POWR-GARD® Protection Relays, Monitors & Systems
POWR-GARD® Protection Relays, Monitors & Systems
Motor Protection – Advanced (PGR 6000 Family)
PGR-6200 SERIES
Motor Protection Relay
Description
The PGR-6200 Motor Protection Relay offers enhanced
motor protection and metering to provide diagnostic and
troubleshooting capabilities for critical process motors. The
PGR-6200 is used to provide current- and temperature-based
protection, metering, and data logging for three-phase lowvoltage medium-horsepower induction motors. This relay is
ideal for retrofitting and upgrading motor protection using
existing CTs. See the PGK Family of Panel Mount Adapter Kits
to replace common obsolete relays.
Motor Protection Relay
1
Three ac-current inputs
1
MOTOR PROTECTION RELAYS
Earth-leakage-CT input
Programmable digital input
24-Vdc source for digital input
Programmable 4 – 20-mA analog output
Ω
Temperature-sensor input, 100-
-Platinum RTD or PTC
Three programmable output relays
Local RS-232 communications, optional Network Communications
PC-interface software
4 line x 20 character backlit LCD display
Keypad for programming and display selection
4 LEDs; 1 user programmable
2
Wiring Diagram
POWR-GARD®POWR-GARD
PHASE CURRENT
TRANSFORMER
PGC 2000 SERIES PGC FAMILY
POWR-GARD®
CURRENT INPUT MODULE
PGA-0CIM
Included (See Ordering Info)
13 14 15 16 17
CIM
POWR-GARD®
MOTOR PROTECTION RELAY
PGR-6200 SERIES
RELAY 2
GROUND-FAULT
CURRENT TRANSFORMER
A B
TEMPERATURE INPUT
2
Current Input Module
The PGA-0CIM Current Input Module is the interface between
the PGR-6200 relay and the 5-A-secondary, 1-A-secondary, and
sensitive current transformers. The PGA-0CIM is included with
®
(required)(required)
POWR-GARD
TEMPERATURE
INPUT MODULE
PGA-0120
®
(optional)
C
POWR-GARD
DIFFERENTIAL
CURRENT MODULE
2
PGA-0140
®
(optional)
D
the PGR-6200 and can be surface or DIN-rail mounted.
Accessories
A
B
PGC-2000 Series Phase Current Transformers
Required CT detects phase current or groundfault current (200 A primary).
Other phase CTs can be used
PGC Family Ground-Fault Transformers
Required zero-sequence current transformers
detect ground-fault current. Available with 5-A and
30-A primary ratings for low-level pickup.
18
19
21 22 23 24
26 25
DIG IN
+
4-20 mA
ANALOG
OUTPUT
27 31
......
I/0 MODULE
C
PGA-0120 Temperature Input Module
Optional module provides 8 inputs to connect
Pt100, Ni100, Ni120, and Cu10 RTDs
D
PGA-0140 Differential Current Module
Optional motor differential protection,
RELAY 3
RELAY 1
compatible with core balance and summation
current transformer connections
12 11
10
9 8 7
5 4 3 2 1
6
CONTROL
1
POWER

POWR-GARD® Protection Relays, Monitors & Systems
Motor Protection – Advanced (PGR 6000 Family)
Features & Benefits
FEATURES IEEE # BENEFITS
Overload
Unbalance (Current)
RTD & PTC Overtemperature
Phase Loss/
Phase Reverse
(Current)
Overcurrent/Jam
Undercurrent
RTD Temperature
Starts Per Hour
Differential
Dynamic Thermal Model
Communications
Ground Fault
Reduced Overcurrent Mode
Metering
PGA-0CIM
Analog Output
Data Logging
Conformal Coating
46 Prevents overheating due to unbalanced phases
49
46 Detects unhealthy supply conditions
50, 51 Detects catastrophic failures and fires; extends motor life
37 Detects low level or no-load conditions
38, 49 Optional RTD temperature protection (PGA-0120 module) for high ambient or loss of ventilation protection
66 Limits the motor starts per hour to prevent overheating
87 Optional with PGA-0140 module allows sensitive winding-fault protection
50G/N, 51G/N Prevents catastrophic failures and fires
Extends motor life and prevents insulation failures and fires
Overtemperature (PTC) protection for high ambient or loss-of-ventilation detection
Provides protection through starting, running, and cooling cycles
Remotely view measured values, event records & reset trips
Minimizes Arc-Flash hazards during maintenance
Alphanumeric display of conditions
Separate current input module to reduce risk of CT hazard and for convenient installation
Provides means for metering selectable parameters
On-board 100-event recorder for data logging
Internal circuits are conformally coated to protect against corrosion and moisture
MOTOR PROTECTION RELAYS
Simplified Circuit Diagram
L1
L2
PHASE CT
A
POWR-GARD®
PGA-0CIM
(Current Input Module)
POWR-GARD
PGR-6200
(Motor Protection Relay)
PHASE CT
®
PHASE CT
1
GF CT
2
B
M
RTD
POWR-GARD®
PGA-0120
(Temperature Input Module)
C
Ordering Information
CATALOG/SYSTEM NUMBER
PGR-6200-00-00
PGR-6200-01-00
PGR-6200-02-00
PGR-6200-04-00
NOTE: The PGR-6200 consists of the Motor Protection Relay and the PGA-0CIM Current Input
Module. To order the relay only, add (-MPU) to the part number listed above.
ACCESSORIES REQUIREMENT PAGE
PGC Family Optional 38
PGA-0120 Optional 41
PGA-0140 Optional 41
PGK-0SMK Optional 41
COMMUNICATION
TIA-232
TIA-232 & RS-485
TIA-232 & DeviceNet™
TIA-232 & Ethernet
Specifications
Protective Functions
(IEEE Device Numbers)
Input Voltage 65 – 265 Vac, 25 VA; 80-275 Vdc, 25 W
Power-Up Time 800 ms at 120 Vac
Ride-Through Time 100 ms minimum
24-Vdc Source 100 mA maximum
AC Measurements True RMS and DF T, Peak, 16 samples/cycle, and
positive and negative sequence of fundamental
Frequency 50, 60 Hz or ASD
Inputs Phase-current, Earth-leakage current, Phase-voltage,
PTC-thermistor, 4 – 20 mA, programmable
Output Contacts Five contact relays — See Product Manual
Approvals CSA certified to US and Canadian standards
Communications RS-485 with Allen-Bradley
(Standard); DeviceNet™, Profibus
Conformally Coated Standard feature
Warranty 10 years
Mounting
(Control Unit) Panel (standard)
Surface (with PGK-0SMK converter kit)
(Current Input Module) DIN, Surface
Overload (49, 51)
Phase reverse (current) (46 )
Overcurrent (50, 51)
Jam
Ground fault (50G/N, 51G/N)
Undercurrent (37)
PTC overtemperature (49)
RTD temperature (38, 49)
Unbalance (current) (46 )
Starts per hour (66)
Phase loss (voltage) (47)
Overvoltage (59)
Differential (87)
Phase loss (current) (46)
®
DFI and Modbus® RTU
®
, Ethernet (Optional)