Personnel Protection
Industrial Shock-Block
SB6000 SERIES
Industrial
Open-Chassis Model*Enclosed Model*
Operator Interface*
*Patent Pending
Simplified Circuit Diagram
K
L1
L2
*
L3
G
AUXILIARY 
CONTACT
SB6100
ENCLOSED SB6100 MODELS
* For a single-phase load; Jumper L
& use L1 & L2 as the input terminals
Ordering Information
ORDERING 
NUMBER
SB6100-00x-0 208
SB6100-10x-0 240
SB6100-20x-0 480
SB6100-30x-0 600
SB6100-01x-0 208
SB6100-11x-0 240
SB6100-21x-0 480
SB6100-31x-0 600
Note: x=0 for open-chassis models and 1 for enclosed models
VOLTAGE 
(V)
GC
G
2 
TRIP 
LEVEL (mA)
20 
(Fixed)
6, 10, 20, 30 
(Selectable)
& L
3
LOAD
A
B
TERMINATION 
DEVICE
SB-OPI
(Operator 
Interface)
UL CATEGORY/CLASS
UL 943C Class C 
special-purpose GFCI
UL 943C Class D  
special-purpose GFCI
UL 943/UL 1053 
Equipment ground-fault 
protective device (EGFPD)
Description 
Special Purpose Ground-Fault Circuit Interrupter (GFCI),  
Class C and Class D
Industrial Shock Block (ISB) is a personnel protection device designed to meet 
the new requirements for special-purpose GFCIs defined by UL 943C. ISB is the 
first and only permanently connected Class C and Class D GFCI on the market. 
Class C GFCIs is introduced to be used on systems where the line -to-line voltage 
is 480 V or less with a trip level of 20 mA, while Class D GFCI is intended to be 
used on 600 V systems. These improvements to the standard Class A GFCI (6 mA 
trip level used on 240 V systems or less) were made to allow the use of GFCIs in 
industrial facilities. 
Equipment Ground-Fault Protective Device (EGFPD) 
ISB is also available with adjustable protection settings as an EGFPD. The EGFPD 
models can be set to trip at 6, 10, 20 or 30 mA. This offers more flexibility since 
GFCI devices are not allowed to have an adjustable trip level. 
Rating and Models
ISB (GFCI & EGFPD) is available for voltage from 208 to 600 V with a maximum 
full load current of 100 A , and a built- in overcurrent protection supplied by 
Littelfuse Class T fuses. The load can be 1-phase (line -to-line) or 3-phase, 
however, cannot have a neutral. The power system can either be solidly- grounded 
or high-resistance grounded. 
Two options for enclosures are available: UL-recognized open- chassis models 
are available for installation in existing electrical enclosure and UL-listed enclosed 
models include a NEMA-4X enclosure for stand-alone installations. 
Ground Wire (Load-Ground) Monitor
The ISB also monitors the ground wire (load- ground) connection between the ISB 
and load. This is a required feature for GFCI devices and is optional for EGFPD 
devices. If the connection is broken, the ISB will provide an alarm by changing the 
state of the alarm contacts. This monitoring circuit includes an extra wire (pilot 
wire) between the ISB and load (since the monitoring current is low, only a small 
wire is required). At the load, the pilot wire is connected to a termination device. 
The other end of the termination device is connected to the load ground (typically  
the enclosure)
Features & Benefits
FEATURES BENEFITS
UL 943 inverse time trip curve
Minimum trip time < 20 msec
UL 943C fixed trip level  
(GFCI 20 mA)
Selectable trip levels  
(EGFPD)
UL 943C ground monitor/ 
interrupt 
Undervoltage, brownout, 
chatter detection 
3 x Class T, 600 V  
incoming fuses
Conformal coating
Operator Interface
Auxiliary Contact Provides a normally-open contact for remote indication
Dete cts and inter rupts to pr otect peo ple and reduce the 
prob ability of nuisa nce trippin g
Reduc es the risk of ve ntricular fib rillation for le akage curre nt of 
250 m A and above 
GFCI protection for systems with leakage current higher than the 
standard 6 mA required by UL 943 Class A
Provides extra safety when a customer is able to operate with a 
setting below 20 mA (GFCI) and the settings above 20 mA can 
reduce nuisance tripping on systems with high leakage current.
