Lindy 32437 User Manual

Page 1
Radio Frequency Energy, Certifications
©LINDY-ELEKTRONIK GMBH - SECOND EDITION (JAN 2006)
For Home and Office Use Tested to Comply with FCC Standards
This equipment has been tested and found to comply with the limits for a Class B Digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is
connected
Consult the dealer or an experienced technician for help You are cautioned that changes or modifications not expressly approved by the party responsible for
compliance could void your authority to operate the equipment.
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions:
1. This device may not cause harmful interference, and
2. This device must accept any interference received, including interference that may cause undesired operation
©LINDY-ELEKTRONIK GMBH - SECOND EDITION (JAN 2006)
For Home and Office Use
Tested to Comply with
FCC Standards
Water Sensor /
Wassermelder
User Manual English Benutzerhandbuch Deutsch
LINDY No. 32437
www.LINDY.com
Page 2
ENGLISH USER MANUAL
Installation and Use – Please store this document securely!
Please read this manual completely – it contains useful and important information on the function and installation of this device. Reliable operation can only be guaranteed if the instructions are followed correctly.
Contents
1x water sensor 1x this manual
Technical Data
Operating voltage: 12 V DC Typical current: 1 mA at U=12 V DC Sensor voltage max. 12 V / 6 kHz Sensor current: max. 0,2 mA Operating temperature: -20°C … + 60°C Sensor activation: fix, min. 1mm of water Over flooding 100% guaranteed Sensor is 100% water proof Sensors: 4 pieces of V4A-steel Cable: approx. 5m, flex 3x 0.34 mm² Weight approx. 150g Dimensions approx. 9x6x3cm
Introduction
This water sensor has been specially designed for use in monitoring and alarm systems. The unit must be powered using a 12V DC power supply. It is 100% waterproof. It reacts on any electrically conducting liquid such as water, alcohol, refreshments, acids and various chemicals. It gives an output when it comes into contact with a conducting liquid.
• Ideal for detecting leakage from burst pipes etc. and condensation build-up in floor elevated rooms, water cooled
server and network racks and other IT equipment.
• Ideal for tunnel and channel leakage detection
• Ideal for use in sumps and drain areas in case of overflows or pump failures
Function
The entire sensor is enclosed in a sealed water proof housing. The four V4A Steel sensors located on the bottom side of the unit detect any conducting liquid present. The unit uses an alternating current to detect the liquid. This prevents the sensors from corrosion due to electrolysis. The sensor is set to digital LOW in when active.
Connection
WHITE
The unit should be wired to a digital in input of the RMS according to the circuit diagram:
RED or BROWN
RED or BROWN + 12 V BLUE or GREEN GND
BLUE or GREEN
WHITE IN+ (Sensor)
Troubleshooting
If the unit has been wired incorrectly an “Overload warning” is given by the RMS. Check and correct the connections and acknowledge the overload warning of the RMS.
Sensors
Spacers
Side View
DEUTSCHES HANDBUCH
Bedienungs- und Montageanleitung - Bitte sorgfältig aufbewahren!
Bitte lesen Sie die Anleitung vollständig durch – sie enthält wichtige Informationen über Funktion, Montage, Platzierung und Pflege des Produktes. Eine zuverlässige Frühwarnung bei Wassereinbruch ist nur gegeben, wenn dieser Wassermelder unter Berücksichtigung der Anweisungen verwendet wird.
Lieferumfang
1x Wassermelder 1x Bedienungsanleitung
Abstandhalter (Füße) Sensoren Seitenansicht
Technische Daten
Betriebsspannung: 12 V DC Ruhestrom: 1 mA bei U=12 V Sensorspannung; max. 12 V / 6 kHz Sensorstrom: max. 0,2 mA Temperaturbereich: -20°C bis + 60°C Abtastniveau: fix, min. 1mm Überflutbarkeit: 100% garantiert Detektor wasserdicht vergossen Sensoren: 4 Stück aus V4A-Stahl Kabel: 5 m, TT-flex 3x 0.34 mm² Gewicht: ca. 150 g Maße: 9x6x3cm
Anwendung
Der Wasser-Detektor wurde speziell für den Anschluss an Alarm- und Meldeanlagen entwickelt. Er arbeitet mit 12 V Gleichspannung. Er ist absolut wasserdicht und spricht auf alle elektrisch leitenden Flüssigkeiten an, z. B. Wasser, Alkohol, Getränke, Säure, div. Chemikalien. Er löst Alarm aus, wenn die Sensoren mit leitender Flüssigkeit in Kontakt kommen.
• Zur Überwachung von Doppelböden von EDV Anlagen und klimatisierten Räumen gegen Wasserrohrbruch
• Kanal- und Tunnelüberwachung gegen Überflutung
• Pumpen und Schachtüberwachung gegen Kanalisationsrückstau oder Pumpenausfall
Funktion
Der Sensor ist in einem wasserdichten Gehäuse untergebracht. Die 4 Sensoren auf der Unterseite des Sensors erfassen jede leitende Flüssigkeit. Ein integrierter Wechselspannungsgenerator erzeugt für den Sondenkreis die notwendige Wechselspannung. Diese Wechselspannung sorgt vor, dass die Stahlsensoren beim Eintauchen in eine Flüssigkeit durch Elektrolyse nicht zerstört werden. Der Sensorausgang schaltet im aktiven Zustand auf digital ''Low“.
Anschluss
Anschluss an einen „Digital In“-Eingang des WEISS RMS entsprechend der Tabelle vornehmen: ROT oder Braun + 12 V ROT oder Braun BLAU oder Grün GND WEISS IN+ BLAU oder Grün
Fehlersuche
Sollte nach Anschluss des Sensors die „Overload Error“ Meldung im Display des RMS erscheinen, liegt höchstwahrscheinlich ein Anschlussfehler am RMS vor. Überprüfen Sie die Anschlüsse und quittieren Sie die Overload-Meldung am RMS.