READ AND FOLLOW ALL SAFETY INSTRUCTIONS!
SAVE THESE INSTRUCTIONS AND DELIVER TO OWNER AFTER INSTALLATION
· To reduce the risk of death, personal injury or property damage from fi re, electric shock, falling parts, cuts/ abrasions, and other hazards please read all warnings and instructions included with and on the fi xture box and all fi xture labels.
· Before installing, servicing, or performing routine maintenance upon this equipment, follow these general precautions.
· Installation and service of luminaires should be performed by a qualifi ed licensed electrician.
· It will occasionally be necessary to clean the outside of the refractor/lens. Frequency of cleaning will depend on ambient dirt level and minimum light output which is acceptable to user. Refractor/lens should be washed in a solution of warm water and any mild, non-abrasive household detergent, rinsed with clean water and wiped dry. Should optical assembly become dirty on the inside, wipe refractor/lens and clean in above manner, replacing damaged gaskets as necessary.
· DO NOT INSTALL DAMAGED PRODUCT! This luminaire has been properly packed so that no parts should have been damaged during transit. Inspect to confi rm. Any part damaged or broken during or after assembly should be replaced.
· Recycle: For information on how to recycle LED electronic products, please visit www.epa.gov.
·
These instructions do not purport to cover all details or variations in equipment nor to provide every possible
contingency to meet in connection with installation, operation, or maintenance. Should further information be desired or should particular problems arise which are not covered suffi ciently for the purchaser’s or owner’s purposes, this matter should be referred to Acuity Brands Lighting, Inc.
WARNING
RISK OF ELECTRIC SHOCK
Disconnect or turn off power before installation or
servicing.
Verify that supply voltage is correct by comparing it with
the luminaire label information.
Make all electrical and grounded connections in
accordance with the National Electrical Code (NEC) and any applicable local code requirements.
All wiring connections should be capped with UL approved
recognized wire connectors.
CAUTION
RISK OF INJURY
Wear gloves and safety glasses at all times when removing
luminaire from carton, installing, servicing or performing maintenance.
Avoid direct eye exposure to the light source while it is on.
WARNING
RISK OF BURN
Allow lamp/fi xture to cool before handling. Do not touch
enclosure or light source.
Do not exceed maximum wattage marked on luminaire
label.
Follow all manufacturer’s warnings, recommendations
and restrictions for: driver type, burning position, mounting locations/methods, replacement and recycling.
CAUTION
RISK OF FIRE
Keep combustible and other materials that can burn,
away from lamp/lens.
Do not operate in close proximity to persons, combustible
materials or substances affected by heat or drying.
Page 2
CAUTION: RISK OF PRODUCT DAMAGE
Never connect components under load. Do not mount or support these xtures in a manner that can cut the outer jacket or damage wire insula on. Unless individual product speci ca ons deem otherwise: Never connect an LED product directly to a dimmer packs,
occupancy sensors,  ming devices, or other related control devices. LED fi xtures must be powered directly off a switched circuit.
Unless individual product specifi ca ons deem otherwise: Do not restrict fi xture ven la on. Allow for some volume of
airspace around fi xture. Avoid covering LED fi xtures with insula on, foam, or other material that will prevent convec on or conduc on cooling.
Unless individual product speci ca ons deem otherwise: Do not exceed xtures maximum ambient temperature. Only use xture in its intended loca on. LED products are Polarity Sensi ve. Ensure proper Polarity before installa on. Electrosta c Discharge (ESD): ESD can damage LED xtures. Personal grounding equipment must be worn during all
installa on or servicing of the unit.
Do not touch individual electrical components as this can cause ESD, shorten lamp life, or alter performance. Some components inside the xture may not be serviceable. In the unlikely event your unit may require service, stop
using the unit immediately and contact an ABL representa ve for assistance.
Always read the fi xtures complete installa on instruc ons prior to installa on for any addi onal fi xture specifi c warnings.
Please see product specifi c installation instructions for additional warnings or any applicable FCC or other regulatory statements.
Failure to follow any of these instructions could void product warranties. For a complete listing of product Terms and Conditions, please visit www.acuitybrands.com.
Our Brands Indoor/Outdoor Indoor Lighting Outdoor Lighting Controls Daylighting
Lithonia Lighting Gotham American Electric Lighting DARK TO LIGHT SunOptics
Carandini Mark Architectural Lighting Antique Street Lamps LC&D Holophane Peerless Hydrel ROAM
RELOC Renaissance Ligh ng Tersen Sensor Switch Light Concepts Winona Lighting Synergy
Acuity Brands Lighting, Inc. assumes no responsibility for claims arising out of improper or careless installation or handling of its products.
ABL LED General Warnings, Form No. 503.203
© 2010 Acuity Brands Lighting, Inc. All rights reserved. 12/01/10
Page 3
Installation Instructions DSX0 LED
5 year limited warranty DELIVERY: Upon receipt of fi xture and accessories (packed separately), thoroughly inspect for any freight damage. All damage should be reported to the delivery carrier. Compare the catalog description listed on the packing slip with the fi xture label on the inside of the housing to be sure you have received the correct merchandise.
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Tools Required: 9/16" socket wrench. 3/16" allen wrench.
Figure 1
Mounting block has has this reinforced cast step and the word "UP" cast into it once.
This mounting block ships in the fi xture carton.
