Littelfuse 700-xxx User Manual

POWR-GARD® Fuses—Medium Voltage
MEDIUM VOLTAGE FUSES
2,400-38,000 VAC • Current-Limiting
Current-limiting E- and R-rated fuses are equipped with a mechanical indicator or striker pin that protrudes through the fuse cap upon operation of the fuse. This provides visual identification of a blown fuse and can be used as a trigger for external devices.
1
Note: Extension distance extension force 2 lb. minimum.
/
2” minimum;
General Information
The terms “Medium Voltage” and “High Voltage” have been used interchangeably by many people to describe fuses operating above 600 volts. Technically speaking, medium voltage fuses are those intended for the voltage range from 2,400 to 38,000 VAC. High voltage fuses are for circuits carrying voltages greater than 38,000 VAC.
Description
Littelfuse® offers a selection of E- and R-rated medium voltage fuses for the protection of trans formers, potential transformers, feeders, and motor circuits. Single, double, and triple barrel designs are available to cover a wide range of current, voltage, and interrupting ratings. Conventional ferrule type, clip lock, and bolt-in mounting configurations are available for virtually any application. Hermetically sealed fuses for use in hazardous environments are also offered.
Contact the factory or your local Littelfuse representative for additional fuse ratings or custom mounting configurations.
24-Hour Emergency Service is available. Call 800 -227-0029, Option 6.
Applications
• Power Transformer Protection
• Potential Transformer Protection
• Motor Controller Back-up Protection
• Fused Switches
• Feeder Circuits
E-rated fuses are considered to be general purpose fuses and can be used to protect against low and high values of fault current. R-rated fuses are designed for back-up protection. They must be used in series with other devices such as motor overload relays in order to achieve both overload and short­circuit protection.
Medium voltage fuses are not intended to provide overload protection in the same sense as fuses rated 600 volts or less. Medium voltage fuse current ratings do not have the same meanings as the ampere ratings of low voltage fuses.
All medium voltage fuses are limited in their ability to interrupt low value overcurrents, especially those between 100% and 200% of the fuse’s continuous current rating. They are designed to carry their rated current without exceeding the temperature rise permitted by NEMA and ANSI standards.
Bolt-in Mount Fuses
1
© JUNE 2011 Littelfuse POWR-GARD Productswww.littelfuse.com
POWR-GARD® Fuses—Medium Voltage
R-RATED MEDIUM VOLTAGE FUSES
Current-Limiting
Description
R-rated fuses provide required short- circuit protection for medium voltage motors, motor controllers and associated circuitry. These components have limited ability to absorb the energy of large short-circuit currents. Medium voltage motor controllers contain overload relays which provide both overload protection and locked rotor protection to the motor. The controllers are also intended to interrupt low value short-circuits within the capability of the motor controller. This protects the medium voltage fuse from sustained overcurrents which are less than their minimum interrupting rating.
NEMA Standards for R-rated medium voltage power fuses require they operate within 15-35 seconds when subjected to an rms current 100 times the R rating. For example, a fuse with a 2R rating will open within 15 to 35 seconds on an applied current of 2 x 100 = 200 amperes.
Part N umber Sys tem
130- 4 R-1C-5.5
Max Voltage (K V)
Style: C (Car tridge)
B (Bolt Mount) IB (Inverted Bolt Mount) BI (Bolt-In Mount)
No. of Barrels
Rating (size)
Continuous Current
Dimensions
Dim.A
Clip
Center
3"DIA
6.38"
Dim.B
9.75"
Characteristics
Voltage Ratings: 2,750 V – 8,250 V Current Range: 2R – 36R
Options
• Hermetically sealed for use in hazardous locations (add “S” suffix to part number)
• Bolt-in mounting configurations
Hookeye Feature*
For hookeye attachment; add “W” suffix to part number
* See web for Bolt Mount, Inverte d Bolt Mount, and Bolt-W dimensions
Medium Voltage Fuse Protection
POWR-GARD® medium voltage fuses provide short-circuit protection for motors and transformers rated 2,400 to 38,000 volts AC. Visit www.littelfuse.com/technicalcenter for additional protection tables, sizing recommendations, and applications.
