LINEAR TECHNOLOGY LT6108-2 Technical data

Simple Energy-Tripped Circuit Breaker with Automatic Delayed Retry
Design Note 495
Tim Regan
Introduction
One way to minimize nuisance breaks is to employ a slow-blow technique, which allows relatively high levels of current for short intervals of time without tripping the breaker. Ideally, the breaker’s trip threshold would be a function of total transient energy, instead of just current. This article describes an electronic circuit breaker, com­bining current sensing with timing to create an energy­tripped breaker, which protects sensitive circuits while minimizing nuisance trips.
LOAD SUPPLY 5V TO 80V DC
R
SENSE
10mΩ
CIRCUIT BREAKER
Q1
NPN
LOAD
0.667V/A
R1
100Ω
LT6108-2
CURRENT SENSE AMP
– +
COMPARATOR
5V
L
RELAY
R14 15k
400mV
CLOSED
5
0
– +
OPEN
R4
40.2k
R2
1.62k
R3
6.34k
CURRENT SENSE COMPARATOR 500mA TRIP THRESHOLD
Higher Currents Permitted for Shorter Time Intervals
The circuit of Figure 1 has three distinct parts – circuit breaking, current sensing and timing.
The circuit breaking function can be any t ype of electroni­cally controlled relay or solid state switch, properly sized for voltage and current rat ings of the load being protecte d.
Load current sensin g is achieved via an LT®6108-2 current sense amplifier with built-in comparator. The LT6108-2 converts the voltage drop across a small valued sense resistor to a ground-referenced output voltage that is directly pr oportional to the load curr ent. The trip threshold is created by s caling the output voltage via resis tor divider and feeding the result to the integrated comparator with a precision 400mV voltage reference. The comparator changes st ate when the load current exce eds the threshold.
To prevent short duration transients from causing nui-
®
sance trips, an LTC
L, LT, LTC, LTM, Linear Technology, the Linear logo and Timerblox are registered trademarks of Linear Technology Corporation. All other trademarks are the property of their respective owners.
R3
3.66k
5V
LT1783
+
5V
R10 10k
6994-2 Timerblox® delay timer is
60ms TO 350ms
DELAY TIMER
R6
64.9k
R7 301k
IN
GND
SET
LTC6994-2
R
OPTIONAL
931k
OUT
DIV
+
V
R8 172k
R9 100k
5V
DN495 F01
10/11/495
Figure 1. Energy-Tripped Circuit Breaker Trips After a Time Interval That Varies as a Function of Sensed Load Current
added between the comparator output and the circuit breaker. Once tripped, the comp arator falling edge star ts a variable time delay interval, which, if allowed to complete, signals the circuit breaker to open. Nothing happens if the transient duration is shorter than the delay.
A Current-Controlled Delay Interval
The LTC6994-2 delays from an edge appearing at its IN pin by a time ranging from 1µs to 33 sec. The delay time is controlled by the current sourced by the SET pin, which programs an internal oscillator frequency, while the bias voltage on the DIV pin selects a frequency divide ratio.
The LT1783 op amp circuit takes the output voltage from the current sense amplifier and adjusts the SET pin current, thereby making the delay time a function of the load current (see Figure 2). As shown, the current sense comparator trip threshold is 500mA. A current of 500mA creates a falling edge and starts a time delay of 350ms. Should the load current drop below 500mA before the delay time expires, the timer output remains high and the circuit breaker does not trip.
Higher load currents correspond to higher current sense amplifier output voltages, which in turn reduce the delay time interval (Figure 2). For instance, a 5A load current trips the circuit breaker in only 60ms. Depending on the average load current in excess of the 500mA threshold, the delay inter val or trip time will fall somewhere between 30ms and 400ms.
output voltage stretches this delay to a maximum time of ~1.3 sec. After this delay the circuit breaker closes and reapplies power to the load. This automatic retry function requires no additional components.
The response of the circuit to a 5A load current spike and automatic retry is shown in Figure 3. If the load current remains too high, the trip/r etry cycle repea ts continually. A current surge is fairly common when the circuit breaker is first closed and can trip the comparator. If the duration is less than the timer delay, the breaker remains closed, thus avoiding an endless loop of self-induced nuisance trips.
A B
1V 5V
5V
Figure 3. An Example Trip and Retry Sequence. At Time Point A, the 5A Load Current Spike Trips the Comparator and 60ms Later the Breaker is Opened. At Time B, After a Delay Time of 1.3 sec, the Timer Closes the Breaker. The Resulting Short Duration Spike of Start-Up Current Is Not Large Enough or Long Enough in Duration to Trip the Breaker Again
CURRENT SENSE OUTPUT
CURRENT COMPARATOR OUTPUT
DELAY TIMER OUTPUT
200ms/DIV
DN495 F03
Once tripped, the load current drops to zero. This resets the current sens e comparator high. This rising edg e is also delayed by the LTC6994-2. The minimum current sense
400
350
300
250
200
150
100
BREAKER DELAY TIME (ms)
50
0
0
31 98
LOAD CURRENT (A)
Figure 2. Low Current Transients Must Last Relatively Longer to Trip the Breaker. Higher Currents Trip the Circuit Breaker in Less Time
Data Sheet Download
www.linear.com
11102 4 5 6 7
DN495 F02
Extending the Retry Time Interval
The LTC6994-2 delay timer has eight divider settings for a wide range of timing intervals. Adding the single optional resistor shown in Figure 1 shifts the delay block to a new setting, increasing the retry time interval if desired. This can give any fault condition more time to subside. The circuit breaker response time interval is not affected.
For the values shown, when the circuit breaker trips and the current drops to zero, the c omparator high level biases the DIV pin to a higher voltage level, resulting in a longer retry delay time of 10 seconds.
Conclusion
The circuit shown here can be easily modified to different timing requirements with a few resistor value changes. Other current sense devices such as the LT1999 can also be used to monitor bidirectional load currents with variable breaker timing functionality.
For applications help,
call (408) 432-1900, Ext. 3409
Linear Technology Corporation
1630 McCarthy Blvd., Milpitas, CA 95035-7417
(408) 432-1900
FAX: (408) 434-0507 ● www.linear.com
dn495f LT/AP 1011 196K • PRINTED IN THE USA
LINEAR TECHNOLOGY CORPORATION 2011
Loading...