Littelfuse L300 User Manual

Fuse Blocks
Screw
with
Pressure
Plate
(P)
Screw
(S)
Box Lug
(C)
General Information
Blocks and Holders
4. Determine if NEC, CSA, UL, or other requirements are applicable
If fuse blocks will be installed in equipment to be submitted for agency approval, the requirements should be obtained from the approving agency in advance of fuse and fuse block selection.
5. Select the type of wire termination
A choice of three types of wire termination is available: a) Screw b) Screw with Pressure Plate
c) Box Lug — the most durable. For use with all types of solid wire and
1/4” Quick Connect terminals rated for up to 20A are
*
— for use with spade lugs or ring terminals.
*
without terminal. Recommended where vibration will be a factor.
Class B and Class C stranded wire. Not for use with welding cable or other rope-stranded conductors.
available on the Midget and Class CC fuse blocks.
— for use with solid or stranded wire
*
Fuse Block Selection
The following guidelines should help simplify the selection of proper fuse blocks:
1. Determine the system voltage
Since fuses are selected on the basis of system voltage, fuse blocks are selected to match the voltage rating of the fuse.
2. Determine the design short-circuit current
Available and/or design short-circuit current is an important consideration when determining the class of fuse and fuse blocks to use. If available short-circuit current cannot be determined, or if it will vary with equipment location, select fuses with a 200,000 ampere interrupting rating (A.I.R.) and mating fuse blocks with a withstand rating of 200,000 amperes for maximum safety.
Class H fuse blocks will accept Class H or K5 fuses (which have an interrupting rating of up to 50,000 amperes) and Class R fuses (which have a 200,000 A.I.R.). To prevent the possibility of inserting a fuse with the incorrect interrupting rating, the use of Class R fuse blocks is recommended for use with Class R fuses. Use Class H fuse blocks with Class H or K5 fuses. These fuse blocks are dimensionally the same, but the Class R fuse blocks incorporate a rejection feature which allows only Class R fuses to be inserted.
3. Determine the type and ampere rating of the fuse to be used
In addition to voltage and interrupting rating as discussed above, the fuse ampere rating, opening characteristics (fast acting or time-delay) and size are other important considerations in fuse selection. Once the fuse type is selected, the mating fuse block can be chosen. Fuse blocks are available in 30, 60, 100, 200, 400 and 600 amp ratings, and may be used with a fuse rated at the corresponding amperage rating or below. For example, a fuse block rated at 30 amperes may be used with a fuse rated from 0 to 30 amperes.
6. Decide on the number of poles in each block
The number of poles for each set of fuses is determined by the characteristics of the circuit. The option to gang individual fuse blocks into long strips will be determined by the available space and by the type of wire being used.
7. Determine if fuse clips need to be reinforced
Fuse clips may have a tendency to lose some of their tension over a period of time. This may be prevented by specifying reinforced fuse clips. Reinforced clips are standard on certain fuse blocks (see individual product pages).
Ordering Information
The Littelfuse fuse block part number consists of 6 or 7 components, as shown below and in the individual fuse block data tables.
Blocks and Holders
© 2005 Littelfuse • POWR-GARD™ Products Catalog
For all Class R, H, J, T and 15, 20 & 60A Class G Fuse Blocks
w w w . l i t t e l f u s e . c o m
For all Class CC, Midget and 30A Class G Fuse Blocks
111
Class J Fuse Blocks
1.16"
[29.4]
.30" TYP.
[7.6]
1.69"
[42.8]
3.38"
[85.7]
.57"
[14.5]
.71"
[17.9]
1.95"
[49.5]
.216[5.5] x .79[20.0] SLOT MOUNTING HOLE
1.69"
[42.8]
3.38"
[85.7]
.57
[14.5]
" TYP.
2.20"
[56.0]
1.04"
[26.4]
1.69"
[42.8]
3.38"
[85.7]
3.25"
[82.5]
1.04"
[26.4]
1 POLE 2 POLE 3 POLE
600 Volt
Blocks and Holders
Class J 600V
Connector Type
Amp
Rating
No. of Poles
Catalog Number
1 LJ60030-1 S (R) P (R) C (R)
30
2 LJ60030-2 S (R) P (R) C (R) 3 LJ60030-3 S (R) P (R) C (R)
Adder LJ60030-A S (R) P (R) C (R)
1 LJ60060-1 C (R)
60
2 LJ60060-2 C (R) 3 LJ60060-3 C (R)
100
200
400
600
1 LJ60100-1 CR 3 LJ60100-3 CR 1 LJ60200-1 C 3 LJ60200-3 C 1 LJ60400-1 CR 3 LJ60400-3 CR 1 LJ60600-1 CR 3 LJ60600-3 CR
Note: Reinforcing springs standard on all Class J fuse blocks rated 100A and above.
*For optional fuse block covers, refer to POWR-Covers section of this catalog. For reinforcing clips on blocks rated 30-60 amp, add “R” suffix to connector type.
(Add Suffix Shown)
Pressure
Screw
Plate
Box Lug
Maximum Wire Size
S & P = #10 CU
C = #6 CU
C = #2 CU-AL
#2/0 CU-AL
250 MCM CU-AL
(2) 350 MCM CU-AL
(2) 500 MCM CU-AL
Features/Benefits
• Phenolic blocks have side barriers for isolation.
• Spring reinforced fuse clips are standard on 100A and larger blocks. Reinforcing springs are optional on 30 and 60 amp blocks.
Space saving 30A design — Up to 45% smaller than existing
30A fuse blocks. 30A interlocking adder block available to create any number of poles (consult factory for availability). Integral DIN rail mount allows this block to be securely fastened to 35 mm “hat” type DIN rails without the use of tools.
LJ60 030
Specifications
Voltage Ratings: 600 Volts Ampere Ratings: 0 – 600 amperes Approvals: UL Listed: File No. E14721
CSA Certified: File No. LR73091
Recommended Fuses
JTD_ID/JTD (time-delay) and JLS (fast acting) series fuses
Blocks and Holders
© 2005 Littelfuse • POWR-GARD™ Products Catalog
w w w . l i t t e l f u s e . c o m
117