Liteplan CE1R/2W/M3, CE1R/2W/ST, CE1R/3W/DALI, CE1S/2W/M3, CE1S/2W/ST Assembly Instructions Manual

...
CE1R/2W/M3/** CE1R/2W/ST/** CE1R/3W/DALI/**
CE1R fitting
Technical Specification:
- Supply Voltage: 220-240V AC 50/60Hz
- Ingress Protection: IP41
- Emergency Duration: 3 hours
- Light Source: for M3 and ST version 2W LED
- Battery 6.4V 1.6Ah LiFEPO4 for M3 & ST Battery 9.6V 1.5Ah LiFEPO4 for DALI
- Battery Recharge Time: 12h
- Max Battery Temperature: 55°C
- Ambient Temperature: 0 - 40°C
- Viewing Distance: 25m
- Charge indicator: Green / Red LED
- Deep Discharge Protection DDP
- Self-Test & DALI versions available
- Surface assembly (ceiling)
- Assembly indoors to flat surface
- Polycarbonate body, Plexi Glass
- Maintained or Non-Maintained Operation
for DALI version 3W
Important:
It is recommended that the unit is installed by a competent person ensuring the installation complies with the necessary standards. The company accept no responsibility for incorrect installation, operation or maintenance. The unit requires an unswitched supply for charging the battery and a switched supply for a maintained unit. After installation of the fitting, the battery must be charged for 24 hours.
LED indication Chart
Testing / Commissioning:
Ensure the load is connected Enter the commissioning date on battery pack and connect the battery Switch on the unswitched supply – Check that the green charge LED illuminates Switch on the maintained supply – Check that the fitting illuminates as normal Switch off the maintained supply Switch off the unswitched supply – Check that the green charge led extinguishes and the fitting illuminates Enter the commissioning date on battery pack Switch on the unswitched supply
It is recommended that the batteries are renewed every 6 years. The fitting is equipped with non-replaceable LED.
Self-Test Function:
A Function Test automatically runs every 28 days. During this test the fitting is switched into emergency mode for 1 minute. During the test the battery discharge current is checked. A Full Duration Test automatically runs every 364 days. During this test the fitting is switched into emergency mode for 3 hours . During the test the battery discharge current and battery voltage is checked
Disassembling the CE1R fitting
IP41
Mounting detailsConnections for DALI version
150mm
min
I
II
Hole dimensions
300
45
Connections for Maintained, Self-Test and Non-Maintained versions
Assembly instruction
Dimensions
327mm
299 mm
Additional guidelines
Guidelines for installation
Ensure a permanent supply to connection L Ensure a switched supply connection L1 For Non-Maintained use only L, do not connect to L1 Ensure correct polarity of the battery The drawing in the fitting may vary to the actual product, connect as per label on fitting. When fitting a flush fitting, refer to installation instruction, including any ceiling manufacturer's instructions.
202 mm
130mm
206 mm
Ø43
20 mm
43mm
Ø19
230mm
206mm
130mm
Ø12