Protection Relays & Controls
Generator & Single-Function Protection–Power
G2000 SERIES
Power Relay
Simplified Circuit Diagram
Description
The G2000 Power Relay is intended for detection of power
level for protection, control and monitoring purposes. In
the default configuration, the G2000 acts as a reverse
power relay for protection of generators running in parallel.
Basic adjustments can be done on the dials on the front
panel. More configuration options are available through PC
configuration via the optional G0100 Programming Kit. PC
programming enables the user to reconfigure the relay as an
overload relay and allows extension of the ranges on the dials
on the front panel.
One version covers all system voltages from 63 Vac to
690 Vac. Rated voltage can be adjusted by a preset button or
PC configuration. Auxiliary supply voltage is 24 Vdc.
24 Vdc
+ –
PICKUP
RELAY
RESET
G2000
(Power Relay)
TRIP
RELAY
Ordering Information
ORDERING NUMBER CONTROL POWER
G2000.0010
ACCESSORIES REQUIREMENT
24 Vdc, 5 A
G0100 Optional
Accessories
G0100 Programming Kit
Connects to RS232 port. Includes blank frontplate labels and permanent pen for texting scales.
Features & Benefits
FEATURES BENEFITS
PC configuration
User configurable scales and
setpoints
63 Vac to 690 Vac systems can
be monitored by the same unit
Forward power or reverse power
relay functionality
Suits broad variety of applications
Supports wide range of system voltages
Specifications
L
1
L
2
L
3
Supply 8-36 Vdc/0.75 W at 24 Vdc
Input Voltage
Input Current 5 A CT, max. 10 A
Frequency 35 -75Hz
Trip Level RP: 2-20% (max. 2-50%)
FP: 50-140% (max. 50-150%)
Hysteresis 1-10% (max . 1-50%)
Delay 2-20 sec. (max. 1-360 sec.)
Relay Rating 380 Vac, 5 A, 1250 VA, 150 Vdc, 5 A, 120 W
Pick-up Relay Normal state: ND (NE)
Latching: Non-latching
Trip Relay Normal state: ND (NE)
Latching: Non-latching (latching)
Reset Automatic (manually by terminal 11)
Accuracy ± 5%
Repeatability ± 1%
Serial Link R J11-modular
Operating Temperature –20°C to + 70°C
EMC EN50263
Burn-in 50 hours before final test
Enclosure Material Polycarbonate. Flame retardant
Weight 0.3 kg
Dimensions H 73 mm (2.87”); W 75 mm (2.95”);
Installation 35 DIN rail or two 4 mm, (
63-690 Vac ± 30%
D 114 mm (4.49”)
3
/16”) screws
© 2013 Littelfuse Protection Relays & Controls
Littelfuse.com/g2000
Rev: 4-A-050213