Littelfuse MPS User Manual

MPS MANUAL
MOTOR PROTECTION SYSTEM
Revision 6-F-022117
Copyright © 2017 by Littelfuse Startco
All rights reserved.
Document Number: PM-1130-EN
Factory default password is 1111
New Password
See Section 4.3.6.
Motor Identification
Page ii MPS Motor Protection System Rev. 6-F-022117
. Table of Contents
TABLE OF CONTENTS
SECTION PAGE
List of Figures ....................................................................... iv
List of Tables ........................................................................ iv
Disclaimer .............................................................................. v
1 Introduction .......................................................... 1-1
1.1 General .................................................................... 1-1
1.2 MPS Features .......................................................... 1-1
1.2.1 Protection .................................................... 1-1
1.2.2 Control – Starting Methods ........................ 1-1
1.2.3 Metering ...................................................... 1-1
1.2.4 Data Logging .............................................. 1-1
1.2.5 Inputs and Outputs ...................................... 1-1
1.2.6 MPS-OPI Operator Interface ..................... 1-2
1.2.7 MPS-RTD Module ..................................... 1-2
1.2.8 MPS-DIF Differential Module ................... 1-2
1.2.9 Communications Interface ......................... 1-2
1.3 Ordering Information .............................................. 1-2
2 Installation ............................................................. 2-1
2.1 General .................................................................... 2-1
2.2 MPS-CTU Control Unit ......................................... 2-1
2.3 MPS-OPI Operator Interface .................................. 2-1
2.4 MPS-RTD Module ................................................. 2-1
2.5 MPS-DIF Differential Module ............................... 2-1
2.6 Earth-Fault CT’s ..................................................... 2-1
3 System Wiring ....................................................... 3-1
3.1 General .................................................................... 3-1
3.2 Wiring Connections ................................................ 3-1
3.2.1 MPS-CTU Connections ............................. 3-1
3.2.1.1 Supply Voltage .............................. 3-1
3.2.1.2 Current Inputs ................................ 3-1
3.2.1.3 Voltage Inputs ............................... 3-1
3.2.1.3.1 Direct Connection ........ 3-3
3.2.1.3.2 1-PT Connection .......... 3-3
3.2.1.3.3 2-PT Connection .......... 3-3
3.2.1.3.4 3-PT Connection .......... 3-3
3.2.1.4 Digital Inputs ................................. 3-3
3.2.1.4.1 DC Operation ............... 3-4
3.2.1.4.2 AC Operation ............... 3-4
3.2.1.4.3 Combined AC and
DC Operation ............................... 3-4
3.2.1.4.4 Tachometer
Input (HSI) ................................... 3-4
3.2.1.5 Analog Input (AN IN) ................... 3-4
3.2.1.6 Analog Output (AN OUT) ............ 3-4
3.2.1.7 PTC Input ...................................... 3-4
3.2.1.8 IRIG-B Input ................................. 3-4
3.2.1.9 I/O Module Communication ......... 3-4
3.2.1.10 RS-485 Network
Communications ......................................... 3-4
3.2.2 MPS-OPI Connections and
Address Selection ....................................... 3-4
3.2.3 MPS-RTD Connections and
Address Selection ....................................... 3-5
3.2.4 MPS-DIF Connections ............................... 3-5
3.2.4.1 Core Balance ................................. 3-5
TABLE OF CONTENTS
SECTION PAGE
3.2.4.2 MPS Summation ............................ 3-5
3.2.4.3 DIF Summation ............................. 3-5
3.2.5 Dielectric-Strength Testing ........................ 3-5
4 Operation and Setup ............................................ 4-1
4.1 General .................................................................... 4-1
4.2 MPS-CTU ............................................................... 4-1
4.2.1 LED Indication ........................................... 4-1
4.2.2 Reset Switch ................................................ 4-1
4.2.3 Phase-CT Inputs .......................................... 4-1
4.2.4 Earth-Fault-CT Input .................................. 4-2
4.2.5 Voltage Inputs ............................................. 4-2
4.2.6 Motor Data .................................................. 4-2
4.2.7 Output Relay Assignment .......................... 4-2
4.2.8 Digital Inputs 1 to 7 .................................... 4-3
4.2.9 Tachometer Input (HSI) ............................. 4-4
4.2.10 Analog Output ............................................. 4-4
4.2.11 Analog Input ............................................... 4-5
4.2.11.1 Metering only .............................. 4-5
4.2.11.2 Protection ..................................... 4-5
