Lithonia Lighting KBMF1284 Specification

Page 1
FEATURES & SPECIFICATIONS
INTENDED USE  Ideal for applications requiring attractive die-cast aluminum signage, superior il-
lumination and low energy consumption. CONSTRUCTION  Precision-molded, die-cas t aluminum construction — ultra-slim, compact housing.
Fine-grain brushed aluminum faceplate with matte black electrostatic polymeric trim. Clear lacquer finish on brushed face inhibits fingerprints and other surface contaminants.
All electronics located inside housing. Fully overlapping light seal prevents light leaks. Universal directional chevron knockouts are completely
concealed and easily removed. Hinged faceplate and spring latches for easy lamp compartment access, no expos ed hardware.
Letter s 6" high with 3/4" stroke, wi th 100 ft viewing d istance rating , based upon UL924 stan dards.
U.S. Patent No. 5,739,639, 5,954,423 and 6,502,044. Canada Patent No. 2,204,218. Other patents pending.
OPTICS  Lamp is constructed using new LED technology. Provides perfectly uniform illumination to
meet 3/4" lett er stroke requir ed by code. The typ ical life of the ex it LED lamp is 10 years, ba sed on continuo us operation. Un ique LED lamp plat form
accommod ates both single -face and double -face exits. Low energ y consumption — r ed exit consu mes std .81W, 1.3W (120V), green exit con sumes std is 1W, 1.5W
(120V). Universal i nput voltage cap abilities (120V through 27 7V, 50 or 60 HZ). ELECTRICAL  S olid-state electronic elements to eliminate risk of electromechanical failure s. Surge protection meets ANSI/IEEE C62.41 category B and IEC 1000 immunity standards for high voltage
surges, electrostatic discharges, high frequency elect rical fast transients and line voltage dips/swells. Emergency Operation (for EL N option only): Battery: Sealed, maintenance-free nickel-cadmium
batter y delivers 90 mi nutes capacit y to lamp. Self-diagnostics (SD option only): Two-state constant-current charger maximizes batter y life and
automatically recharges after bat tery discharge. Test switch provided for manual testing. Self-diagnostic testing for five minutes every 30 days, 30 minutes at 180-day interval, and 90 minutes
annually. Diagnos tic evaluation of L ED light source, AC to DC tr ansfer, charging an d battery con dition. Continuously monitors AC functionality. Low voltag e disconnect p revents excessi ve deep discharg e that can permane ntly damage the bat tery. Single- point microcom puter control f or all electron ic features. Crys tal oscillator ti ming system wit h watchdog prote ction for pre cision accurac y. AC/LVD reset allows battery connection before AC power is applied and prevents battery damage from
deep discharge. Brownout protection is automatically switched to emergency mode when supply voltage drops below
80% of nomi nal. Single multi-chromatic LED indicator to display two-state charging, test activation and three-state
diagnostic status. Test switch p rovides manual ac tivation of 30 -second diagn ostic testing f or on-demand v isual inspect ion.
Catalog Number
Notes
Type
Die-Cast Aluminum Exits
LE surface
LRE recessed
INSTALLATION  Universal mou nting (top, end or bac k). Double face ava ilable with top o r end mounting
only. LRE: Trim ring has 3/4” depth adjustment to ensure a flush fit against the surface. Protrudes 1/10” from the s urface. No exp osed hardware.
Die-cast aluminum canopy provided for surface mount only. LISTINGS  UL damp location listed 50°F - 104°F (10°C - 40°C). Meets UL 924, NFPA 101 (current Life
Safety Code), NEC and OSHA illumination standards. North Carolina Department of Insurance. NEMA Premium certified.
WARRANTY — 5-ye ar limited warran ty. (Battery is p rorated.) Comple te warranty ter ms located at
www.acuitybrands.com/CustomerResources/Terms_and_conditions
Actual p erformance m ay differ as a result of e nd-user envir onment and applic ation. All values a re design or typ ical values, meas ured under labor atory conditi ons at 25 °C. Note: Spec ifications subj ect to change wi thout notice.
LE and LRE
ORDERING INFORMATION
For shortest lead times, configure products using bolded options.
Example: LE S 1 R EL N SD
Series Face t ype Housing color Number of faces Letter color Input voltage Operation Options
LE LED,
surface mount
LRE LED, r e-
cessed
Accessories: Order as separate catalog num ber.
