Littelfuse B9300 User Manual

B9300 Power Reference Unit
POWER REF. UNIT
B9300
ON
100
MAINS-SWITCH
POWER REFERENCE B9300-XX-14
LOAD SHARER
T4400
LOAD SHARER
T4400
BUS
GRID
MAINS-SWITCH
AUT./MAN.
POWER REFERENCE B9300-XX-10
MOTOR SUPPLY
DECR.INCR.
GEN.
1
LOAD SHARER
T4800
AUT./MAN.
LOAD SHARER
T4800
MOTOR SUPPLY
DECR.INCR.
GEN.
1
BUS
GRID
• Setting of generator capacity via SELCO load sharers
• DC output (0 - 1V DC, ±1V DC, 0 - 3V DC or 0 - 5V DC)
• Knob for manual control
• Screw lock for knob
• 50 hours burn-in before test
• Ambient temperature range:
-20°C to +70°C
• Flush mounted unit
Application
The B9300 Power Reference Unit is applied for setting the capacity to be provided by the engine driven gene­rator(s) when the generators are operated in parallel with a grid (utility) or a shaft generator.
The B9300 is used as a complementary unit to SELCO’s range of load sharers (Load Sharer type T4300, T4400 and T4800).
Function
The load sharer will adjust the power of an engine driven generator according to the setting of the knob placed on the front panel of the Power Reference Unit. The setting is 0 - 10 (equivalent to 0 - 100 %).
A finger screw is provided for locking the dial.
to half of its original setting. If instability occurs, the dead band zone should be increased by increasing the STABILITY setting on the T4800.
tiometer Type and B9300 Power Reference Unit is available. The unit is specified E7800-9x. For details, please refer to the data sheet for the E7800
Motorized Potentiometer. This data The B9300 Power Reference Unit is for flush mounting and it has standard
sheet can be downloaded from our web
site www.selco.com instrument dimensions 96 x 96 x 80mm (H x W x D).
Example of setting:
Generator rating: 695A at PF 0.8
Active current: 695 x 0.8 = 556A
Option
In order to obtain remote setting of the power reference function, a combina­ tion of Selco’s E7800 Motorized Poten-
Current transformer: 800/5
Maximum on dial: 10
Full load on dial: 10 x 556/800 = 6.95
(69.5%)
The same Power Reference Unit can also be connected to several load sharers where a multi engine installa­ tion is operating in parallel with a grid supply.
The output of the B9300 Power Reference Unit (terminals 5 and 3) is connected to the parallel lines of the load sharer(s) (terminals 12 and 13).
The connection of terminal 5 of the B9300 Power Reference Unit and terminal 13 on the SELCO T4800 Load Sharer will disable the frequency control function in the load sharer. This is used when running parallel to the grid (utility) or other frequency determining power sources.
Please note that the dead band zone in the T4800 Load Sharer will be reduced
Fig. 1. Application Diagram. B9300 with T4400. Fig. 2. Application Diagram. B9300 with T4800.
Fig. 3. Dimensions.
75mm
26
96mm
Cut out 92 x 92mm
96mm
SELCO Worldwide
Specifications
B9300 Power Reference Unit
Max. voltage 480V Voltage range 90 - 120% Consumption DC output 0 - 1V DC, ±1V DC, 0 - 3V DC or 0 - 5V DC Operating temperature -20 to +70°C EMC CE according to EN50081-1, EN50082-1, EN50081-2,
EN50082-2
Burn-in 50 hours before final test Weight 0.7kg Dimensions 96 x 96 x 80mm (H x W x D) Panel cut out 92 X 92mm (H x W)
The specifications are subject to change without notice.
Type Selection Table
Terminals Type 1-2 Function B9300.0010 220-240V Output 0 - 1V DC B9300.0030 220-240V Output 0 - 3V DC, to be used with T4300/T4400-xx B9300.0040 220-240V Output 0 - 3V, to be used with T4300/T4400-xx,
max. adjustment from 1.5 - 3V DC B9300.0050 100-110V Output 0 - 1V DC B9300.0060 380-450V Output 0 - 1V DC B9300.0070 380-450V Output ±1V DC B9300.0090 415-480V Output 0 - 1V DC
Other voltages and combinations are available on request.
2VA at UN
Main office: SELCO A/S
Betonvej 10 DK-4000 Roskilde Denmark Phone: + 45 7026 1122 Fax: + 45 7026 2522 e-mail: selco.dk@selco.com www.selco.com
B9395-72 E