Littelfuse PGR-6300 Series Catalog Page

POWR-GARD® Protection Relays, Monitors & Systems
Motor Protection – Advanced (PGR 6000 Family)
PGR-6300 SERIES
Motor Protection System
Description
The PGR-6300 Motor Protection System monitors voltage, current, and temperature (optional) to provide a comprehensive package of 22 protective functions. The PGR-6300 is a modular system with integrated protection, motor control, metering, and data-logging functions. This system is typically used to provide protection for three-phase low- and medium-voltage, medium-
1
MOTOR PROTECTION RELAYS
2
Wiring Diagram
POWR-GARD
OPERATOR INTERFACE
PGR-6300 SERIES
(included)
®
1
POWR-GARD
PHASE CURRENT TRANSFORMERS
PGC 2000 SERIES
®
(required) (required)
A B
POWR-GARD
GROUND-FAULT CURRENT TRANSFORMER
PGC FAMILY
®
PHASE
VOLTAGES
(optional)
®
POWR-GARD
TEMPERATURE INPUT MODULE
PGA-0120
C
(optional)
®
POWR-GARD
DIFFERENTIAL CURRENT MODULE
PGA-0140
D
33 22
30 29 27 26 23 22
POWR-GARD®
MOTOR PROTECTION SYSTEM
PGR-6300 SERIES
20 17
(Control Unit)
......
60 56
I/0 MODULE
53 52
+
4-20 mA
ANALOG
INPUT
to high-horsepower induction motors.
1
Operator Interface
Large, bright, 4 x 20 vacuum-fluorescent display Display metered values Keypad for motor control and menu selection Access set points Powered by Control Unit Panel mount or attach directly to Control Unit Remote mounting (1.2 km or 4000 ft maximum loop length) 1/2 DIN size Hazardous-location certified
2
Control Unit
Current inputs—5-A or 1-A secondary phase current transformers Voltage inputs—up to 600 V without PTs Earth-leakage input—5-A or 1-A secondary or sensitive transformer Tachometer (high-speed pulse) input 8 digital inputs, 5 relay outputs, 1 analog input and output 24-Vdc supply for OPI and RTD modules, and for digital inputs IRIG-B time-code input 1/2 DIN size, surface mount RS-485 network communications DeviceNet
, Profibus®, or Ethernet communications available
Accessories
A
B
C
PGC-2000 Series Phase Current Transformers
Required CT detects phase current or ground­fault current (200-A primary). Other current ratios available.
PGC Family Ground-Fault Transformers
Required zero-sequence current transformers detect ground-fault current. Available with 5-A and 30-A primary ratings for low-level pickup.
PGA-0120 Temperature Input Module
Optional module provides 8 inputs to connect Pt100, Ni100, Ni120, and Cu10 RTDs.
1
CONTROL
POWER
ANALOG OUTPUT
RELAY
OUTPUTS
2
5 16
......
RS-485
35 37
......
4-20 mA
+
39 40
DIGITAL INPUTS
43 51
......
2
D
PGA-0140 Differential Current Module
Optional differential protection, compatible with core balance and summation current transformer connections.
PHASE CT
PHASE CT
GF CT
PHASE CT
PGA-0CIM
RTD
M
PGA-0120
(Temperature Input Module)
(Current Input Module)
PGR-6200
(Motor Protection Relay)
POWR-GARD®
POWR-GARD®
POWR-GARD
®
POWR-GARD® Protection Relays, Monitors & Systems
Motor Protection – Advanced (PGR 6000 Family)
Features & Benefits
FEATURES IEEE # BENEFITS
Overload Current Unbalance/
Phase Loss/Phase Reverse Overcurrent/Jam
Undercurrent Ground Fault
RTD Temperature
Overvoltage Undervoltage Voltage Unbalance Phase Differential Dynamic Thermal Model Reduced Overcurrent Mode Starter Control Metering Data Logging Communications Conformal Coating
Simplified Circuit Diagram
PHASE CT
A
PHASE CT
L1 L2
POWR-GARD®
PGR-6300
(Control Unit)
POWR-GARD®
PGR-6300
(Operator Interface)
GF CT
PHASE CT
2
1
B
Ordering Information
CATALOG/ SYSTEM NUMBER COMMUNICATIONS
PGR-6300-01-00 RS-485
PGR-6300-02-00 RS-485 & DeviceNet
PGR-6300-03-00 RS-485 & Profibus
PGR-6300-04-00 RS-485 & Ethernet
ACCESSORIES REQUIREMENT PAGE
PGC 2000 Series Required 38
PGC Family Required 38
PGA-0120 Optional 41
PGA-0140 Optional 41
49, 51
Extends motor life and prevents insulation failures and fires
46 Prevents overheating and extends motor life
50, 51 Prevents catastrophic failures and fires and extends motor life
37 Detects low-level or no-load conditions
50G/N, 51G/N Prevents catastrophic failures and fires
38, 49
Optional RTD temperature protection (PGA-0120 module) for high ambient or loss of ventilation protection
59 Prevents stress to insulation 27 Prevents a start attempt when it will damage the motor 47 Detects unhealthy supply voltage 87 Provides sensitive protection for high-resistance winding faults
Provides protection through starting, running, overload, and cooling cycles Minimizes Arc-Flash hazards during maintenance Simplifies the installation by reducing component count Displays the measured and calculated motor parameters On-board 64-event recorder helps with system diagnosis Remotely view measured values, event records & reset trips Internal circuits are conformally coated to protect against corrosion and moisture
Specifications
Protective Functions (IEEE Device Numbers)
C
Input Voltage 65 – 265 Vac, 25 VA; 80-275 Vdc, 25 W Power-Up Time 800 ms at 120 Vac Ride-Through Time 100 ms minimum 24-Vdc Source 100 mA maximum AC Measurements True RMS and DF T, Peak, 16 samples/cycle, and
positive and negative sequence of fundamental
Frequency 50, 60 Hz or ASD Inputs Phase-current, Earth-leakage current, Phase-voltage,
7 digital, tachometer, 1 analog
Output Contacts 5 contacts — See Product Manual Approvals CSA certified to US and Canadian standards Communications Allen-Bradley
DeviceNet™, Profibus
Conformally Coated Standard feature Warranty 10 years Mounting (Control Unit) Surface (Operator Interface) Panel
®
M
RTD
POWR-GARD
PGA-0120
(Temperature Input Module)
®
Overload (49, 51) Phase reverse (current) (46 ) Overfrequency (81) Overcurrent (50, 51) Jam Underfrequency (81) Ground fault (50G/N, 51G/N) Undercurrent (37) Unbalance (voltage) (47) Failure to accelerate RTD temperature (38, 49)
®
DFI and Modbus® RTU (Standard);
®
, Ethernet (Optional)
MOTOR PROTECTION RELAYS
Unbalance (current) (46 ) Underspeed (14) Starts per hour (66) Phase loss (voltage) (47) Overvoltage (59) Differential (87) Phase loss (current) (46) Undervoltage (27) Phase reverse (voltage) (47) Power factor ( 55)