Littelfuse D0100 User Manual

Protection Relays & Controls
Arc-Flash Monitoring
D0100 SERIES & D0900 SERIES
Arc-Flash Relay
Description
The D0100/D0900 Arc-Flash relays provide a simple and cost­effective solution for Arc-Flash monitoring. Two light sensors can be connected directly to one relay, or optional junction boxes allow up to 16 sensors per relay.
Light Sensors react to light and are available with 180º or 360º detection area. Sensors are supplied with 5, 10 or 15 m of cable and a mounting bracket. 1-2 sensors are recommended per cubicle or drawer.
Installation Diagram
Place sensors in direct line of sight to possible arc faults, preferably pointing down from the ceiling.
Ordering Information
ORDERING NUMBER CONTROL POWER
D0100.0010 D0100.0020 D0900.0010
ACCESSORIES REQUIREMENT
A0033.0010 Detector cable 2 x 0.25 mm w/screen. 100 m
A0200.0010 Light Sensor 180˚; 5 m cable A0200.0020 Light Sensor 180˚; 10 m cable A0200.0030 Light Sensor 180˚; 15 m cable A0300.0010 Light Sensor 360˚; 5 m cable A0300.0020 Light Sensor 360˚; 10 m cable A0300.0030 Light Sensor 360˚; 15 m cable
D0400.0010 For 8 sensors, without indication
D0500.0010 For 8 sensors, with indication
D1100.0010 Diode Logic Unit
Junction Box.
Junction Box.
48-220 Vdc 24 Vdc 220-250 Vac
Optional
Required: At least 1 sensor per cubicle or drawer
Optional
Optional
Optional
Features & Benefits
FEATURES BENEFITS
Compact module
Trip time <1 ms
Two optical sensor types
Dual sensor input
Sensor expansion option
Adjustable light sensitivity
Service mode
Fits into wide range of Arc-Flash applications
Limits Arc-Flash damage and risk of injury
Point sensors with 180° or 360° detection area depending on specific installation
Single Arc-Flash relay can monitor 2 sensors or junction boxes
Junction box allows for up to 16 sensors per Arc-Flash relay (8 sensors/box)
Allows for operation in bright environments and maximum sensitivity in dark environments
Allows for system test without tripping
Accessories
A
A0200 (180˚)/A0300 (360˚) Light Sensors
Line-of-sight light sensor detects an arc as small as 3 kA within a 2-m half-sphere. Available in 180˚ or 360˚; 5, 10, or 15 m cable.
D0400/D0500 Junction Box for parallel connection
of more than 2 sensors for one relay. Designed to connect up to 8 sensors, and is available with and without indication. Max. 2 junction boxes can be connected to one Arc-Flash relay.
Specifications
Voltage Supply D0100.0010: 48-220 Vdc D0100.0020: 24 Vdc D0900.0010: 220-250 Vac D0900.0020: 220-250 Vac D0900.0030: 110 Vac
Thyristor Output 250 Vac/Vdc, 8 A cont., 25 A. for 0.1s, min. load 50 mA Sensitivity Adjustable 2,000-24,000 lux Number of Sensors Max. 16 pcs. with 2 junction boxes Response Time Less than 1 ms Power Consumption D0100: 4.3 W; D0900: 3.5 W Ambient Temperature –25°C to + 70°C EMC EN50081-1/2 and EN50082-1/2 Dimensions H 90 mm (3.5”); W 105 mm (4.1”); D 75 mm (3.0”)
© 2013 Littelfuse Protection Relays & Controls Littelfuse.com/d0900
Rev: 4-A-050213
Loading...