Littelfuse PGR-6100 SERIES Catalog Page

Protection Relays & Controls
Motor Protection–Basic (PGR 6000 Family)
PGR-6100 SERIES (GFR4000)
Ground-Fault & Insulation Monitor
Simplified Circuit Diagram
A
A
GROUNDED
SUPPLY
B
C
L1
L2
Ordering Information
ORDERING NUMBER CONTROL POWER
PGR-6100-120 120 Vac
PGR-6100-240
ACCESSORIES REQUIREMENT
PGC-5000 Series Required
PGH Family Required >1300 V
PGA-0500 Optional
PGA-0510 Optional
Note (1) - PGR- 6100-24 0 ordering option is not UL Listed.
For optional conformal coating pl ease consult factory.
(1)
240 Vac
CT
D
PGR-6100 SERIES
(Ground-Fault & Insulation Monitor)
(1)
Description
The PGR-6100 combines the features of a ground-fault protection relay and insulation monitor into one unit. It protects against ground faults by monitoring insulation resistance when the motor is de-energized and by monitoring ground-fault current when the motor is energized. The PGR-6100 features two separate analog outputs for optional current and ohm meters, and two separate alarm relays. It operates on one- or three-phase solidly grounded, resistance grounded and ungrounded systems up to 6 kV.
Features & Benefits
FEATURES BENEFITS
Adjustable GF pickup (10 mA - 3 A)
Adjustable insulation pickup (250 kΩ - 2 MΩ)
Adjustable time delay (50 ms - 1.0 s)
Output contacts
Analog outputs (0 - 1 mA)
CT-Loop monitoring Alarms when CT is not connected
Selectable contact operating mode
Trip setting provides a wide range of low-level protection and system coordination
Customizable insulation resistance setpoints for maximum protection
Adjustable trip delay for quick protection and system coordination
Two Form C output contacts for ground fault and insulation-resistance fault
Two analog outputs indicate insulation resistance and ground-fault current
Selectable fail-safe or non-fail-safe operating modes allows connection to shunt or undervoltage breaker coil
Accessories
A
B
C
D
PGC-5000 Series Ground-Fault Transformers
Required zero-sequence current transformer specifically designed for low level detection. Flux conditioner is included to prevent saturation.
PGA-0500 Analog % Current Meter PGA-0510 Analog Ohm Meter
Optional panel-mounted meters display ground-fault current as a percentage of the set-point and insulation resistance.
PGH Family High Tension Couplers
Required (for systems >1,300 V) PGH Family high-tension coupler must be connected between the phase conductor and the PGR-6100.
Specifications
IEEE Device Numbers Ground Fault (50G/N, 51G/N), Ground detector (64), Alarm Relay (74)
Input Voltage See ordering information Dimensions H 75 mm (3”); W 100 mm (3.9”); D 115 mm (4.5”) Response delay < 250 ms Contact Operating Mode Selectable fail-safe or non-fail-safe Harmonic Filtering Standard feature Test Button Standard feature Reset Button Standard feature CT-Loop Monitoring Standard feature Output Contacts Two Form C Analog Output 0-1 m A Approvals UL Listed (E183688) Warranty 5 years Mounting DIN, Surface