Littelfuse PGR-6100 Users Manual

Ground-Fault & Insulation Monitor PGR-6100
PGR-6100 MANUAL
Revision 2-B-111014
Document Number: PM-1100-EN Printed in Canada.
Copyright © 2014 by Littelfuse, Inc.
All rights reserved.
Page i PGR-6100 Ground-Fault & Insulation Monitor Rev. 2-B-111014
This page intentionally left blank.
Page ii PGR-6100 Ground-Fault & Insulation Monitor Rev. 2-B-111014

TABLE OF CONTENTS

SECTION PAGE
1 General ....................................................................... 1
2 Operation ................................................................... 1
2.1 Output Relay Operating Mode ................................... 1
2.2 PGR-6100 Operating Mode ....................................... 1
2.2.1 Online Operation ............................................ 1
2.2.2 Offline Operation ........................................... 1
2.3 Front-Panel Controls .................................................. 1
2.3.1 Ground-Fault Trip Level ................................ 1
2.3.2 Ground-Fault Trip Time ................................ 1
2.3.3 Insulation Resistance Response ..................... 1
2.3.4 Reset ................................................................ 1
2.3.5 Test .................................................................. 2
2.4 Front-Panel Indication ................................................ 2
2.4.1 Power .............................................................. 2
2.4.2 >I .................................................................. 2
2.4.3 CT .................................................................. 2
2.4.4 Active .............................................................. 2
2.4.5 <R .................................................................... 2
2.5 Analog Outputs ........................................................... 2
2.5.1 Out I ................................................................ 2
2.5.2 Out R ............................................................... 2
2.6 Remote Test ................................................................ 2
2.7 Remote Reset .............................................................. 2
2.8 CT Verification ........................................................... 2
3 Installation ................................................................. 2
3.1 PGH-5000 and PGH-6000 ......................................... 4
4 Technical Specifications .......................................... 8
4.1 PGR-6100 ................................................................... 8
4.1.1 PGR-6100 Online Operation ......................... 8
4.1.2 PGR-6100 Offline Operation ......................... 8
4.2 PGH High Tension Couplers ..................................... 9
5 Ordering Information .............................................. 9
6 Tests ........................................................................ 10
6.1 Ground-Fault Test .................................................... 10
6.2 Insulation Test .......................................................... 11
Appendix A PGR-6100 Revision History ........................ 12
FIGURE PAGE
1 PGR-6100 Outline and Mounting Details ................. 3
2 Typical Connection Diagram ..................................... 4
3 PGC-5000-Series Current Sensors ............................ 5
4 PGH-5000 Outline and Mounting Details ................ 6
5 PGH-6000 Outline and Mounting Details ................ 7
6 PGA-0500 Analog Percent Current Meter ................ 9
7 PGA-0510 Analog Ohm Meter ............................... 10
8 Ground-Fault-Test Circuit ....................................... 11
T
ABLE PAGE
1 Ground-Fault-Test Record ....................................... 11
Specifications are subject to change without notice. Littelfuse, Inc. is not liable for contingent or consequential damages, or for expenses sustained as a result of incorrect application, incorrect adjustment, or a malfunction.

LIST OF FIGURES

LIST OF TABLES

DISCLAIMER
Page iii PGR-6100 Ground-Fault & Insulation Monitor Rev. 2-B-111014
This page intentionally left blank.
Page 1
PGR-6100 Ground-Fault & Insulation Monitor Rev. 2-B-111014

1. GENERAL

2.2.1 O
NLINE OPERATION
In Online mode, the PGR-6100 in conjunction with a
The PGR-6100 Ground-Fault & Insulation Monitor can detect a motor ground fault whether the motor is running (Online mode) or stopped (Offline mode), and can be used to protect a motor supplied by a solidly grounded, resistance-grounded, or ungrounded system. On an ungrounded system, use only the Offline mode. On grounded systems, a current transformer (CT) is used to detect ground-fault current as low as 10 mA when the motor is running. Insulation resistance is measured to detect a fault when the motor is stopped. Online or Offline mode is selected with a digital input connected to a starter auxiliary contact. In the Online mode, ground-fault current is sensed by a PGC-5000-series zero-sequence CT. The trip level of the ground-fault circuit is selectable from 10 mA to 3 A. Trip time is selectable from <50 ms to 10 s. Additional current-detection features include harmonic filtering, a relay output that can operate in the fail-safe or non-fail­safe mode, CT-connection detection, LED trip, LED power, and LED open-CT indication, autoreset or latching trips with front-panel and remote reset, a test button, and a 0- to 1-mA-analog output. In the Offline mode, insulation-resistance monitoring is enabled with a selectable 250-k to 2-M alarm-setting range. Additional insulation-monitoring features include a relay output that can operate in the fail-safe or non-fail­safe mode, LED active and low-resistance indication, and a 0- to 1-mA-analog output. The PGR-6100 can be directly connected to a supply up to 1.3 kV. For systems from 1.3 to 5 kV, use a PGH­5000 High Tension Coupler. For systems from 5 kV to 6 kV, use a PGH-6000 High Tension Coupler.

2. OPERATION

2.1 OUTPUT RELAY OPERATING MODE

In the fail-safe mode the output relays energize when power is applied and the ground-fault and insulation­resistance circuits are not tripped. Fail-safe mode is the factory setting. For non-fail-safe operation connect terminals 19-20 and 22-23. The respective output relay will energize when a fault occurs. See Fig. 2.
2.2 PGR-6100 O
Connect terminals 27 and 28 to a normally closed (Form B) auxiliary starter contact. When terminals 27
PERATING MODE
PGC-5000-series zero-sequence current sensor operates as a ground-fault relay.
2.2.2 O
FFLINE OPERATION
The PGR-6100 changes mode by means of an auxiliary contact on the main contactor when the motor is off. It becomes an insulation-resistance monitor and imposes a small dc voltage to the motor windings and supply cable from the motor starter. Leakage to ground is detected.
RONT-PANEL CONTROLS
2.3 F
2.3.1 G
ROUND-FAULT TRIP LEVEL
The Leakage Current I selector switch is used to set the ground-fault trip level from 10 mA to 3 A. For ground­fault detection, the switch setting must be set substantially below the prospective ground-fault current. To avoid sympathetic tripping, the switch setting must be above the charging current of the protected feeder.
2.3.2 G
ROUND-FAULT TRIP TIME
The PGR-6100 has a definite-time trip characteristic. In tripping systems, the TIME DELAY selector is used to set the ground-fault trip time for coordination with upstream and downstream ground-fault devices. Trip time is selectable from < 50 ms to 1.0 s. Coordination requires the same trip level for all ground-fault devices in a system and the trip time to progressively increase upstream. The amount of equipment removed from the system will be a minimum if the first ground-fault device to operate is the one immediately upstream from the fault.
2.3.3 I
NSULATION RESISTANCE RESPONSE
The PGR-6100 insulation resistance function has an adjustable alarm range of 250 k to 2 M. There is no selectable time delay. The unit will operate in less than three seconds.
2.3.4 R
ESET
The front-panel RESET button is used to reset latching trips. After a fault has been cleared, cycling the supply voltage will also reset the PGR-6100. To use the PGR-6100 in autoreset mode, connect terminals 18-19 and 21-22. See Fig. 2. The reset function is not instantaneous. Press the RESET button for several seconds.
and 28 are open, Online mode is selected (insulation monitoring off). When terminals 27 and 28 are connected, Offline mode is selected (insulation monitoring active).
Loading...
+ 11 hidden pages