4.2.11.3 Synchronize to ASD .................... 4-5
4.2.11.4 Motor Speed ................................ 4-5
4.2.12 Starter .......................................................... 4-5
4.2.13 Protection .................................................... 4-5
4.2.14 Miscellaneous Configuration ..................... 4-5
4.2.15 Network Communications .......................... 4-5
4.3 MPS-OPI ................................................................. 4-5
4.3.1 General ........................................................ 4-5
4.3.2 Configuring the MPS-CTU for
OPI Operation ............................................. 4-5
4.3.3 Starter Control ............................................. 4-6
4.3.3.1 OPI Control .................................... 4-6
4.3.3.2 Local Control ................................. 4-6
4.3.3.3 Remote Control ............................. 4-6
4.3.4 Metering ...................................................... 4-7
4.3.5 Messages ..................................................... 4-7
4.3.5.1 Trip Reset ....................................... 4-7
4.3.5.2 Status .............................................. 4-7
4.3.5.3 Data Logging ................................. 4-9
4.3.5.4 Statistical Data ............................... 4-9
4.3.5.5 Emergency Thermal Reset ............ 4-9
4.3.6 Password Entry and Programming ............. 4-9
4.4 MPS-RTD ............................................................. 4-10
4.5 MPS-DIF ............................................................... 4-10
4.6 Waveform Capture ............................................... 4-10
5 Protective Functions ......................................... 5-1
5.1 General ............................................................... 5-1
5.2 Overload ............................................................. 5-1
5.2.1 Thermal Model ....................................... 5-1
5.2.2 Locked-Rotor Times ............................... 5-4
5.2.3 Emergency Thermal Reset ...................... 5-4
5.3 Overcurrent ........................................................ 5-4
5.4 Auxiliary Overcurrent ........................................ 5-5
5.5 Reduced Overcurrent ......................................... 5-5
5.6 Jam ..................................................................... 5-5
5.7 Earth Fault .......................................................... 5-5
Page iii MPS Motor Protection System Rev. 6-F-022117
. Table of Contents
SECTION PAGE
5.8 Current Unbalance .............................................. 5-5
5.9 Phase Loss—Current .......................................... 5-6
5.10 Phase Reverse—Current ..................................... 5-6
5.11 Undercurrent ....................................................... 5-6
5.12 Overvoltage ........................................................ 5-6
5.13 Voltage Unbalance ............................................. 5-6
5.14 Phase Loss—Voltage ......................................... 5-6
5.15 Phase Reverse—Voltage .................................... 5-6
5.16 Undervoltage ...................................................... 5-7
5.17 Underpower ........................................................ 5-7
5.18 Reversepower ..................................................... 5-7
5.19 Power Factor—Quadrant 4 ................................. 5-7
5.20 Power Factor—Quadrant 3 ................................. 5-7
5.21 Underfrequency .................................................. 5-7
5.22 Overfrequency .................................................... 5-8
5.23 Starts per Hour/Time Between Starts ................. 5-8
5.24 Failure to Accelerate and Underspeed ................ 5-8
5.25 Differential Current Protection ........................... 5-9
5.26 PTC Temperature ............................................... 5-9
5.27 RTD Temperature .............................................. 5-9
5.28 Hot-Motor Compensation ................................ 5-10
5.29 Analog Input ..................................................... 5-10
5.29.1 Protection .............................................. 5-10
5.29.2 Synchronize to ASD ............................. 5-10
5.29.3 Motor Speed .......................................... 5-10
5.29.4 Metering Only ....................................... 5-10
6 Starter Functions .............................................. 6-1
6.1 General ............................................................... 6-1
6.2 Starter Timing Sequences ................................... 6-4
6.3 Full-Voltage Non-Reversing Starter .................. 6-7
6.4 Adjustable-Speed Drive ..................................... 6-7
6.5 Soft-Start Starter ................................................. 6-7
6.6 Full-Voltage Reversing Starter ........................... 6-8
6.7 Two-Speed Starter .............................................. 6-8
6.8 Reactor or Resistor Closed-Transition
