Ground-Fault Protection – Ungrounded AC System
PGR-3200 SERIES
Ground-Fault Protection System
Description
The PGR-3200 detects ground faults by continuously monitoring the insulation integrity of ungrounded electrical systems. The relay monitors the insulation for damage and assists with predictive maintenance and troubleshooting of developing ground faults by providing two warning and an alarm level. The PGR-3200 operates on one- or three-phase ungrounded systems up to 6 kV.
The PGR-3200 can also be used on a grounded system to monitor the insulation for damage, while the power system is de-energized. The mode-of-operation terminals (27-28) are connected to the circuit breaker or contactor auxiliary contacts to toggle the relay off when the contactor or breaker is closed.
Simplified Circuit Diagram
A
B
C
A
PGR-3200
L1
(Ground-Fault Protection System)
L2
Ordering Information
ORDERING NUMBER CONTROL POWER
PGR-3200
PGR-3200-120
ACCESSORIES REQUIREMENT
PGH Series Required >1,300 V
PGA-0510 Optional
Note: Fo r optio nal conformal coating please consu lt factory. To convert to a res istance grounded system, see neutral-grounding-resistors packages.
240 Vac
120 Vac
Features & Benefits
FEATURES BENEFITS
Meets National Electrical Code (NEC
NEC® and CEC Code compliant
Output contact (50 k
Ω
)
Output contact
Ω
)
(10 k
Analog output (0 - 1 mA)
DIN-rail or surface mount
250.21(B) and Canadian Electrical Code Part 1, Section 10-106 (2) requirements for ungrounded systems
Form C output contact for alarming when the insulation resistance is below 50 k
Form C output contact for tripping when the insulation resistance is below 10 k
Provides means for connecting to an optional meter (PGA-0510) or control system
Flexible options for ease of installation
Ω
Ω
®
) Article
Accessories
A
PGH Series High-Tension Coupler
A PGH Series high-tension coupler is required for systems between 1,300 V and 6,000 V.
PGA-0510 Analog Ohm Meter
Optional PGA-0510 Analog Meter allows for metering of insulation resistance.
Specifications
IEEE Device Numbers Undervoltage Relay (27) Ground Detector Relay (64)
Input Voltage Dimensions H 75 mm (3”); W 100 mm (3.9”); D 110 mm (4.3”) Resistance Ratings Insulation warning (30 k
Contact Operating Mode Non-fail-safe Tes t Bu t ton Local Reset Button Local and remote Output Contacts Two Form C Analog Output 0-1 m A Conformally Coated Consult factory Warranty 5 years Mounting DIN, Surface
See ordering information
Insulation alarm (10 k
Ω
)
Ω
and 50 kΩ)