POWR-GARD® Fuse Datasheet
CLASS T – JLLN / JLLS SERIES FUSES  
300/600 VAC • Fast-Acting • 1-1200 A
Ordering Information
1 30 90 250 800 
2 35 100 300  900* 
3 40 110 350 1000
6 45 125 400 1100 
10 50 150 450 1200 
15 60 175 500
Description
JLLN/JLLS fuses are less than 1/3 the size of comparable 
Class R fuses and are typically used for short circuit 
protection of drives and surge sensitive components. When 
rated in accordance with the NEC
®
, JLLN/JLLS fuses provide 
fast-acting overload and short circuit protection for noninductive circuits and equipment.
Applications
• Variable speed drive protection 
• Compact mains switches
20 70 200 600 
25 80 225 700
*JL L S o n l y
Note: Contact the factory for RoHS compliant Class T fuses.
SERIES VOLTA GE AMP
JLLS 600 6 – JLLS006 JLLS006.T 
JLLN 300 35 V JLLN035V JLLN035.TXV
Part Numbering System
AMPERE R ATINGS
MOUNTING 
SUFFIX
CATALOG 
NUMBER
ORDERING 
NUMBER
Features/Benefits
• Extremely current-limiting
• Compact design
• 200 kA Interrupting Rating
Specifications
Voltage Ratings    AC: 300 V (JLLN) 
600 V (JLLS)
  DC: 160 V (JLLN 1 – 60 A) 
125 V (JLLN 70 – 1200 A)  
300 V (JLLS)
Interrupting Ratings  AC: 200 kA rms symmetrical 
  DC: 20 k A (JLLN & JLLS)
Ampere Range  1 – 1200 A 
Approvals  AC: Standard 248-15, Class T 
UL Listed (File: E81895) : 
JLLN (1 – 1200 A) 
JLLS (1 – 800 A) 
UL Recognized (File: E71611) 
JLLN PCB Mount (35 – 60 A) 
JLLS ( 900 – 1200 A) 
CSA Certified (File: LR29862) 
JLLN/JLLS (1 – 600 A)
  DC: UL Listed (File: E81895): 
JLLN (35 – 1200 A) 
Littelfuse self-certified 
JLLN (1 – 30 A) 
JLLS (1 – 1200 A)
Environmental  RoHS Compliant
JLLN xxx T XL
Series
Amperage
Package Quantity
T = 10 (1-60 A ) 
V = 5 (70-100 A) 
X = 1 (110-1200 A)
Mounting Options
JLLN 35-6 0 A Only
Blank = Cartridge Type 
XL = Leaded 
XV = Vertical Mount 
XLS = Solder Lead 
Web Resources
TC Curves, downloadable CAD drawings and other technical 
information: 
Littelfuse.com/jlln 
Littelfuse.com/jlls
Recommended Fuse Holders
LFT30 Series 
LFT60 Series 
LSCR Series for 700-800 A
Dimensions
Please refer to the Class T dimensions on page 3
1 of 3
© 2013 Littelfuse POWR-GARD® ProductsLittelfuse.com 
Rev: 012413
 

POWR-GARD® Fuse Datasheet
2000
3000
4000
6000
8000
10000
20000
30000
40000
60000
80000
100000
200000
100
200
300
400
600
800
1000
100
200
300
400
600
800
1000
2000
3000
4000
6000
8000
10000
20000
30000
40000
60000
80000
100000
200000
300000
400000
600000
800000
1000000
800A 
600A
400A
200A
100A 
60A
30A
PEAK LET-THRU IN AMPERES
AVAILABLE FAULT CURRENT
SYMMETRICAL R. M. S. AMPERES
JLLS
CLASS T – JLLN / JLLS SERIES FUSES  
Peak Let-Thru Curve and Current-Limiting Effects of JLLN (300 V) Fuses 
JLLN
1000000
800000 
600000
400000 
300000
200000
100000
80000 
60000
40000 
30000
20000
10000
PEAK LET-THRU IN AMPERES
8000 
6000
4000 
3000
2000
1000
SHORT 
CIRCUIT 
CURRENT*
 5,000 
 10,000 