Starter ............................................................... 6-10
6.9 Slip-Ring Starter ............................................... 6-10
6.10 Part-Winding and Double-Delta Starters ......... 6-11
6.11 Soft-Start-With-Bypass Starter ........................ 6-12
6.12 Reactor or Resistor Open-Transition Starter .... 6-12
6.13 Two-Winding Starter ........................................ 6-12
6.14 Wye-Delta Open-Transition Starter ................. 6-12
6.15 Autotransformer Closed-Transition Starter ...... 6-13
6.16 Wye-Delta Closed-Transition Starter ............... 6-13
7 Theory of Operation ......................................... 7-1
7.1 Signal-Processing Algorithms ............................ 7-1
7.2 Power Algorithm ................................................ 7-1
7.3 Operator Interface (MPS-OPI) ........................... 7-1
7.4 RTD Module (MPS-RTD) ................................. 7-1
7.5 Differential Module (MPS-DIF) ........................ 7-1
7.6 Firmware Diagnostics ........................................ 7-1
8 Communications ............................................... 8-1
8.1 Personal-Computer Interface .............................. 8-1
8.1.1 Firmware Upgrade .................................. 8-1
8.1.2 SE-Comm-RIS ........................................ 8-1
SECTION PAGE
8.2 Network Interface ............................................... 8-1
8.2.1 RS-485 Communications ........................ 8-1
8.2.2 DeviceNet Communications ................... 8-1
8.2.3 Ethernet Communications ....................... 8-1
8.2.4 Profibus Communications ....................... 8-1
9 Technical Specifications ................................... 9-1
9.1 Control Unit (MPS-CTU) .................................. 9-1
9.2 Operator Interface (MPS-OPI) ........................... 9-3
9.3 RTD Module (MPS-RTD) ................................. 9-3
9.4 Differential Module (MPS-DIF) ........................ 9-4
10 Warranty ........................................................... 9-5
Appendix A MPS-OPI Menu Map ............................ A-1
Appendix B MPS Set-Up Record .............................. B-1
Appendix C MPS Modbus Protocol .......................... C-1
Appendix D MPS A-B DF1 Protocol ......................... D-1
Appendix E Communications Database Table ......... E-1
Appendix F Register Formats .................................... F-1
Appendix G MPS Revision History .......................... G-1
Page iv MPS Motor Protection System Rev. 6-F-022117
. Table of Contents
LIST OF FIGURES
FIGURE PAGE
1.1 Motor Protection System Block Diagram ............. 1-3
1.2 MPS Ordering Information .................................... 1-4
2.1 MPS-CTU Outline and Mounting Details ............. 2-2
2.1.1 MPS-CTU-XX-X1 Ring Terminal
Outline and Mounting Details ................................ 2-3
2.2 MPS-OPI Outline and Mounting Details ............... 2-4
2.3 MPS-CTU with OPI Outline and
Mounting Details .................................................... 2-5
2.3.1 MPS-CTU Ring Terminal with OPI Outline and
Mounting Details .................................................... 2-6
2.4 SE-IP65CVR-M Weatherproof Cover Outline .. 2-7
2.5 SE-IP65CVR-M Weatherproof Cover
Installation .......................................................... 2-8
2.6 MPS-RTD Outline and Mounting Details ............. 2-9
2.7 MPS-DIF Outline and Mounting Details ............. 2-10
2.8 EFCT-1 Outline and Mounting Details ............... 2-11
2.9 EFCT-2 Outline and Mounting Details ............... 2-12
2.10 EFCT-26 and SE-CS30-26 Outline and
Mounting Details .................................................. 2-13
2.11 SE-CS30-70 Outline and Mounting Details ........ 2-14
2.12 SE-CS30-4, -5, and -8 Outline and Mounting
Details ................................................................... 2-15
3.1 Residual Phase-CT Connection ............................. 3-1
3.2 Typical MPS Connection Diagram ........................ 3-2
3.3 Direct Connection ................................................... 3-3
3.4 1-PT Connection ..................................................... 3-3
3.5 2-PT Connection ..................................................... 3-3
3.6 3-PT Connection ..................................................... 3-3
3.7 Digital Tachometer Input (HSI) ............................. 3-4
3.8 Address Selection Switch Detail ............................ 3-5
3.9 Two Examples of I/O Module Connections .......... 3-6
3.10 MPS-RTD Connection Diagram ............................ 3-7
3.11 Core Balance Connection ....................................... 3-8
3.12 MPS Summation Connection ................................. 3-8
3.13 DIF Summation Connection .................................. 3-9
4.1 Menu Example ........................................................ 4-1
4.2 Menu Symbols ........................................................ 4-1
4.3 MPS-OPI Interface ................................................. 4-6
