Littelfuse PGR-4300 Users Manual

Generator Ground-Fault Relay PGR-4300
PGR-4300 MANUAL
REVISION 3-A-073115
Document Number: PM-1030-EN Printed in Canada.
Copyright © 2015 by Littelfuse, Inc.
All rights reserved.
Page i
PGR-4300 Generator Ground-Fault Relay Rev. 3-A-073115
This page intentionally left blank.
Page ii

TABLE OF CONTENTS

SECTION PAGE
1 General ....................................................................... 1
2 Operation ................................................................... 1
2.1 System Selection ........................................................ 1
2.2 Front-Panel Controls .................................................. 1
2.2.1 Ground-Fault Trip Level ................................ 1
2.2.2 Ground-Fault Trip Time ................................ 1
2.2.3 Reset ................................................................ 1
2.2.4 Test .................................................................. 1
2.3 Front-Panel Indication ................................................ 1
2.3.1 Power .............................................................. 1
2.3.2 >I .................................................................. 1
2.3.3 N-G ................................................................ 1
2.4 Analog Output ............................................................ 3
2.5 Remote Reset .............................................................. 3
2.6 Relay Operating Mode ............................................... 3
3 Installation ................................................................. 3
4 Technical Specifications .......................................... 7
5 Ordering Information .............................................. 7
6 Warranty ................................................................... 7
7 Performance Test ..................................................... 8
Appendix A PGR-4300 Revision History .......................... 9
PGR-4300 Generator Ground-Fault Relay Rev. 3-A-073115

LIST OF FIGURES

FIGURE PAGE
1 PGR-4300 Outline and Mounting Details ................. 2
2 Three-Pole Transfer Switch Typical Connection
Diagram ...................................................................... 3
3 Four-Pole Transfer Switch Typical Connection
Diagram ...................................................................... 4
4 PGA-0500 Analog Percent Current Meter ................ 4
5 PMA-55 Panel-Mount Adapter ................................. 5
6 PMA-60 Panel-Mount Adapter ................................. 6
7 PGR-4300 Performance Test Circuit ......................... 8

LIST OF TABLES

TABLE PAGE
1 Ground-Fault-Test Record ......................................... 8
DISCLAIMER
Specifications are subject to change without notice. Littelfuse, Inc. is not liable for contingent or consequential damages, or for expenses sustained as a result of incorrect application, incorrect adjustment, or a malfunction.
Page iii
PGR-4300 Generator Ground-Fault Relay Rev. 3-A-073115
This page intentionally left blank.
Page 1
PGR-4300 Generator Ground-Fault Relay Rev. 3-A-073115
RONT-PANEL CONTROLS

1. GENERAL

2.2 F

2.2.1 GROUND-FAULT TRIP LEVEL

The PGR-4300 Generator Ground-Fault Relay provides a simple method for detecting a ground-fault condition on a generator-supplied system, without the need for a current transformer. It continuously monitors for ground-fault current and neutral-to-ground continuity. It can be applied on a three phase system with a three­pole or four-pole transfer switch and can be used in a dedicated generator application. In a three-pole transfer-switch application, the generator neutral and system neutral are connected to ground at the service entrance. The connection between the generator neutral and service-entrance ground is assumed to have a resistance of 2 m and voltage across this conductor is measured to calculate ground-fault current. See Fig. 2. The selection of a neutral-bonding conductor can be made using NEC 250.102(D) and
250.122, and calculating the conductor length needed for a 2 m resistance. In a four-pole transfer-switch application the ground connection to earth is at the generator. See Fig. 3. The resistance of the bonding cable between the generator neutral and ground is assumed to have a resistance of 0.2 m. The voltage across this conductor is measured to calculate ground-fault current. A 0.9 m (3’) length of AWG 3/0 copper cable is recommended per NEC
250.102(C). In a dedicated generator application, to ensure proper operation of the PGR-4300 there can be only one ground connection to earth. If the earth connection is at the generator, configure the PGR-4300 as a four-pole system. If the earth connection is at the load or service entrance, configure as a three-pole system. The PGR-4300 has one output relay with normally open / normally closed contacts for use in a control circuit. Additional features include LED trip and power indication, front-panel and remote reset, 0- to 1-mA analog output, a level-selector switch, and a trip-time setting. An epoxy-filled enclosure provides the PGR-4300 protection against vibration. The trip level of the ground-fault circuit is switch selectable from 100 to 1,200 A. Trip time is selectable from 0 to 1.0 s.

2. OPERATION

YSTEM SELECTION
2.1 S
For a four-pole system, connect terminals 11 and 12. For a three-pole system, leave terminals 11 and 12 open.
The I selector switch is used to set the ground-fault trip level from 100 to 1,200 A. Unbalanced single-phase currents returning through the bonding conductor will appear as ground-fault current. To avoid nuisance tripping, set the trip-level setting above these currents.
2.2.2 G
ROUND-FAULT TRIP TIME
The PGR-4300 has a definite-time trip characteristic. In tripping systems, the TIME DELAY selector is used to set the ground-fault trip time for coordination with downstream ground-fault devices. Trip time is selectable from 0 to 1.0 s. Coordination requires the same trip level for all ground-fault devices in a system and the trip time to progressively increase upstream. The amount of equipment removed from the system will be a minimum if the first ground-fault device to operate is the one immediately upstream from the fault.
2.2.3 R
ESET
The front-panel RESET button is used to reset latching trips. When remote-reset terminals 4 and 5 are connected, a trip remains latched until the RESET button is pressed or the remote-reset terminals are opened. Cycling the supply voltage will also reset the PGR-4300. If the remote-reset terminals are not connected, the PGR-4300 operates in the non-latching mode and a trip will reset when the fault is removed.
2.2.4 T
EST
The TEST button is used to test the ground-fault circuit, the indication, and the output relay. When the TEST button is pressed, the circuit will trip, the >ΔI LED will light, the output relay will energize, and the analog output will indicate full scale (1 mA).

2.3 FRONT-PANEL INDICA TION

2.3.1 POWER

The green LED labelled PWR indicates the presence of supply voltage.
2.3.2 >I
The red LED labelled >I indicates a ground-fault trip. It also lights when the neutral connection is open.

2.3.3 N-G

The red LED labelled N-G indicates a neutral-to­ground trip. When continuity between the generator neutral and ground is broken, the N-G and >I LED’s will be on and the output relay will be energized.
Loading...
+ 9 hidden pages