 15,000 
1200A 
800A
600A 
400A
200A
100A
60A 
30A
 20,000 
 25,000 
 30,000 
 35,000 
 40,000 
 50,000 
 60,000 
800 
600
400 
300
200
100
100
200
300
400
600
800
2000
3000
4000
6000
1000
AVAILABLE FAULT CURRENT
SYMMETRICAL R. M. S. AMPERES
8000
10000
20000
30000
40000
60000
80000
100000
200000
 80,000 
 100,000 
 150,000 
 200,000 
*Prospective RMS Symmetrical Ampere s Shor t-Circuit Current
Note: Data Derived from Peak Let-Thru Curves
APPA RE NT RMS SYMMETRICA L CURRE NT F OR 
VARIOUS FUSE RATINGS
30 A 6 0 A 100 A 2 00 A 4 00 A 600 A 800 A 1200 A
700 775 1,100 1,650 3,500 4,000 5,000 5,000
900 1,000 1, 4 0 0 2 ,100 4,400 5,10 0 6,750 8,250
1,000 1,100 1, 600 2,400 5,000 5,900 7,750 10,000
1,100 1,25 0 1,80 0 2,700 5,500 6,500 8,750 11,000
1,230 1, 300 1, 950 2,900 6,000 7,000 9,500 12,000
1,3 00 1,47 5 2,050 3,100 6,400 7,500 10,000 12,500
1,3 30 1,57 5 2,150 3,300 6,750 7,7 5 0 10,500 13,500
1,4 30 1,60 0 2,300 3,500 7,000 8,000 11,000 14,000
1,500 1,7 50 2,400 3,700 7,500 8,750 12,000 15,000
1,700 1,900 2,700 4,000 8,000 9,500 12,500 16,000
1,8 50 2,10 0 2,800 4,400 9,000 10,500 14,000 17,500
2,000 2,250 3,15 0 4,800 9,750 11,500 15,000 18,500
2,300 2,600 3,600 5,500 11,000 13,000 17,500 22,000
2,600 2,800 3,900 6,000 12,000 14,500 19,500 24,000
Peak Let-Thru Curve and Current-Limiting Effects of JLLS (600 V) Fuses 
JLLS
1000000
800000 
600000
400000 
300000
200000
100000
80000 
60000
40000 
30000
20000
10000
8000 
6000
4000 
3000
2000
PEAK LET-THRU IN AMPERES
1000
800 
600
400 
300
200
100
SHORT 
CIRCUIT 
CURRENT*
 5,000 
 10,000 
 15,000 
800A 
600A
400A
200A
100A 
60A
30A
100
200
300
400
600
800
2000
3000
4000
6000
1000
AVAILABLE FAULT CURRENT
SYMMETRICAL R. M. S. AMPERES
8000
10000
20000
30000
40000
60000
80000
100000
200000
 20,000 
 25,000 
 30,000 
 35,000 
 40,000 
 50,000 
 60,000 
 80,000 
 100,000 
 150,000 
 200,000 
*Prospective RMS Symmetrical Ampere s Shor t-Circuit Current
Note: Data Derived from Peak Let-Thru Curves
2 of 3
APPA RE NT RMS SYMMETRICA L CURRE NT F OR 
VARIOUS FUSE RATINGS
30 A 60 A 100 A 200 A 400 A 600 A 8 00 A 1200 A
750 1,22 5 1,4 00 2,850 4,600 5,000 5,000 5,000
945 1, 525 1,7 0 0 3,600 6,000 8,500 9,400 10,000
1,0 5 0 1,700 2,000 4,050 6,600 9,750 10,500 13,000
1,150 1,900 2,200 4,450 7,25 0 10,500 11,000 14,750
1,3 00 2,050 2,400 4,800 8,000 11,500 12,500 15,500
1,3 75 2,150 2,450 5,000 8,250 12,000 13,75 0 16,500
1,4 00 2,250 2,600 5,100 8,500 13,000 14,000 17,000
1,4 25 2,400 2,800 5,200 8,700 14,000 14,750 18,000
1,6 0 0 2,450 2,900 6,000 9,500 14,500 16,000 20,000
1,6 5 0 2,625 3,100 6,250 10,000 15,500 17,3 0 0 21,000
1,8 25 2,800 3,400 7,000 11,000 17,000 18,7 50 23,000
2,000 3,100 3,70 0 7, 2 5 0 12,000 18,000 20,000 25,000
2,250 3,400 4,300 8,500 13,000 21,000 23,000 28,500
2,450 3,800 4,600 9,000 15,000 23,000 25,000 31,000
© 2013 Littelfuse POWR-GARD® ProductsLittelfuse.com 
Rev: 012413