5.1 Class-20 Overload Curve ....................................... 5-3
5.2 Asymmetrical-Current Multipliers ......................... 5-5
5.3 Used I2t Bias Curve .............................................. 5-10
6.1 Typical 3-Wire Control .......................................... 6-3
6.2 Typical 2-Wire Control .......................................... 6-4
6.3 Starter Sequence 1 .................................................. 6-4
6.4 Starter Sequence 2 .................................................. 6-4
6.5 Starter Sequence 3 .................................................. 6-5
6.6 Starter Sequence 4 .................................................. 6-5
6.7 Starter Sequence 5 .................................................. 6-6
6.8 Starter Sequence 6 .................................................. 6-6
6.9 Full-Voltage Non-Reversing-Starter
Connection .............................................................. 6-7
6.10 Adjustable-Speed-Drive Connection ..................... 6-7
6.11 Soft-Start-Starter Connection ................................. 6-7
LIST OF FIGURES
FIGURE .............................................. PAGE
6.12 Full-Voltage-Reversing-Starter Connection .......... 6-8
6.13 Two-Speed Two-Winding-Starter Connection ...... 6-8
6.14 Two-Speed Constant- and Variable-Torque-
Starter Connections ................................................. 6-9
6.15 Two-Speed Constant-Horsepower-Starter
Connection ............................................................... 6-9
6.16 Reactor or Resistor-Starter Connection ................ 6-10
6.17 Slip-Ring-Starter Connection ................................ 6-10
6.18 Part-Winding and Double-Delta-Starter
Connections ........................................................... 6-11
6.19 Soft-Start-With-Bypass-Starter Connection ......... 6-12
6.20 Two-Winding-Starter Connection ........................ 6-13
6.21 Wye-Delta Open-Transition-Starter
Connection ............................................................. 6-14
6.22 Autotransformer Closed-Transition-Starter
Connection ............................................................. 6-14
6.23 Wye-Delta Closed-Transition-Starter
Connection ............................................................. 6-15
LIST OF TABLES
TABLE PAGE
3.1 MPS-OPI Address Selection ................................... 3-4
3.2 MPS-RTD Address Selection ................................. 3-5
4.1 Output-Relay Functions .......................................... 4-2
4.2 Digital-Input Functions ........................................... 4-3
4.3 Analog-Output Parameters ...................................... 4-4
4.4 Metering Display ..................................................... 4-8
4.5 Status Messages ....................................................... 4-8
5.1 Trip Time ................................................................. 5-4
5.2 Fault Duration Required for Trip ............................ 5-4
6.1 Start-Source Summary ............................................ 6-1
6.2 Starter Summary ...................................................... 6-3
Page v MPS Motor Protection System Rev. 6-F-022117
. Table of Contents
DISCLAIMER
Specifications are subject to change without notice. Littelfuse Startco is not liable for contingent or consequential damages, or for expenses sustained as a result of incorrect application, incorrect adjustment, or a malfunction.
Page 1-1 MPS Motor Protection System Rev. 6-F-022117
Introduction
1. INTRODUCTION
1.1 GENERAL
The Littelfuse Startco Motor Protection System (MPS) is a modular system with integrated protection, control, metering, and data-logging functions. The Control Unit (MPS-CTU) is the core module. It can operate as a stand­alone unit or with the Operator Interface (MPS-OPI), RTD Modules (MPS-RTD), and Differential Module (MPS-DIF). The CTU can be programmed using the OPI or the communications network. Programmable inputs and outputs provide a flexible hardware platform and custom software can be easily loaded from a PC to the CTU’s flash memory. The MPS block diagram is shown in Fig. 1.1.
1.2 MPS FEATURES
1.2.1 PROTECTION
Overload (49, 51)
Overcurrent (50, 51)
Earth fault (50G/N, 51G/N)
Unbalance (voltage and current) (46, 47)
Phase loss (voltage and current) (46, 47)
Phase reverse (voltage and current) (46, 47)
Jam
Undercurrent (37)
Failure to accelerate
Underspeed (14)
Overvoltage (59)
Undervoltage (27)
Underpower (37)
Reversepower (32)
Power factor (55)
Overfrequency (81)
Underfrequency (81)
PTC overtemperature (49)
RTD temperature (38, 49)
Starts per Hour (66)
Differential (87)
1.2.2 CONTROL—STARTING METHODS
(1)
Non-reversing
Reversing
Soft start
Soft start with bypass
Adjustable-speed drive
Two speed
Wye-delta (open or closed transition)
Reactor (open or closed transition)
Resistor (open or closed transition)
Autotransformer
Part winding
Slip ring
Two winding
Double delta
(1)
Only three CT’s required for all starting methods.
