Littelfuse MPU-32 User Manual

Protection Relays & Controls
Motor Protection–Advanced
MPU-32 SERIES (PGR-6200)
Motor Protection Unit
1
2
Simplified Circuit Diagram
PHASE CT
A
PHASE CT
MPU-CIM
(Current Input Module)
MPU-32
L1
L2
(Motor Protection Relay)
PHASE CT
GF CT
2
1
B
MPS-RTD
(Temperature Input Module)
M
RTD x 8
C
Description
The MPU-32 Motor Protection Unit is used to provide current­and temperature-based protection, metering, and data logging for three-phase low-voltage medium-horsepower induction motors. This relay is ideal for retrofitting and upgrading obsolete or aging motor protection using existing CTs. See the PMA Family of Panel Mount Adapter Kits to replace common obsolete relays.
1
Motor Protection Unit
g
Three ac-current inputs
g
Earth-leakage-CT input
g
Programmable digital input
g
24-Vdc source for digital input
g
Programmable 4-20-mA analog output
g
On-board temperature-sensor input,
g
100-Ω-Platinum RTD or PTC
g
Three programmable output relays
g
Local RS-232 communications, optional Network Communications
g
PC-interface software (SE-Comm-RIS)
g
4 line x 20 character backlit LCD display
g
Keypad for programming and display selection
g
4 LEDs; 1 user programmable
2
Current Input Module (MPU-CIM)
The MPU-CIM Current Input Module is the interface between the MPU-32 relay and the 5-A-secondary, 1-A-secondary, and sensitive current transformers. The MPU-CIM is ordered separately from the MPU-32 and can be surface- or DIN-rail mounted. Wire-clamping terminals are standard but the MPU-CTI is available for those who require ring-tongue terminals.
Accessories
A
Phase Current Transformers
Phase CTs are required to detect phase currents. For upgrade applications, existing CTs can be used.
Ordering Information
ORDERING NUMBER COMMUNICATION
MPU-32-00-00 TIA-232
MPU-32-01-00 TIA-232 & TIA-485
MPU-32-02-00 TIA-232 & DeviceNet™
MPU-32-04-00 TIA-232 & EtherNet/IP™ & Modbus® TCP
NOTE: One of the following is required: MPU-CIM-00-00 Current Input Module, or
MPU-CTI-RT-00 Current Input Module with ring-tonque terminals.
ACCESSORIES REQUIREMENT
Phase CTs Required
MPS-RTD-01-00 Optional
MPS-DIF-01-00 Optional
MPU-32-SMK Optional
CA-945 Optional
MPU-16A-Y92A-96N Optional
© 2013 Littelfuse Protection Relays & Controls Littelfuse.com/mpu-32
B
Ground-Fault Current Transformer
Optional zero-sequence current transformer detects ground-fault current. Available with 5-A and 30-A primary ratings for low-level pickup.
C
MPS-RTD Temperature Input Module
Optional module provides 8 inputs to connect Pt100, Ni100, Ni120, and Cu10 RTDs.
D
MPS-DIF Differential Current Module
Optional motor differential protection, compatible with core balance and summation current transformer connections.
Rev: 4-A-050213
Based on Manual Rev 4
Protection Relays & Controls
Motor Protection–Advanced
MPU-32 SERIES (PGR-6200)
Motor Protection Unit
Features & Benefits
FEATURES IEEE # BENEFITS
Overload Dynamic thermal model Communications Ground fault Current unbalance/
Phase loss/Phase reverse RTD temperature Phase loss/Phase reverse (current) Overcurrent Jam Undercurrent PTC overtemperature Starts per hour Differential Reduced overcurrent mode Metering MPU-CIM Analog output Data logging Conformal coating
49, 51
50G/N, 51G/N
46
38, 49
46
50, 51
37 49 66 87
Extends motor life and prevents insulation failures and fires Provides protection through starting, running, and cooling cycles Remotely view measured values and event records, reset trips, and access setpoints Prevents catastrophic failures and fires
Prevents overheating due to unbalanced phases
RTD temperature protection (MPS-RTD module) for high-ambient or loss-of-ventilation protection Detects unhealthy supply conditions Prevents catastrophic failures and fires; extends motor life Prevents motor damage by detecting mechanical jams or excessive loading Detects low level or no-load conditions Overtemperature (PTC) protection for high-ambient or loss-of-ventilation detection Limits the motor starts per hour to prevent overheating Optional MPS-DIF module for sensitive winding-fault protection Minimizes arc-flash hazards during maintenance View measured and calculated parameters with on-board display Separate current input module to reduce risk of open-CT hazard and for convenient installation Provides means for metering selectable parameters On-board 100-event recorder for data logging Internal circuits are conformally coated to protect against corrosion and moisture
Wiring Diagram
PHASE CURRENT TRANSFORMERS
(required)
MPU-CIM
CURRENT INPUT MODULE
13 14 15 16 17
CIM
MOTOR PROTECTION UNIT
MPU-32
RELAY 2
12 11
GROUND-FAULT CURRENT TRANSFORMER
(recommended)
A B
2
TEMPERATURE INPUT
9 8 7
10
18
RELAY 1
19
21 22 23 24
26 25
DIG IN
RELAY 3
5 4 3 2 1
6
MPS-RTD
INPUT MODULE
(optional)
MPS-DIF
DIFFERENTIAL MODULE
(optional)
+
4-20 mA ANALOG OUTPUT
C
D
27 31
......
I/0 MODULE
Specifications
Protective Functions (IEEE Device Numbers)
Input Voltage 65-265 Vac, 25 VA; 80-275 Vdc, 25 W Power-Up Time 800 ms at 120 Vac Ride-Through Time 100 ms minimum 24-Vdc Source 100 mA maximum AC Measurements True RMS and DF T, Peak, 16 samples/cycle, and
positive and negative sequence of fundamental
Frequency 50, 60 Hz or ASD Output Contacts Three Form C programmables Communications TIA-232 (standard); TIA- 485, DeviceNet™, Ethernet (optional) Analog Output 4-20 mA, programmable Conformally Coated Standard feature Warranty 10 years Mounting
(Control Unit) Panel (standard) Surface (with MPU-32-SMK converter kit) (Current Input Module) DIN, Surface Approvals CSA certified, CE (European Union),
1
C-Tick ( Australian)
Overload (49, 51) Phase reverse (current) (46) Overcurrent (50, 51) Jam Ground fault (50G/N, 51G/N) PTC overtemperature (49
RTD temperature (38, 49) Unbalance (current) (46) Starts per hour (66) Differential (87) Phase loss (current) (46) Undercurrent (37)
© 2013 Littelfuse Protection Relays & Controls Littelfuse.com/mpu-32