Catalog Option Option Option Option Option Option Option Option
No Rating Rating Code Rating Code Rating Code Rating Code Rating Code Rating Code Rating Code Rating Code
LPS3 30A 208V T20 24 VDC Coil R2 120V K Red R 30–60A N6 1 NO & 1 NC A Single Pole F1 NEMA 3R U
LPS6 60A 240V T24 120 VAC Coil R1 Green G 100A N1 2 NO & 2 NC B Three Pole F3 NEMA 4 Y
LPS1 100A 480V T48 White W 200A N2 NEMA 12 Z
LPS2 200A 600V T60 400A N4
LPS4 400A
Catalog Amp NEMA 1 NEMA 3R NEMA 4, 12 Lug
Series Rating Dimensions Dimensions Dimensions Size
LPS3 30 24”H x 20”W x 9”D 24”H* x 20”W x 8”D 24”H x 20”W x 10”D #14 - #8 AL or CU
LPS6 60 24”H x 20”W x 9”D 24”H* x 20”W x 8”D 24”H x 20”W x 10”D #14 - #8 AL or CU
LPS1 100 24”H x 20”W x 9”D 24”H* x 20”W x 8”D 24”H x 20”W x 10”D #8 - 1/0 AL or CU
LPS2 200 30”H x 20”W x 9”D 30”H* x 20”W x 8”D 24”H x 20”W x 10”D #6 - 250kcmil AL or CU
LPS4 400 48”H x 36”W x 12”D Contact Factory Contact Factory Contact Factory
Amp Voltage Max Max Momentary
Rating Rating Inrush Ontime Inrush
30–400 120V, 60Hz 4A 1.5 cycles 140VA
Littelfuse
Switch Catalog
Number
Control Power
Transformer
Std. 100VA with
PRI & SEC
Fuse (120V
Sec.)
Fire Safety
Interface Relay
(3PDT, 10amp,
120V)
Key to Test
Switch
Pilot Light
“ON”
Isolated Neutral
Lug
Mechanical Interlock
Auxilliary Contact
forHydraulic
Elevators w/
Automatic Recall (5
amp 120 VAC rated)
Fire Alarm
Voltage
Monitoring Relay
(Tp Monitor
Shunt Trip
Voltage)
Optional
Enclosures
149
LPS Series POWR-SWITCH
SPECIFICATIONS
Approvals: UL Listed and CSA Certified
Rating: 30A, 60A, 100A, 200A, 400A
Shunt Trip Ratings:
ORDERING INFORMATION
Complete catalog numbers consist of switch catalog numbers and the desired options. See example below.
ENCLOSURE DIMENSIONS
Note: Over-size enclosures used to accomodate control power transformer, interface relay and terminal blocks.
*For NEMA 3R enclosures add 2 inches to height for mounting tabs.
Example Catalog Number:
LPS T8 R1 K N1 U = Littelfuse Catalog Number LPS1T48R1KN1U
Note: Desired options must appear in the order shown above. Typical options include Control Power Transformer, Fire Safety Interface
Relay, Mechanical Interlock Auxiliary Contact and Fire Alarm Voltage Monitoring Relay.