1.2.3 METERING
Line currents
Current unbalance
Positive-sequence current
Negative-sequence current
Earth-leakage current
Differential currents
Line-to-line voltages
Line frequency
Voltage unbalance
Positive-sequence voltage
Negative-sequence voltage
Power
§ Apparent, Reactive, Real, and Power factor
Energy
§ kWh, kVAh, and kVARh
Used thermal capacity
Thermal trend
Motor speed
RTD temperatures
Analog input and output
1.2.4 DATA LOGGING
Sixty-four records
§ Date and time of event
§ Event type
§ Line currents
§ Current unbalance
§ Earth-leakage current
§ Differential currents
§ Line-to-line voltages
§ Voltage unbalance
§ Thermal capacity
§ Thermal capacity used during starts
§ Start time
§ Analog-input value
§ Frequency
§ Power (P, S, Q, PF)
§ RTD temperatures
§ Trip counters
§ Running hours
§ Waveform Capture
§ 5 seconds of pre-trip waveform data
§ 16 samples per cycle
§ COMTRADE and CSV file generation
1.2.5 INPUTS AND OUTPUTS
Three ac-current inputs
Three ac-voltage inputs
Earth-leakage-current input
Seven programmable digital (ac/dc) inputs
24-Vdc source for digital inputs
Tachometer (high-speed pulse) input
4-20-mA analog input
4-20-mA analog output
PTC thermistor temperature input
Page 1-2 MPS Motor Protection System Rev. 6-F-022117
Introduction
Up to twenty-four RTD inputs
Five programmable output relays
Network communications
IRIG-B time-code input
1.2.6 MPS-OPI OPERATOR INTERFACE
4 x 20 vacuum-fluorescent display
Starter-control keys
Display-control and programming keys
LED status indication
Remote operation up to 1.2 km (4,000’)
Powered by MPS-CTU
1.2.7 MPS-RTD MODULE
Eight inputs per module
Individually selectable RTD types
RTD Voting
Solid-state multiplexing
Up to three modules per system
Remote operation up to 1.2 km (4,000’)
Powered by MPS-CTU
1.2.8 MPS-DIF DIFFERENTIAL MODULE
3-CT core-balance connection
6-CT summation connection
Remote operation up to 1.2 km (4,000’)
Powered by MPS-CTU
1.2.9 COMMUNICATIONS INTERFACE
The standard network communication interface is an RS-485 port with Modbus® RTU and A-B® DF1 protocol support. In addition to the standard interface, network communication options include DeviceNet™, Profibus®, Modbus® TCP, and Ethernet/IP.
1.3 ORDERING INFORMATION
See Fig. 1.2 for MPS-CTU, MPS-OPI, MPS-RTD, and MPS-DIF model numbers.
Earth-Fault Current Sensors:
EFCT-1 ......................... Earth-Fault CT,
5-A-primary rating, 82 mm (3.2”) window
EFCT-1FC ..................... Flux Conditioner for EFCT-1,
70 mm (2.7”) window
EFCT-2 ......................... Earth-Fault CT with
Flux Conditioner, 5-A-primary rating, 139 mm (5.5”) window
EFCT-26 ....................... Earth-Fault CT,
5-A-primary rating, 26 mm (1”) window (All EFCT’s include 6 m (19.5’) of 22 AWG (0.33 mm2) shielded cable.)
SE-CS30-4 ............................. Current Sensor,
30-A-primary rating, c/w Flux Conditioner,
95.0 mm (3.7”) window
SE-CS30-5 ............................. Current Sensor,
30-A-primary rating, c/w Flux Conditioner,
130.0 mm (5.1”) window
SE-CS30-8 ............................. Current Sensor
30-A-primary rating, c/w Flux Conditioner,
200.0 mm (7.9”) window
SE-CS30-26 ......................... Current Sensor,
30-A-primary rating,
26 mm (1.0”) window
SE-CS30-70 ......................... Current Sensor,
30-A-primary rating, 70 mm (2.7”) window
Phase CT’s ............................... Protection-Class CT’s,
Contact factory
Accessories:
SE-IP65CVR-M ................... Hinged Transparent OPI
Cover
SE-485-PP ............................ Port-Powered Serial
Converter
SE-485-DIN ......................... Serial Converter,
Industrial, 24 Vdc
Software:
SE-Comm-RIS ..................... PC Communication
Software
(1)
SE-Flash ............................... Firmware Upgrade
Software
(1)
(1)
Available at www.littelfuse.com/relayscontrols.
Page 1-3 MPS Motor Protection System Rev. 6-F-022117
Introduction
FIGURE 1.1 Motor Protection System Block Diagram.
Page 1-4 MPS Motor Protection System Rev. 6-F-022117
Introduction
FIGURE 1.2 MPS Ordering Information.
Page 2-1 MPS Motor Protection System Rev. 6-F-022117
Installation
2. INSTALLATION
2.1 GENERAL
A basic Motor Protection System (MPS) consists of an MPS-CTU and three customer-supplied current transformers (CT's) for measuring phase current. For core-balance earth-fault detection, a 1-A, 5-A, EFCT-1, or EFCT-2 CT is required. For the optional Ring Terminal MPS-CTU, the 1-A connection is not available. The residual phase-CT connection can also be used for earth­fault detection. Voltage inputs do not require potential transformers (PT’s) for system voltages up to 600 Vac. For RTD-temperature measurement, up to three MPS-RTD modules can be connected to the MPS-CTU. For differential protection, an MPS-DIF module can be connected to the MPS-CTU. The MPS-OPI provides an operator interface for the MPS. The MPS power-factor-corrected switch-mode power supply is rated 65 to 265 Vac and 80 to 275 Vdc. All modules can be mounted in any orientation.
