Littelfuse M3000 User Manual

Alarm Monitoring
14
12
13
11
INPUT GROUP 1
IN 1
IN 2
IN 3
GND
84
82
83
81
INPUT GROUP 8
IN 1
IN 2
IN 3
GND
101
114
120
11 5
11 6
121
122
130
131
132
+
M3000
(Analog Alarm Annunciator)
24 V
DIM
AL. OUT
SIREN
B
A
COM
RS485
RS232
OPEN
COLLECTOR
OUTPUTS
Monitoring
M3000 SERIES
Analog Alarm Annunciator
Description
The M3000 Analog Alarm Annunciator has 24 inputs that can be configured individually for dry contact (NO or NC) inputs or analog inputs. Analog inputs can read measurements through 4-20 mA, 0-10 Vdc or 0-24 Vdc transmitters. Up to 48 alarms can be configured with individual reference to any of the 24 inputs. An alarm is activated and indicated when the input value exceeds a preset critical low or high level. The alarm can be related to any of the 24 LEDs and any of the 14 outputs. Several alarms may activate the same LED and/or output. The M3000 has a common alarm output, a siren output, as well as dedicated inputs for remote reset and blocking.
Simplified Circuit Diagram
Features & Benefits
FEATURES BENEFITS
24 inputs One unit for both, digital and analog sensors
48 alarms
Programmable 10-character LCD text
24 LEDs with indication of new and acknowledged alarms.
14 open collector outputs
RS485 interface For field-bus communication with PLC or HMI
RS232 link
Ordering Information
ORDERING NUMBER CONTROL POWER
ACCESSORIES REQUIREMENT
M1500 24 Vdc
www.littelfuse.com/m3000
Individual refer ence to any of the 24 inp uts allows easy configuration of gr oup and individual alar ms
Each alarm is indicated as clear text
First incoming alarm can be identified easily
Provide ON/OFF control and simple connection to remote displays
Allows easy programming with PC-based software
Configure the unit from a PC through the built-in RS232 interface or the front panel. It also comes equipped with an RS485 interface supporting MODBUS-RTU and with configuration software. It features a spreadsheet-like graphical interface enabling flexible configuration of all the parameters in the unit. The M3000 also offers configuration of average deviations alarms. This feature is used in monitoring of the exhaust gas temperatures of diesel or gas engines. The average temperature from a number of cylinders is calculated. If the temperature value of one of the cylinders deviates from the average of the remaining cylinders by more than a preset ± offset, a deviation alarm will be activated.
Accessories
A
M1500 PT100 6-way Transmitter
Six current transducers in one box for use with DIN60751 3-wire PT100 temperature sensors. The output signals are 4-20 mA current, which can be easily fed into the M3000. Each sensor input can be configured for 3 different temperature ranges.
Specifications
Voltage Supply Consumption Max. 400 mA Sensor Inputs 24 Input Types 20 mA, 10 Vdc and 24 Vdc Alarms 48 Alarm Delays 300 msec. to 10 days Outputs 14 on/off open collector outputs, each controlled
by one or more alarms. Max. 150 mA per output
General Alarm Output Max. 150 mA Siren Control Max. 150 mA LEDs 24 LCD Display 2 x 16 characters with background light Communication RS485 interface Protocol MODBUS-RTU
Operating Temp. –20°C to +70°C Humidity 95% RH at 20°C Vibration Test 4 g RMS according to IEC 60068-2-64 EMC CE according to EN50081-1, EN50082-1, EN50081-2,
EN50082-2 and EN61000-2-6
Approvals Certified by major marine classification societies Burn-in 50 hours before final test Weight 0.8 kg Dimensions H 144 mm (5.7”); W 144 mm (5.7”); D 70 mm (2.7”) Panel Cut-out H 138 mm (5.4”); W 138 mm (5.4”)
Protection Degree at Front IP54
24 Vdc ± 30%