UP
1. Attach mounting block to the pole by placing the fl at bar stock with the 3 holes, two of which are threaded, inside the pole, aligning with the drill pattern (shown on next page). Place the cast aluminum block on the outside of the pole, with the word “Up” towards the top of the pole and facing outward or away from the pole. Thread the (2) 3/8" diameter hex head bolts through the block and pole into the threaded bar stock. (There is no gasket needed). Check plumb and level of the block and secure bolts tightly with 9/16" wrench or socket. (See Figure 1)
2. Insert the wires from the fi xture through the center hole of the mounting block assembly, pulling them into the pole. Place the luminaire over the mounting block while tilted up at a slight angle above horizontal, and then tip back down to horizontal once oriented on the block making certain the wires are not pinched. For ease of installation, the mounting block will hold the weight of the luminaire prior to tightening the mounting bolt. (See Figure 2)
3. To secure the fi xture, open doorframe by loosening the (2) captive screws using 3/16" allen wrench. (See Figure 3)
4. Tighten the locking hex head bolt inside the arm with a 9/16" socket to 20-30 ft. lbs. torque (overtightening will cause stripping and void all warranties). (See Figure 4)
5. Check the mounted assembly to assure proper placement and secured mounting has been achieved such that the fi xture is fully seated on the cleat and arm is fl ush with pole.
6. Close the doorframe and tighten the (2) captive doorframe screws.
7. Make wire connections, observing proper voltage and polarity. Connect green ground wire from the fi xture to the fi eld ground wire. Reference wiring diagram on driver. Secure wires; push back into pole.
Figure 2
Figure 3
Figure 4
Troubleshooting: If this fi xture fails to operate properly, check to make sure: • The fi xture is wired correctly. • The fi xture is grounded correctly. • The line voltage at the fi xture is correct. If all these variables have been checked and the fi xture still does not operate as specifi ed, contact your local Lithonia Lighting distributor.
Lithonia Lighting Outdoor • One Lithonia Way • Conyers, Georgia 30012
Phone: 800-279-8041 • Fax: 770.918.1209 •
© 2011 Acuity Brands Lighting, Inc. All rights reserved.
www.lithonia.com
Part Number: RJ521357 Rev A
Revision Date: 3-5-13
Page 4
Installation Instructions DSX0 LED
DSX0 LED 1 HS (1 panel) or DSX0 LED 2 HS (2 panels shown)
1) Remove the screws shown in picture from the light engine and discard.
2) Place a House-side shield on the light engine and align the holes on the shield with the holes on the light engine.
3) Assemble the shield to the light engine using the supplied screws.
4) Repeat steps 1-3 as needed.
Accessory: DSX0HS U (one per light engine)
DSX0 DROP LENS
1) Place drop lens over the light engines and align the holes on the lens with the holes on the housing.
2) Fasten using the supplied screws.
DSX WBA (Wall bracket)
1. CAUTION: APPLY A CONTINUOUS BEAD OF WEATHER - PROOF CAULKING BETWEEN MOUNTING PLATE AND WALL TO EN­SURE WEATHER - TIGHT INTEGRITY OF ELECTRICAL COMPONENTS (see diagram below).
2. Secure base plate to wall with (4) 1/4" fastener (by others) using the (4) holes located on the outer corners of the base plate. Check the base plate to confi rm that it is level and plumb in all directions (see diagram below).
3. Prepare the cover plate by attaching the fi xture's mounting block to the cover plate using (2) 3/8" diameter by 1-1/4" bolts with lockwashers by inserting the bolts and washers into the mounting block through the cover plate and thread into the threaded steel bar stock. Use a 9/16" socket or wrench and tighten securely (see diagram below).
4. Place the curved portion of the cover plate upwards. Ensure the factory installed gasket is in place on the backside of the cover plate. Place large eyelet of safety cable over the lower bolt. Secure with provided nut (see diagram below).
Step 2
(4) 1/4" fasteners
(by others)
Safety chain
Step 11
3/8" screw
Cover
plate
Step 5
Hex head
screws
Cover plate
Step 1
Silicone sealant
(by others)
To wall
Base plate
Attach to lower
bolt with nut
Step 4
Gasket
(factory installed)
Fixture's mounting block (See fi gure 1)
Step 3
Threaded
Steel Bar
5. Insert and tighten (4) 3/8" diameter by 1-1/4" stainless steel hex head screws into the threaded opening of the cover plate by turning approximately 6-7 full turns (see diagram above).
6. To prepare fi xture for installation, open doorframe by loosening the (2) captive screws using 3/16" allen wrench. (See Figure 3)
7. Pull the wires from the fi xture through the mounting block on the cover plate. Place fi xture onto the mounting block, being sure the wires are not being pinched.
8. Tighten the locking hex head bolt inside the arm with a 9/16" socket to 20-30 ft. lbs. torque (overtightening will cause stripping and void all warranties). (See Figure 4)
9. Close the doorframe and tighten the (2) captive doorframe screws.
10. Make wire connections, observing proper voltage and polarity. Connect green ground wire from the fi xture to the fi eld ground wire. Reference wiring diagram on driver.
11. Attach small eyelet of safety cable to base plate with provided 1/4-20 screw (see diagram above).
12. Slide the entire fi xture assembly over the base plate, tighten the top (2) 3/8" x 1-1/4" stainless steel hex head screws until 3/8" to 1/4" of the screw is still visible. Tighten the two bottom hex head screws until 3/8" to 1/4" of the screw is still visible. Alternating between the top two and bottom two sets of screws, gently tighten until snug, (approx one thread showing on each screw).
Lithonia Lighting Outdoor • One Lithonia Way • Conyers, Georgia 30012
Phone: 800-279-8041 • Fax: 770.918.1209 •
© 2011 Acuity Brands Lighting, Inc. All rights reserved. Mar/13
www.lithonia.com
Part Number: RJ521357 Rev A
Revision Date: 3-5-13