2.2 MPS-CTU CONTROL UNIT
The Control Unit is configured for surface mounting. Outline and mounting details for the MPS-CTU are shown in Figs. 2.1 and 2.1.1.
2.3 MPS-OPI OPERATOR INTERFACE
Outline and mounting details for the MPS-OPI are shown in Fig. 2.2. It is certified for use in Class I, Zone 2 and Class I, Division 2 hazardous locations. The Operator Interface is configured for panel mounting or it can be mounted on the MPS-CTU as shown in Fig. 2.3. The Operator Interface can also be mounted on the MPS-CTU ring terminal as shown in Fig. 2.3.1 (surface mount only). If an optional SE-IP65CVR-M is used, follow the included installation instructions. See Figs. 2.4 and 2.5.
2.4 MPS-RTD MODULE
Outline and mounting details for the MPS-RTD are shown in Fig. 2.6. The MPS-RTD will fit inside most motor RTD-termination junction boxes and it is certified for use in Class I, Zone 2 and Class I, Division 2 hazardous locations. The MPS-RTD can be surface or DIN-rail mounted.
2.5 MPS-DIF DIFFERENTIAL MODULE
Outline and mounting details for the MPS-DIF are shown in Fig 2.7. The MPS-DIF can be surface or DIN­rail mounted.
2.6 EARTH-FAULT CT’S
Outline and mounting details for the EFCT-1, EFCT-2, EFCT-26, and SE-CS30 series are shown in Figs. 2.8, 2.9,
2.10, 2.11, and 2.12.
Page 2-2 MPS Motor Protection System Rev. 6-F-022117
Installation
FIGURE 2.1 MPS-CTU Outline and Mounting Details.
Page 2-3 MPS Motor Protection System Rev. 6-F-022117
Installation
FIGURE 2.1.1 MPS-CTU-XX-X1 Ring Terminal Outline and Mounting Details.
Page 2-4 MPS Motor Protection System Rev. 6-F-022117
Installation
FIGURE 2.2 MPS-OPI Outline and Mounting Details.
Page 2-5 MPS Motor Protection System Rev. 6-F-022117
Installation
FIGURE 2.3 MPS-CTU with OPI Outline and Mounting Details.
Page 2-6 MPS Motor Protection System Rev. 6-F-022117
Installation
FIGURE 2.3.1 MPS-CTU Ring Terminal with OPI Outline and Mounting Details.
Page 2-7 MPS Motor Protection System Rev. 6-F-022117
Installation
FIGURE 2.4 SE-IP65CVR-M Weatherproof Cover Outline.
Page 2-8 MPS Motor Protection System Rev. 6-F-022117
Installation
FIGURE 2.5 SE-IP65CVR-M Weatherproof Cover Installation.
Page 2-9 MPS Motor Protection System Rev. 6-F-022117
Installation
FIGURE 2.6 MPS-RTD Outline and Mounting Details.
Page 2-10 MPS Motor Protection System Rev. 6-F-022117
Installation
FIGURE 2.7 MPS-DIF Outline and Mounting Details.
Page 2-11 MPS Motor Protection System Rev. 6-F-022117
Installation
FIGURE 2.8 EFCT-1 Outline and Mounting Details.
Page 2-12 MPS Motor Protection System Rev. 6-F-022117
Installation
FIGURE 2.9 EFCT-2 Outline and Mounting Details.
Page 2-13 MPS Motor Protection System Rev. 6-F-022117
Installation
FIGURE 2.10 EFCT-26 and SE-CS30-26 Outline and Mounting Details.
Page 2-14 MPS Motor Protection System Rev. 6-F-022117
Installation
FIGURE 2.11 SE-CS30-70 Outline and Mounting Details.
Page 2-15 MPS Motor Protection System Rev. 6-F-022117
Installation
FIGURE 2.12 SE-CS30-4, -5, and -8 Outline and Mounting Details.
Page 2-16 MPS Motor Protection System Rev. 6-F-022117
Installation
This page intentionally left blank.
Page 3-1 MPS Motor Protection System Rev. 6-F-022117
System Wiring
3. SYSTEM WIRING
3.1 GENERAL
A typical connection diagram is shown in Fig. 3.2. The MPS-CTU provides the 24-Vdc supply for the peripheral modules and it communicates with them using an RS-485 interface. The total length of the I/O communication system must be less than 1.2 km (4,000’). I/O communications addressing supports up to three modules of each type; however, the power supply in the MPS-CTU will not support more than three I/O modules. An external 24-Vdc power supply is required if more than three modules are used. The MPS-CTU voltage inputs can be directly connected to a system with line-to-line voltages up to 600 Vac. PT's are required for system voltages higher than 600 Vac. Input resistance of the voltage inputs is
3.4 MΩ.
NOTE: The current and voltage inputs must be phase sequenced A-B-C with correct polarity observed.