Protects from shock by tripping if continuity of ground wire 
between Industrial Shock-Block and load is broken.
Ensures proper operation and prolongs the internal contactor 
lifetime 
The fuses provide overcurrent protection for a 100 A circuit and a 
higher short-circuit current (SCC) rating of 50 kA.
Internal circuits are conformally coated to protect against corrosion 
and moisture, yet still repairable 
Shows unit status, alarm types, percentage of leakage current, and 
allows for Test and Reset capabilities
Littelfu se reserves the r ight to m ake product changes, wit hout notice . Mate rial in this document is as accurate as know n at the time of pu blication. V isit Littel fuse.com for the mo st up-to- date information.
© 2013 Littelfuse Protection Relays & Controls 
© 2013 Littelfuse Protection Relays & Controls 
Littelfuse.com/IndustrialShockBlock
Based on Manual Rev. 1-B-112913
Rev: 4-H-112613 

Personnel Protection - PRELIMINARY 
Industrial Shock-Block
SB6000 SERIES
Accessories
A
B
Operator Interface  
(AC6000-OPI-00)
1N5339B - Termination Device 
Axial-lead ground-check termination, 
included with SB6000 series
SE-TA6 - Termination Assembly 
Optional termination assembly with 
terminals and mounting holes
SE-TA6-SM Stud-Mount  
Termination Assembly 
Optional ground-check termination 
for submersible pumps.
AC6000-CART-00  
Two-wheeled Cart
Optional for mounting ISB to allow for 
moving the unit while power is off
Connection Diagram
The SB6100 is installed in-line between incoming power or 
existing over-current protection device and the load. 
The open-chassis SB6100 can be installed in electrical 
equipment and the enclosed version is typically wall-mounted.
Incoming Power
Circuit Breaker
SB6100 
Industrial 
Shock-Block 
Open-Chasis 
Model
Circuit Breaker
SB6100 Industrial 
Shock-Block 
Enclosed Model
AC6000-MNT-00  
Mounting Frame
Optional for mounting ISB to a cart 
or other surface. Included with the 
AC6000-CART-00.
Ordering Information - Accessories
ACCESSORIES REQUIREMENT PAGE*
AC6000-OPI-00 Included N/A
1N5339B Included 120
SE-TA6 Optional 120
SE-TA6-SM Optional 120
SE-TA6ASF-WL Optional 120
AC6000-CART-00 Optional N/A
AC6000-MNT-00 Optional N/A
Specifications
Voltage Rating  See ordering information
Amperage Rating  100 A (continuous)
Load    3-phase, 3-wire (no neutral) or 1-phase 
  (line-to-line), 60 Hz
Short Circuit Rating  50,000 A  
Trip Level Settings   Selectable (6, 10, 20, 30 mA), or fixed at 20 mA 
Trip Time Setting  Inverse time trip curve
Enclosure  NEMA 4X, Polyester, Lockable
Operating Temperature –35°C (–31°F) to +40°C(104°F), up to +66°C (151°F) 
  with derating
Wiring Requirements  2/0 AWG (maximum)
Approval  GFCI: UL Listed (enclosed models) and UL Recognized 
  component (open-chassis models) EGFPD: cULus Listed  
  (enclosed models) and cURus Recognized Component  
  (open-chassis models)
Dimensions  Enclosed: H 453.8 mm (17.9”);  
  W 406.2 mm (16.0”); D 223.3 mm (8.8”)
  Open-chassis: H 455.0 mm (17.9”);  
  W 340.7 mm (13.4”); D 174.9 mm (6.8”)
Warranty  1 year
© 2013 Littelfuse Protection Relays & Controls 
© 2013 Littelfuse Protection Relays & Controls 
Littelfuse.com/IndustrialShockBlock
Based on Manual Rev. 1-B-112913
Rev: 4-H-112613