Littelfuse PGR-4300 User Manual

Protection Relays & Controls
Generator & Single-Function Protection–Ground Fault
PGR-4300 SERIES (GFA300)
Generator Ground-Fault Relay
Simplified Circuit Diagram
G
Description
The PGR-4300 Generator Ground-Fault Relay provides a simple method for detecting a ground-fault condition on generators without the need for current transformers (CTs). This greatly simplifies the installation. In addition, it is compatible with both three- and four-pole transfer switches. This relay also monitors the neutral-to-ground path for continuity. The PGR-4300 is ideal for any generator or application where there is not sufficient space to install CTs.
Features & Benefits
FEATURES BENEFITS
No CTs required Saves space and simplifies installation
Adjustable pickup (100 - 1200 A)
Adjustable time delay (0 - 1.0 s)
Output contacts
Analog output (0 - 1 mA)
N-G continuity alarm
Passive filtering Eliminates nuisance tripping
Adjustable trip setting provides a wide range of protection and allows system coordination
Adjustable trip delay allows quick protection and system coordination
Form C ground-fault output contacts for alarming or tripping purposes
Provides means for connecting to an optional meter (PGA-0500) or control system
Monitors neutral-to-ground integrity and alarms if ground path becomes open circuit
PGR-4300
(Generator Ground-Fault Relay)
Ordering Information
ORDERING NUMBER CONTROL POWER
PGR-4300-12 12 Vdc
PGR-4300-24 24 Vdc
ACCESSORIES REQUIREMENT
PGA-0500 Optional
PMA-55 Optional
PMA-60 Optional
Note: For o ptional conforma l coating please consult factory.
Accessories
PGA-0500 Analog % Current Meter
Optional panel-mounted analog meter displays ground-fault current as a percentage of the set-point.
Specifications
IEEE Device Numbers Ground Fault (50G/N, 51G/N) Input Voltage See ordering information Dimensions H 75 mm (3.0”); W 55 mm (2.2”); D 115 mm (4.5”) Trip Level Settings 100-1200 A Trip Time Delay Settings 0-1.0 s Contact Operating Mode Non-fail-safe Test Button Local Reset Button Local and remote Output Contacts Form C Approvals UL Listed Analog Output 0-1 mA Conformally Coated Consult factory Warranty 5 years Mounting DIN, Surface (standard)
Panel (with PMA-55 or PMA-60 adapter)
© 2013 Littelfuse Protection Relays & Controls Littelfuse.com/pgr-4300