START1, START2, and STOP starter-control commands can be issued through the digital inputs, the network interface, or the MPS-OPI. Start, stop, and interlock contacts can be wired to any of the programmable digital inputs. The five programmable output relays can be used for starting control, protection, and interlock functions. Relay 5 is a solid-state, low-level output relay not recommended for starter control. See Section 9 for relay ratings.
NOTE: The default configuration has no assignments for digital inputs and relay outputs.
3.2 WIRING CONNECTIONS
3.2.1 MPS-CTU CONNECTIONS
The MPS-CTU CT-input terminal blocks accept 22 to 10 AWG (0.3 to 4.0 mm2) conductors. The remaining MPS-CTU clamping blocks accept 24 to 12 AWG (0.2 to 2.5 mm2) conductors. Terminal blocks unplug to allow the MPS-CTU to be easily replaced. The MPS-CTU Ring Terminal CT-input terminal block accept a maximum ring width of 8 mm (0.315”). These terminal blocks cannot be unplugged.
3.2.1.1 SUPPLY VOLTAGE
Derive supply voltage from the line side of the motor controller or from an independent source. Connect supply voltage to terminals 1 and 2 (L1 and L2) as shown in Fig. 3.2. In 120-Vac systems, L2 is usually designated as the neutral conductor. For direct-current power supplies, use L1 for the positive terminal and L2 as the negative terminal. Earth terminal 3 ( ). Internal surge-protection devices are connected to terminals 4 (SPG) and 4A (SPGA) to allow dielectric­strength testing. Terminals 4 and 4A must be connected except during dielectric-strength testing. The 24-Vdc I/O module supply (terminals 56 and 60) can support three I/O modules. An external 24-Vdc supply is required if more than three modules are used.
3.2.1.2 CURRENT INPUTS
The MPS-CTU uses 1-A or 5-A CT’s for phase-current measurement. The MPS-CTU Ring Terminal uses 5-A CT’s for phase-current measurement. To maintain specified accuracy, phase CT’s should be protection class and selected with a primary rating between 100 and 300% of motor full-load current (FLA). Current threshold is a function of full-load current and CT-primary rating as defined by the following formula.
The Current Threshold is also used to determine when the motor is in Run mode. Several protective functions are only enabled when in Run mode. See Section 5.1 for a description of Run mode. For synchronous-motor applications, the CT-primary
rating should be selected such that the current threshold is less than the idle current, typically less than 5%. All CT
inputs can withstand a common-mode voltage of 120 Vac so that the MPS-CTU can be connected in series with other CT loads. The connection diagram in Fig. 3.2 shows a typical connection where the MPS-CTU is the only device connected to the phase CT's. The MPS-CTU requires the phase sequence to be A-B-C with correct polarity. The Ip Threshold sets the current level where unbalance protection becomes active. See Section 5.8. A 1-A, 5-A, or sensitive CT is used for core-balance earth-leakage measurement. The MPS-CTU Ring Terminal has no 1-A input. See Fig. 3.1 for the phase-CT residual connection for earth-fault detection.
FIGURE 3.1 Residual Phase-CT Connection.
3.2.1.3 VOLTAGE INPUTS
For all input-voltage connections, the MPS-CTU requires the phase sequence to be A-B-C with correct polarity. If voltage inputs are not used, connect VA, VB, and VC to VN.
NOTE: A voltage input is required for line-frequency metering.
Page 3-2 MPS Motor Protection System Rev. 6-F-022117
System Wiring
FIGURE 3.2 Typical MPS Connection Diagram.
Page 3-3 MPS Motor Protection System Rev. 6-F-022117
System Wiring
3.2.1.3.1 DIRECT CONNECTION
PT's are not required for system voltages up to 600 Vac
line-to-line. Connect the voltage inputs as shown in Figs. 3.2 and 3.3.
FIGURE 3.3 Direct Connection.
3.2.1.3.2 1-PT CONNECTION
The 1-PT connection is shown in Fig. 3.4. Connect the PT between phase A and phase B. The PT-secondary voltage must be less than 350 Vac.
NOTE: The 1-PT connection does not allow detection of voltage unbalance.
FIGURE 3.4 1-PT Connection.
3.2.1.3.3 2-PT CONNECTION
The 2-PT connection is shown in Fig. 3.5. The PT­secondary voltages must be less than 350 Vac. Connect the PT secondaries in open delta.
FIGURE 3.5 2-PT Connection.
3.2.1.3.4 3-PT CONNECTION
The 3-PT connection is shown in Fig. 3.6. The PT­secondary voltages must be less than 350 Vac. Since the MPS-CTU measures line-to-line voltage, there is no advantage in using a 3-PT connection over a 2-PT connection.
