Protection Relays & Controls
Generator & Single-Function Protection–Ground Fault
PGR-4300 SERIES (GFA300)
Generator Ground-Fault Relay
Simplified Circuit Diagram
G
Description
The PGR-4300 Generator Ground-Fault Relay provides
a simple method for detecting a ground-fault condition
on generators without the need for current transformers
(CTs). This greatly simplifies the installation. In addition,
it is compatible with both three- and four-pole transfer
switches. This relay also monitors the neutral-to-ground path
for continuity. The PGR-4300 is ideal for any generator or
application where there is not sufficient space to install CTs.
Features & Benefits
FEATURES BENEFITS
No CTs required Saves space and simplifies installation
Adjustable pickup
(100 - 1200 A)
Adjustable time delay
(0 - 1.0 s)
Output contacts
Analog output
(0 - 1 mA)
N-G continuity alarm
Passive filtering Eliminates nuisance tripping
Adjustable trip setting provides a wide range of
protection and allows system coordination
Adjustable trip delay allows quick protection and
system coordination
Form C ground-fault output contacts for alarming
or tripping purposes
Provides means for connecting to an optional
meter (PGA-0500) or control system
Monitors neutral-to-ground integrity and alarms if
ground path becomes open circuit
PGR-4300
(Generator
Ground-Fault Relay)
Ordering Information
ORDERING NUMBER CONTROL POWER
PGR-4300-12 12 Vdc
PGR-4300-24 24 Vdc
PGR-4300-120 120 Vac
ACCESSORIES REQUIREMENT
PGA-0500 Optional
PMA-55 Optional
PMA-60 Optional
Note: For o ptional conforma l coating please consult factory.
Accessories
PGA-0500 Analog % Current Meter
Optional panel-mounted analog meter
displays ground-fault current as a
percentage of the set-point.
Specifications
IEEE Device Numbers Ground Fault (50G/N, 51G/N)
Input Voltage See ordering information
Dimensions H 75 mm (3.0”); W 55 mm (2.2”); D 115 mm (4.5”)
Trip Level Settings 100-1200 A
Trip Time Delay Settings 0-1.0 s
Contact Operating Mode Non-fail-safe
Test Button Local
Reset Button Local and remote
Output Contacts Form C
Approvals UL Listed
Analog Output 0-1 mA
Conformally Coated Consult factory
Warranty 5 years
Mounting DIN, Surface (standard)
Panel (with PMA-55 or PMA-60 adapter)
© 2013 Littelfuse Protection Relays & Controls
Littelfuse.com/pgr-4300
Rev: 4-A-050213
Based on Manual Rev 3