Figure 1 Figure 2 Figure 3
Cartridge “C”
Bolt Mount “B”
Sample Part #: 130 -4R-1B-5.5
Inverted-Bolt “IB”
Sample Part #: 130 -4R-1IB-5.5
2
Bolt-In Mount “BI”
Sample Part #: 130 -4R-1BI-5.5
© JUNE 2011 Littelfuse POWR-GARD Productswww.littelfuse.com
POWR-GARD® Fuses—Medium Voltage
R-RATED MEDIUM VOLTAGE FUSES
Current-Limiting
R
RATED
2.75 KV
R
RATED
5.5 KV
R
RATED
5.5 KV
14”CLIP CENTERS
R
RATED
8.25 KV
For hookeye attachment; add “W” suffix to part number
SySTEM/ CATALOG NUMBER
702R1C2.75 2R 70 7" 10.875" 170 80,000 1
1003R1C2.75 3R 100 7" 10.875" 250 80,000 1
130 4R1C 2.75 4R 130 7" 10.875" 340 80,000 1
150 5R1C2.75 5R 15 0 7" 10.875" 390 80,000 1
1706R1C2.75 6R 170 7" 10.8 75" 500 80,000 1
20 09R1C2 .75 9R 200 7" 10.87 5" 760 80,000 1
23012R1C2.75 12R 230 7" 10.8 75" 1000 80,000 1
39018R2 C2.75 18R 390 7" 10.875" 1500 80,000 2
45024R2C2.75 24R 450 7" 10.8 75" 19 50 80,000 2
SySTEM/ CATALOG NUMBER
702R1C5 .5 2R 70 12" 15.875" 170 80,000 1 1003R1C5.5 3R 100 12" 15.875" 250 80,000 1 1304R1C5.5 4R 130 12" 15.875" 340 80,000 1 150 5R1C5.5 5R 150 12" 15.875" 390 80,000 1 170 6R1C5.5 6R 170 12" 15.875" 500 80,000 1 20 09R1C5 .5 9R 200 12" 15.875" 760 80,000 1
23012R1C5.5 12R 230 12" 15.875" 1000 80,000 1 39018R2C5.5 18R 390 12" 15.875" 1500 80,000 2
45024R2C5.5 24R 450 12" 15.875" 19 50 80,000 2 48026R2C5.5 26R 480 12" 15.875" 210 0 80,000 2 55030R2C5.5 30R 550 12" 15.875" 2400 80,000 2 60032R2C5.5 32R 600 12" 15.875" 2600 80,000 2 65036R2C5.5 36R 650 12" 15.875" 2900 80,000 2 55030R3C5.5 30R 550 12" 15.875" 2400 80,000 3 60032R3C5.5 32R 600 12 " 15.875" 2600 80,000 3 65036R3C5.5 36R 650 12" 15.875" 2900 80,000 3
SySTEM/ CATALOG NUMBER
702R1C5.5X 2R 70 14" 17. 875" 170 80,000 1 1003R1C5.5X 3R 10 0 14" 17. 8 75" 250 80,000 1 1304R1C5.5X 4R 130 14" 1 7.8 7 5 " 340 80,000 1 150 5R1C5.5X 5R 150 14" 17. 8 75" 390 80,000 1 1706R1C5.5X 6R 170 14" 17.875" 500 80,000 1 2009R1C5.5X 9R 200 14" 17.875" 760 80,000 1
23012R1C5.5X 12R 230 14" 17. 87 5" 1000 80,000 1
39018R2C5.5X 18R 390 14" 1 7.8 7 5 " 1500 80,000 2 45024R2C5.5X 24R 450 14" 17.8 7 5" 1950 80,000 2 55030R2C5.5X 30R 550 14” 17.8 7 5” 2400 80,000 2
SySTEM/ CATALOG NUMBER
702R1C8.25 2R 70 12" 15.875" 190 80,000 1 1003R1C8.25 3R 10 0 12" 15.875" 225 80,000 1 130 4R1C 8.25 4R 130 12" 15.875" 330 80,000 1 150 5R1C8. 25 5R 150 12 " 15.875" 440 80,000 1 1706R1C8.25 6R 170 12" 15.875" 500 80,000 1 20 09R1C8.25 9R 200 12" 15.875" 740 80,000 1
23012R1C8.25 12R 230 12" 15.875" 955 80,000 1 39018R2 C8.25 18 R 390 12" 15.875" 144 0 80,000 2 45024R2C8.25 24R 450 12" 15.875" 1910 80,000 2
SIzE
SIzE
SIzE
SIzE
MA xIMUM
CONTINUOUS
CURRENT @
40 DEGREES C°
MA xIMUM
CONTINUOUS
CURRENT @
40 DEGREES C°
MA xIMUM
CONTINUOUS
CURRENT @
40 DEGREES C°
MA xIMUM
CONTINUOUS
CURRENT @
40 DEGREES C°
DIM. A
(INChES)
DIM. A
(INChES)
DIM. A
(INChES)
DIM. A
(INChES)
DIM. B
(INChES)
DIM. B
(INChES)
DIM. B
(INChES)
DIM. B
(INChES)
MINIMUM
INTERRUPTING
RATING RMS
AMPS
MINIMUM
INTERRUPTING
RAT ING RMS
AMPS
MINIMUM
INTERRUPTING
RAT ING RMS
AMPS
MINIMUM
INTERRUPTING
RAT ING RMS
AMPS
MAxIMUM
INTERRUPTING
RATING RMS
(ASyM)
MAxIMUM
INTERRUPTING
RAT ING RMS
(ASyM)
MAxIMUM
INTERRUPTING
RAT ING RMS
(ASyM)
MAxIMUM
INTERRUPTING
RAT ING RMS
(ASyM)
FIGURE
NUMBER
FIGURE
NUMBER
FIGURE
NUMBER
FIGURE
NUMBER
3
© JUNE 2011 Littelfuse POWR-GARD Productswww.littelfuse.com