0