Littelfuse M1000 User Manual

Engine Control
Alarm Monitoring
Monitoring
M1000 SERIES
Alarm Monitor
Simplified Circuit Diagram
+
SUPPLY
28 29
1
10
11
12
13
ALARM INPUT CONTACTS
M1000
(Alarm Monitor)
TEST
RESET
BLOCK
COLLECTOR
OUTPUTS
Features & Benefits
FEATURES BENEFITS
10 configurable digital inputs
11 open collector outputs Allows ex ternal contr ol and remote indic ation
1 siren relay output Direct connection of alarm siren
Special indication of first alarm
Multiple units can be connected as one system
Voltage and insulation monitoring
Dimming of LEDs Suitable for bridge consoles
Type-approved by marine classification societies
Configuration by DIP switches or PC
RS485 Modbus RTU
Supports both NO and NC input contacts
Provides clear alarm overview in larger systems
Modular and scalable solution
Replaces voltage and insulation monitoring relay on the DC system
Applicable in harsh environments
Easy installation and configuration
Communication with HMI and SCADA systems
OPEN
SIREN
17
26
30
31
32
Description
The M1000 is an alarm panel with 10 digital inputs. Inputs from a dry contact (normally open [NO] or normally closed [NC]) will cause the corresponding LED to flash. Simultaneously a common alarm output and a siren output will be activated as well as an individual output. The unit has separate indications of first alarm, following alarms and acknowledged alarms. It also has dedicated inputs for remote reset and blocking. The unit can be configured for cable monitoring and monitoring of its own supply and insulation level.
Multiple M1000 units can be interconnected to form a large scale alarm system. In this situation functions are available for synchronizing the flashing of the LEDs and enabling global indication of first alarm for all connected units. Alarm related parameters like time delays, reset functions and other features can be configured through 18 programming switches. The M1000 can also be configured via the RS232 interface. A standard ANSI/VT100 terminal is used as programming tool. The M1000 is equipped with a 2-wire RS485 interface supporting MODBUS-RTU communication.
Specifications
Voltage Supply 12-24 Vdc-30%/+30% (8-32 Vdc) 48-110 Vdc-30%/+40% (33-155 Vdc)
Max. Power Consumption 180 mA
Ambient Temp. –10°C to +70°C (also available for –40°C to +70°C) Siren Relay Contact 220 Vac/2 A; 30 Vdc/2 A, 30 W Output Max. 150 mA per channel Resistance in
Sensing Cable Max. 1000 W Insulation Monitor 25 kW±8 kW (50 kW±10 kW for M1000-11-XXC) Impulse Test 4.5 kV EMC CE according to EN50081-1, EN50082-1,
EN50081-2, EN50082-2 and EN61000-2-6
Programming 16 dip-switches or via RS232 interface Communication RS485 interface Weight 0.4 kg Dimensions H 144 mm (5.7”); W 144 mm (5.7”);
Panel Cut-out H 138 mm (5.4”); W 138 mm (5.4”)
Protection Degree at Front IP54 (see Type Description)
1
/50 μsec.
D 35 mm (1.4”)
Ordering Information
ORDERING NUMBER
M1000.0040 48-110 Vdc IP54 front
M1000.0080 12-24 Vdc IP54 front
M1000.0220 12-24 Vdc Internal siren, IP54 at front
© 2013 Littelfuse Protection Relays & Controls www.littelfuse.com/m1000
FUNCTION
Rev: 4-A-050313