Engine Control
Alarm Monitoring
Monitoring
M1000 SERIES
Alarm Monitor
Simplified Circuit Diagram
+
SUPPLY
–
28 29
1
10
11
12
13
ALARM
INPUT
CONTACTS
M1000
(Alarm Monitor)
TEST
RESET
BLOCK
COLLECTOR
OUTPUTS
Features & Benefits
FEATURES BENEFITS
10 configurable
digital inputs
11 open collector outputs Allows ex ternal contr ol and remote indic ation
1 siren relay output Direct connection of alarm siren
Special indication of
first alarm
Multiple units can be
connected as one system
Voltage and insulation
monitoring
Dimming of LEDs Suitable for bridge consoles
Type-approved by marine
classification societies
Configuration by
DIP switches or PC
RS485 Modbus RTU
Supports both NO and NC input contacts
Provides clear alarm overview in
larger systems
Modular and scalable solution
Replaces voltage and insulation monitoring
relay on the DC system
Applicable in harsh environments
Easy installation and configuration
Communication with HMI and
SCADA systems
OPEN
SIREN
17
26
30
31
32
Description
The M1000 is an alarm panel with 10 digital inputs. Inputs from
a dry contact (normally open [NO] or normally closed [NC])
will cause the corresponding LED to flash. Simultaneously a
common alarm output and a siren output will be activated as
well as an individual output. The unit has separate indications
of first alarm, following alarms and acknowledged alarms. It
also has dedicated inputs for remote reset and blocking. The
unit can be configured for cable monitoring and monitoring of
its own supply and insulation level.
Multiple M1000 units can be interconnected to form a large
scale alarm system. In this situation functions are available
for synchronizing the flashing of the LEDs and enabling
global indication of first alarm for all connected units. Alarm
related parameters like time delays, reset functions and other
features can be configured through 18 programming switches.
The M1000 can also be configured via the RS232 interface.
A standard ANSI/VT100 terminal is used as programming
tool. The M1000 is equipped with a 2-wire RS485 interface
supporting MODBUS-RTU communication.
Specifications
Voltage Supply 12-24 Vdc-30%/+30% (8-32 Vdc)
48-110 Vdc-30%/+40% (33-155 Vdc)
Max. Power
Consumption 180 mA
Ambient Temp. –10°C to +70°C (also available for –40°C to +70°C)
Siren Relay Contact 220 Vac/2 A; 30 Vdc/2 A, 30 W
Output Max. 150 mA per channel
Resistance in
Sensing Cable Max. 1000 W
Insulation Monitor 25 kW±8 kW (50 kW±10 kW for M1000-11-XXC)
Impulse Test 4.5 kV
EMC CE according to EN50081-1, EN50082-1,
EN50081-2, EN50082-2 and EN61000-2-6
Programming 16 dip-switches or via RS232 interface
Communication RS485 interface
Weight 0.4 kg
Dimensions H 144 mm (5.7”); W 144 mm (5.7”);
Panel Cut-out H 138 mm (5.4”); W 138 mm (5.4”)
Protection Degree
at Front IP54 (see Type Description)
1
/50 μsec.
D 35 mm (1.4”)
Ordering Information
ORDERING
NUMBER
M1000.0040 48-110 Vdc IP54 front
M1000.0080 12-24 Vdc IP54 front
M1000.0220 12-24 Vdc Internal siren, IP54 at front
© 2013 Littelfuse Protection Relays & Controls
www.littelfuse.com/m1000
CONTROL
POWER
FUNCTION