Littelfuse D0920 User Manual

Protection Relays & Controls
Arc-Flash Monitoring
D0920 ARC DETECTION UNIT
Arc Detection Unit
Installation Diagram
The D0920 Arc-Flash relay provides a simple and cost effective solution for Arc-Flash monitoring. Two light sensors can be connected directly to one relay.
Light Sensors react to light and have a 180º detection zone. Sensors are supplied with 10 or 15 m of cable. 1-2 sensors are recommended per cubicle or drawer.
Features & Benefits
FEATURES BENEFITS
Compact module
Trip time <1 ms
Two optical sensor cable lengths
Inputs for two sensors
Adjustable light sensitivity
Service mode
Fits into wide range of Arc-Flash applications
Limits Arc-Flash damage and risk of injury
Point sensors with 10 or 15 m of cable
Single Arc-Flash relay can monitor 2 sensors
Allows operation in bright environments and maximum sensitivity in dark environments
Allows relay and sensor test without tripping system
Install sensors in line of sight to possible arc faults.
Ordering Information
ORDERING NUMBER CONTROL POWER
D0920.0010
D0920.0020
ACCESSORIES REQUIREMENT
A0033.0010 Detector cable 2 x 0.25 mm2 w/screen. 100 m
A0220.0010 Arc Detector V-Type; 10 m cable A0220.0020 Arc Detector V-Type; 15 m cable
PGA-1100/D1100 Diode Logic Unit
230 V AC +15, -30%
230 V AC +15, -30%, remains powered on after trip
Optional
Required: At least one sensor per monitored zone
Optional
Accessories
A
A0220 Light Sensors
Line-of-sight light sensor detects an arc as small as 3 kA within a 2-m half-sphere. Available with 10 or 15 m cable.
PGA-1100/ D1100 Diode Logic
For tripping one circuit breaker with multiple D0920 Relays
Specifications
Supply Voltage 230 V AC Thyristor Output 325 V DC from charged capacitor, nominal energy 3.5 J Sensitivity Adjustable 2 - 24 klux Number of Sensors Max. 2 Response Time Less than 1 ms Power Consumption 3.5 VA Ambient Temperature –25°C to 70°C Dimensions H 90 mm (3.5”); W 105 mm (4.1”); D 75 mm (3.0”) Certification CE
+15,-30%
© 2014 Littelfuse Protection Relays & Controls
Based on Manual Rev: 0-B-011014
Rev: 4-A-021014