NOTE: This connection relies on PT primary­magnetization current for voltage balance. Do not connect any other secondary loads.
FIGURE 3.6 3-PT Connection.
3.2.1.4 DIGITAL INPUTS
Digital inputs 1 to 8 (terminals 44 to 51) are referenced to COM (terminal 43). These inputs are isolated from all other terminals and operate over a 12 to 120 Vac/Vdc range. Inputs 1 to 7 have programmable functions. See Table 4.2. Input 8 is a high-speed input (HSI) for a tachometer sensor.
Page 3-4 MPS Motor Protection System Rev. 6-F-022117
System Wiring
3.2.1.4.1 DC OPERATION
Supply voltage for dc-input operation can be obtained from the 24-Vdc source (terminals 41 and 42), or it can be obtained from an external 12- to 120-Vdc supply. The internal source is current limited at 100 mA and is referenced to the analog output (terminal 40) and the I/O Supply (terminal 56). Connect the “” terminal of the dc source to COM and connect field inputs between “+” and the digital-input terminals.
3.2.1.4.2 AC OPERATION
Inputs operate over a 12- to 120-Vac range. Connect the ac neutral to COM and connect field inputs between line and the digital inputs.
3.2.1.4.3 COMBINED AC AND DC OPERATION
If both ac and dc inputs are used, connect both the ac­supply common and dc-supply “” to COM.
3.2.1.4.4 TACHOMETER INPUT (HSI)
A tachometer sensor can be used to provide motor­speed measurement. Connect a logic-output PNP tachometer as shown in Fig. 3.7.
FIGURE 3.7 Digital Tachometer Input (HSI).
3.2.1.5 ANALOG INPUT (AN IN)
The analog input (terminal 52 and 53) is a 4-20-mA current input with a 100-Ω input impedance.
NOTE: The analog input is referenced to an internal supply with 100-kΩ resistors. Maximum common-mode voltage is ± 5 Vdc with respect to MPS-CTU terminal 4.
3.2.1.6 ANALOG OUTPUT (AN OUT)
The analog output is a self-powered current-source output. The current source output is the “+” (terminal 39) and the common is “” (terminal 40).
NOTE: The analog output (terminal 40) is internally referenced to the 24-Vdc source (terminal 42) and the I/O supply (terminal 56).
3.2.1.7 PTC INPUT
Terminals 54 and 55 are provided for PTC over­temperature protection. See Section 9 for specifications.
3.2.1.8 IRIG-B INPUT
Terminals 61 and 62 are used for an IRIG-B time-code signal. When an IRIG-B signal is detected, the real-time clock (RTC) synchronizes with it. The user must set the MPS date value because the IRIG-B day-of-the-year parameter is not supported. If the time-code generator does not have a local-time adjustment, the IRIG Offset set points can be used to adjust the hour and minute values so that the MPS will read local time.
3.2.1.9 I/O MODULE COMMUNICATION
The I/O module communications interface (terminals 56 through 60) is used to support optional modules. The connector labeled Operator Interface on the MPS-CTU top panel is in parallel with terminals 50 to 56. It is used for direct MPS-OPI mounting. See Section 2.3. I/O module communication is based on the 2-wire multi-drop RS-485 standard. Overall line length must not exceed 1.2 km (4,000’). For line lengths exceeding 10 m (33’), 150-Ω terminations are required at the cable ends. See Fig. 3.9.
3.2.1.10 RS-485 NETWORK COMMUNICATIONS
Terminals 35, 36, and 37 are used for the standard RS-485 interface. See Section 4.2.15.
3.2.2 MPS-OPI CONNECTIONS AND ADDRESS SELECTION
Connect the MPS-OPI to the MPS-CTU using shielded cable (Belden® 3124A or equivalent). The 24-Vdc supply for the MPS-OPI is provided by the MPS-CTU. The cable shield must be connected at both ends so that MPS-OPI transient protection is operational. See Fig. 3.9. The MPS-OPI has two switches to select its network address. See Figs. 2.2 and 3.8. Up to three MPS-OPI modules can be connected to the I/O MODULE bus, and each active OPI must have a unique address. If one OPI is used, address 1 must be used. If two OPI's are used, addresses 1 and 2 must be used. If three OPI's are used, addresses 1, 2, and 3 must be used. Table 3.1 and Fig. 3.8 shows the addressing selection format.
TABLE 3.1 MPS-OPI ADDRESS SELECTION
ADDRESS
SWITCH 1
SWITCH 2
0
(Factory Test)
Open
Open
1
(First OPI)
Closed
Open
2
(Second OPI)
Open
Closed
3
(Third OPI)
Closed
Closed
Loading...
+ 118 hidden pages