Littelfuse LFCL User Manual

POWR-GARD® Fuse Datasheet
60 0 VAC
Description
Cable limiters are fusible devices that provide very fast short-circuit protection, primarily to faulted cables, but also to other conductors such as busway. Cable limiters do not have an ampere rating, and cannot be used to provide overload protection. They are instead selected by cable size; for example, a 500 kcmil cable requires a 500 kcmil cable limiter. Their main use is to isolate faulted cables in circuits con tain ing three or more parallel conductors per phase. They may be installed on the line side of the main service to provide short­circuit protection to the service conductors. This is especially important when service conductors are tapped from large low voltage networks or from large low impedance transformers.
Cable limiters have terminals which permit them to be installed in a variety of equipment. The most common configuration is the offset blade on one end and the crimp terminal on the other end. This permits the limiter to replace a cable terminal (lug).
DesCription Cata log numb er
type te rmination Cable size
4/0 LFCL4/0C1 LF CL4/ 0A1
250MCM LFCL250C1 LF CL 250A1
1
CABLE TO CABLE
3
CABLE TO
OFFSET BUS
5
STRAIGHT BUS TO OFFSET BUS
6
MOLE TO CABLE
8
MOLE TO
OFFSET BUS
Note: For Type 5 and Type 8 Aluminum cable limiters, use the Copper Type C5 and C8.
350MCM LFCL350C1 LF CL350 A1 500MCM LFCL500C1 LFCL500A1 750MCM LFCL750C1 LFCL750A1
4/0 LFCL4/ 0C3 LFCL4/0A3 250MCM LFCL250C3 LFCL250A3 350MCM LFCL350C3 LFCL350A3 500MCM LFCL500C3 LFCL500A3 750MCM LFCL750C3 LFCL750A3
4/0 LFCL4/ 0C5 — 250MCM LFCL250C5 — 350MCM LFCL350C5 — 500MCM LFCL500C5 — 750MCM LFCL750C5
4/0 LFCL4/0C6 LFCL4/0A6 250MCM LFCL250C6 LFCL250A6 350MCM LFCL350C6 LFCL350A6 500MCM LFCL500C6 LFCL500A6 750MCM LFCL750C6 LFCL750A6
4/0 LFCL4/ 0C8 — 250MCM LFCL250C8 — 350MCM LFCL350C8 — 500MCM LFCL500C8 — 750MCM LFCL750C8
Cable t ype
Cop per aluminum
Web Resources
For additional information, see website:
www.littelfuse.com/lfcl
Applications
• Service entrance conductors
• Between transformer or network bus and busway
terminal boxes
• Large feeders with three or more conductors per phase
Features
• Current-limiting characteristics provide pro tec tion to conductor insulation and reduce damage when faults occur.
• Properly applied cable limiters may permit the use of equip ment with reduced withstand ratings
• Wide variety of terminations and cable ratings permit use in almost every situation.
Specifications
Voltage Ratings 60 0 VAC Interrupting Rating 200 k A Cable Size Range 4/0 – 75MCM Copper or Aluminum
Note: For Type 5 and Type 8 Aluminum cable limiters, use the Copper Type C5 and C8.
Ordering Information
LFCL - 500 - C - 1
Littelfuse
Cable Limiter
Conductor Size
Terminal Material
(Aluminum or Copper)
Type of
Termination
1 of 1
© 2013 Littelfuse POWR-GARD® ProductsLittelfuse.com
Rev: 012313