Littelfuse PGR-6101 User Manual

Tel: +1-800-832-3873
E-mail: techline@littelfuse.com
www.littelfuse.com
PGR-6101 MANUAL
GROUND-FAULT & INSULATION MONITOR
Revision 0-C-041918
Copyright © 2018 by Littelfuse, Inc.
All rights reserved.
Document Number: PM-1101-EN
PGR-6101 Ground-Fault & Insulation Monitor Page i
Rev. 0-C-041918
This page intentionally left blank.
PGR-6101 Ground-Fault & Insulation Monitor Page ii
Rev. 0-C-041918
TABLE OF CONTENTS
SECTION PAGE
1 General.......................................................................... 1
2 Operation...................................................................... 1
2.1 Output Relay Operating Mode .................................... 1
2.2 PGR-6101 Operating Mode......................................... 1
2.2.1 Online Operation ........................................... 1
2.2.2 Offline Operation .......................................... 1
2.3 Front-Panel Controls .................................................... 1
2.3.1 Ground-Fault Trip Level .............................. 1
2.3.2 Ground-Fault Trip Time ............................... 1
2.3.3 Insulation Resistance Response ................... 1
2.3.4 Reset ............................................................... 1
2.3.5 Test ................................................................. 2
2.4 Front-Panel Indication .................................................. 2
2.4.1 Power .............................................................. 2
2.4.2 >I .................................................................. 2
2.4.3 CT .................................................................. 2
2.4.4 Active ............................................................. 2
2.4.5 <R ................................................................... 2
2.5 Analog Outputs ............................................................. 2
2.5.1 OUT I ............................................................. 2
2.5.2 OUT R ............................................................ 2
2.6 Remote Test................................................................... 2
2.7 Remote Reset ................................................................ 2
2.8 CT Verification ............................................................. 2
3 Installation.................................................................... 2
3.1 PGH-5000 and PGH-6000 ........................................... 4
4 Technical Specifications ............................................. 8
4.1 PGR-6101 ...................................................................... 8
4.1.1 PGR-6101 Online Operation ....................... 8
4.1.2 PGR-6101 Offline Operation....................... 8
4.2 PGH High Tension Couplers ....................................... 9
5 Ordering Information ................................................ 9
6 Performance Tests .................................................... 10
6.1 Ground-Fault Test ....................................................... 10
6.2 Insulation Test ............................................................. 11
Appendix A PGR-6101 Revision History ......................... 12
LIST OF FIGURES
FIGURE PAGE
1 PGR-6101 Outline and Mounting Details .................. 3
2 Typical Connection Diagram ....................................... 4
3 PGC-5000-Series Current Sensors .............................. 5
4 PGH-5000 Outline and Mounting Details .................. 6
5 PGH-6000 Outline and Mounting Details .................. 7
6 PGA-0500 Analog Percent Current Meter ................. 9
7 PGA-0510 Analog Ohm Meter ................................. 10
8 Ground-Fault-Test Circuit .......................................... 11
LIST OF TABLES
TABLE PAGE
1 Ground-Fault-Test Record ......................................... 11
DISCLAIMER
Specifications are subject to change without notice. Littelfuse, Inc. is not liable for contingent or consequential damages, or for expenses sustained as a result of incorrect application, incorrect adjustment, or a malfunction.
PGR-6101 Ground-Fault & Insulation Monitor Page iii
Rev. 0-C-041918
This page intentionally left blank.
PGR-6101 Ground-Fault & Insulation Monitor Page 1
Rev. 0-C-041918
1. GENERAL
The PGR-6101 Ground-Fault & Insulation Monitor can detect a motor ground fault whether the motor is running (Online mode) or stopped (Offline mode), and can be used to protect a motor supplied by a solidly grounded, resistance-grounded, or ungrounded system. On an ungrounded system, use only the Offline mode. On grounded systems, a current transformer (CT) is used to detect ground-fault current as low as 30 mA when the motor is running, and insulation resistance is measured to detect a fault when the motor is stopped. Online or Offline mode is selected with a digital input connected to a starter auxiliary contact. In the Online mode, ground-fault current is sensed by a PGC-5000-series zero-sequence CT. The trip level of the ground-fault circuit is selectable from 30 to 200 mA. Trip time is selectable from <50 to 250 ms. Additional current­detection features include harmonic filtering, a relay output that can operate in the fail-safe or non-fail-safe mode, CT­connection detection, LED trip, power, and open-CT indication, autoreset or latching trips with front-panel and remote reset, a test button, and a 0- to 1-mA-analog output. In the Offline mode, insulation-resistance monitoring is enabled, with a selectable 60- to 600-k alarm-setting range. Additional insulation-monitoring features include a relay output that can operate in the fail-safe or non-fail-safe mode, LED active and low-resistance indication, and a 0­to 1-mA-analog output. The PGR-6101 can be directly connected to a supply up to 1.3 kV. For systems from 1.3 to 5 kV, use a PGH-5000 High Tension Coupler. For systems from 5 kV to 6 kV, use a PGH-6000 High Tension Coupler.
2. OPERATION
2.1 OUTPUT RELAY OPERATING MODE
In the fail-safe mode the output relays energize when power is applied and the ground-fault and insulation­resistance circuits are not tripped. Fail-safe mode is the factory setting. For non-fail-safe operation connect terminals 19-20 and 22-23. The respective output relay will energize when a fault occurs. See Fig. 2.
2.2 PGR-6101 OPERATING MODE
Connect terminals 27 and 28 to a normally closed (Form B) auxiliary starter contact. When terminals 27 and 28 are open, Online mode (insulation monitoring off) is selected and when terminals 27 and 28 are connected, Offline mode (insulation monitoring active) is selected.
2.2.1 ONLINE OPERATION
When the monitor is running, the PGR-6101 in conjunction with a PGC-5000-series zero-sequence current sensor operates as a sensitive ground-fault relay.
2.2.2 OFFLINE OPERATION
The PGR-6101 changes mode by means of an auxiliary contact on the main contactor when the motor is off. It becomes an insulation-resistance monitor and imposes a small dc voltage to the motor windings and supply cable from the motor starter. Leakage to ground is detected.
2.3 FRONT-PANEL CONTROLS
2.3.1 GROUND-FAULT TRIP LEVEL
The Leakage Current I selector switch is used to set the ground-fault trip level from 30 to 200 mA. For ground-fault detection, the switch setting must be set substantially below the prospective ground-fault current. To avoid sympathetic tripping, the switch setting must be above the charging current of the protected feeder.
2.3.2 GROUND-FAULT TRIP TIME
The PGR-6101 has a definite-time trip characteristic. In tripping systems, the TIME DELAY selector is used to set the ground-fault trip time for coordination with upstream and downstream ground-fault devices. Trip time is selectable from < 50 ms to 250 ms. Coordination requires the same trip level for all ground-fault devices in a system and the trip time to progressively increase upstream. The amount of equipment removed from the system will be a minimum if the first ground-fault device to operate is the one immediately upstream from the fault.
2.3.3 INSULATION RESISTANCE RESPONSE
The PGR-6101 insulation resistance function has an adjustable alarm range of 60 to 600 k. There is no selectable time delay. The unit will operate in less than three seconds.
2.3.4 RESET
The front-panel RESET button is used to reset latching trips. After a fault has been cleared, cycling the supply voltage will also reset the PGR-6101. To use the PGR-6101 in autoreset mode, connect terminals 18-19 and 21-22. See Fig. 2. The reset function is not instantaneous. Press the RESET button for several seconds.
Loading...
+ 11 hidden pages