ELA US12 ELA WG1 Back-mount wir e guard (see spec shee t ELA-WG) ELA WGEXT Top-mount wir e guard (see spec she et ELA-WG) ELA WGEXE End-mount w ire guard (see spec sh eet ELA-WG)
S Stencil P Panel
(blank) Mat te
black, brushed aluminum face
BZ Dark
bronze
W W hite B Matte
black
12” stem kit (se e spec sheet ELA-StemKits)
1 Sing le face 2 Dou ble face
2,8
ELA LEHO 120/277 N Remote-c apable exit with b lack canopy; provi des
ELA ERK Recess mo unting rough-in k it for LRE only (see
2
R Red G Green
(blank) Universal
input voltage (120 ­27 7V, 50 or 60
(blank) AC only EL N Nickel-cadmium
battery back-up
X2 Lamp wire d on two
separate AC circuits
HZ)
90 minute s of 11.1W capacit y for remote head (see spec sh eet ELA-LEHO)
2,8
spec shee t ELA-ERK)
(blank) None TP Two tamper pro of Torx-he ad screws VR Vandal-resistant shield (1/8” thick
polycarbonate)
FI FA Field selectable fire alarm interface
or flashing emergency operation with inter mittent audib le alarm (one flash per min ute)
FI Fire alarm flashing interface FA Flashing emergency operation and
intermittent audible alarm
SD Self-diagnostic s
Notes
1 Panel face avai lable for spec ial wording on ly
(see Cust om Signage spe c sheet). 2 Not available with LRE models. 3 UL Listed as emergency lighting. 4 VR contains tamper proof screws. 5 Available wit h SD option only. 6 Available wit h AC only or EL N opera tion only. 7 Available wit h EL N option only. 8 Add W for white.
EMERGENCY LELRE
Page 2
LE-LRE LED, Signature
LE - End Mounting LE - Top Mounting
(15.2)
(28.9)
STANDARD MOUNTING
MOUNTING WITH OPTIONAL ROUGH-IN KIT (ELA ERK)
Wall opening dimensions: 8-7/8” H x 12-3/8” W x 4” D
SPECIFICATIONS
ELECTRICAL
Primary circuit
Typical LED
Typ e
life
1
Red LED AC only 10 Years
Green LED AC o nly 10 Years
Red LED emergency 10 Years
Green LED emergency 10 Years
BATT ERY
Sealed Nickel-Cadmium
Shelf life
2
Typical life
2
3 years 7-9 years none
Notes
1 The typ ical life of th e exit LED lamp is 10 ye ars, based on c ontinuous op eration.
2 At 77°F (25 °C).
3 All life s afety equi pment, inclu ding emergen cy lighting f or path of egre ss must be main tained, ser viced, and
tested i n accordance wi th all National F ire Protec tion Assoc iation (NFPA) and loc al codes. Failur e to perfor m the requir ed maintenanc e, service, or te sting could j eopardize t he safety of o ccupants an d will void all war ranties.
4 Optimu m ambient tempe rature rang e where unit wil l provide cap acity for 90 m inutes. High er and lower
temper atures affec t life and cap acity.
Supply
voltage Input watts Max. amps
120 0.81 0.05
277 1.2 0.0 6
120 1.05 0.05
277 1.32 0.06
120 1. 3 0.06
277 1.4 0.07
120 1. 5 0.07
277 1.7 0 .07
Maintenance
3
Optimum temperature
50°F – 104° F
(10°C – 40°C)
MOUNTING
All dimensions are in inches (centimeters). For VR option, add 1/4" to height and width . Add 1/8" depth for single f ace; 1/4" depth for do uble face.
Shipping we ight: LE - 4 lbs (1.8 kgs)
LE EL N- 5 lbs (2.3 kgs)
LRE - 4 lbs (1.8 kgs)
LRE EL N - 5 lbs (2.3 kgs)
1-5/8 (4.1)
6
11-3/8 (28.9)
(33.0)
4
12-15/16
(32.9)
Trim ring brackets
(provided)
7-7/8 (20.0)
13
LE - Back Mounting
5-3/4 (14.4)
11-3/8
9-7/16
(24.0)
(10.2)
4-1/2 (11.4)
9-1/2 (24.0)
1-3/4 (4.4)
7-7/8 (20.0)
4
Trim ring
(provided)
SELFDIAGNOSTICS
KEY FEATURE
SD option only)
Five-minute test every 30 days
30-minute test every six months
90-minute test annually
Diagnostics evaluate the battery, lamp, charger and
AC to DC transfer.
Condition Indication Normal mode Steady green
Self-testing Flashing green
Emergency mode Off
Hi-charge Steady red
Battery failure Single-flash red
Lamp failure Double-flash red
Circuit failure Triple-flash red
LE-LRE
EMERGENCY: One Lithonia Way, Conyers, GA 30012 Phone: 800-334-8694 www.lithonia.com © 1994-2018 Acuity Brands Lighting, Inc. All rights reserved. Rev. 02/06/18
The typical life of the exit LED lamp is 10 years.
Wall opening dimensions: 8-3/4” H x 12-3/8” W x 1-3/4” D
Contractor
furnished
supports
8-7/8 (22.5)
4
(10.2)
J-box
(contractor furnished)
12-3/8
(31.4)