U.S. Fax: (888) 790-8193 • Int’l Fax: (260) 436-0735
Technical Service Hot Line
(800) 678-9511
www.lincolnfp.com
1600advsvc REV: 1/8/07
TABLE OF CONTENTS
TABLE OF CONTENTS..............................................................................................................................................2
SEQUENCE OF OPERATIONS / 1600-000-A , 1601-000-A.....................................................................................3
PARTS / GENERAL - 1600-000-A ADVANTAGE SERIES......................................................................................18
BLOW UP / GENERAL – 1600-000-A ADVANTAGE SERIES ................................................................................19
PARTS / CONTROL BOX, RIGHT - 1600-000-A, 1601-000-A ................................................................................20
BLOW UP / CONTROL BOX, RIGHT - 1600-000-A, 1601-000-A ...........................................................................21
PARTS / CONTROL BOX, LEFT - 1600-000-A, 1601-000-A...................................................................................22
BLOW UP / CONTROL BOX, LEFT - 1600-000-A, 1601-000-A..............................................................................23
PARTS / OVEN BACK - 1600-000-A - SERIES .......................................................................................................24
BLOW UP / OVEN BACK - 1600-000-A - SERIES ..................................................................................................25
PARTS / CONVEYOR - 1600-000-A - SERIES .......................................................................................................26
BLOW UP / CONVEYOR - 1600-000-A - SERIES...................................................................................................27
2
Low Profile – 1600-000-A Advantage Series Service Manual – Domestic
SEQUENCE OF OPERATIONS / 1600-000-A, 1601-000-A
MODEL 1600-000-A / 120 VAC / 60 HZ / NATURAL GAS
MODEL 1601-000-A / 120 VAC / 60 HZ / L.P. GAS
POWER SUPPLY Electrical power to be supplied to the oven by a three conductor cordset. Voltage from
the black conductor to the white conductor to be 120 VAC.
White conductor is Neutral.
Green conductor is Ground.
CONTROL BOX
AUTO COOL DOWN
MAIN FAN CIRCUIT 120 VAC is permanently supplied to the normally open double pole power switch, a
BURNER CIRCUIT Closing the Oven Power Relay supplies 120 VAC to the (2) burner Systems
TEMPERATURE
CONTROL
CONVEYOR DRIVE Closing the on/off switch supplies 120 VAC through the oven power relay to the motor
NOTE: The conveyor control uses a sensor and magnet, mounted on the conveyor motor that
TEMPERATURE
DISPLAY
When the temperature in either one of the Control Boxes reaches 120°F ± 3°F (49°C
± 1.7°C), the Cooling Fan Thermostats will switch power to the Cooling Fans. The
thermostats will interrupt power to the Cooling Fans when the temperature falls to
100°F ± 3°F (37°C ± 1.7°C).
normally open contact of the oven power relay and the normally open cooling fan
thermostats. Closing the power switch supplies 120 VAC, through the 3 A cooling fan
fuse, through both control box hi-limit thermostats to the coil of the oven power relay.
These normally open contacts now close supplying 120 VAC, through the 10A main
fan fuse to the 2 main fan motors and the 2 burner motors. Power is also supplied to
the cooling fans, the heat and conveyor control systems.
NOTE: This oven utilizes (2) complete Burner/Temp. Control systems. The sequence
of operations is the same for each system.120 VAC is supplied, through the
Centrifugal Switch of the Main Fan Motor (this switch closes when the Main Fan
reaches approximately 1600 R.P.M.) through the 10 Amp Fuse, to the Ignition
Control, the Electronic Temperature Control, and the burner transformer. As the
Burner Blower reaches approximately 1600 R.P.M., its internal centrifugal switch will
close, supplying 24 VAC to the ignition control. The Ignition Control operates on both
24 VAC and 120 VAC. When the control is energized by 24 VAC, 120 VAC is
switched to the Hot Surface Igniter for 45 seconds for Hot Surface Igniter warm up.
The igniter glows red, 24 VAC is switched to the gas valve which opens, and ignition
should now occur. If ignition does not occur in 6 seconds, the control will lock out. To
recycle after lockout, turn off the burner switch for 45 seconds and then turn the
switch back on.
When the Centrifugal Switch of the Main Fan Motor closes, power is applied to the
Temperature Control. The1K ohm Temperature Pot is adjusted to desired
temperature. Thermocouple will provide varying millivolts to the Temperature
Controller. The Temperature Controller supplies 120 VAC to the solenoid valve at
intermittent intervals to maintain desired temperature. The heat lamp is energized
with the solenoid valve.
control board. AC volts are converted to DC volts and are supplied to the conveyor
motor at terminals A+ and A-.Adjustments of the speed control potentiometer will
change resistance at terminals P1 and P2 varying the DC voltage to the motor. The
speed of the conveyor motor will increase or decrease as the DC voltage from the
board increases or decreases respectively.
senses the motor speed. Any change in motor load, (±RPM) is detected by the
sensor and the voltage to the motor is adjusted accordingly.
Closing the switch supplies 120 VAC to the primary of the temperature display
transformer. The secondary of this transformer supplies 12 VAC to the temperature
display. The thermocouple supplies D.C. millivolts to the temperature display. The
display converts this millivolt reading to a temperature reading.
Low Profile – 1600-000-A Advantage Series Service Manual – Domestic
3
TROUBLESHOOTING GUIDE
GAS OVENS
MODEL 1600-000-A / NATURAL GAS / 120 VAC / 60 HZ / 1 PHASE
MODEL 1601-000-A / L.P. GAS / 120 VAC / 60 HZ / 1 PHASE
NOTE: When checking components on left side of unit, be sure to check for proper connections in power
connector, (marked P. C. on Schematic Diagram.) located inside motor cover.
SYMPTOM POSSIBLE CAUSE EVALUATION
Oven fan will not run
No control box cooling
No automatic control
box cooling
Incoming Power
Supply
Main Fan Switch Check continuity between switch terminals.
Fuse, 10 Amp Check, replace if necessary.
Fuse Holder Check, replace if necessary.
Fuse 3A Check, replace if necessary.
Fuse holder Check, replace if necessary.
Hi Limit Thermostat(s)
Control Box
Oven Power Relay Check for 120 VAC to the relay coil. If voltage is not present,
Main Fan Motor Check for opens, shorts, or grounds. WITH POWER OFF turn
Capacitor Check for shorts or grounds.
Incoming Power Check main circuit breakers, reset if required, call power
Main Fan Switch Check continuity between switch terminals
Fuse 3 amp. Check, replace if necessary.
Fuse Holder Check, replace if necessary.
Hi Limit Thermostat(s)
Control Box
Cooling Fan(s) 120 VAC should now be at the fan motor. If voltage is present,
Incoming Power
Supply
Cooling Fan
Thermostat(s)
Fuse, 3 amp Check, replace if necessary
Fuse Holder Check, replace if necessary
Hi Limit Thermostat(s)
Control Box
Check breakers, reset if required. Check power plug to be sure
it is firmly in receptacle. Measure the incoming power/call
power company if needed.
Check for voltage on both sides of the switch. Terminals are
normally closed. If open, reset and test oven for proper
operation. If thermostat will not hold and control box
temperature is not exceeding 140°F (60°C), replace
thermostat.
trace wiring back to the control box hi-limit. If voltage is
present, check to insure contacts are closing. Check for 120
VAC supplied to terminal #2 of the relay.
fan blade to check for locked rotor.
WARNING: Capacitor has a stored charge, discharge before
testing.
company if needed.
Check for voltage on both sides of the switch. Terminals are
normally closed. If open, reset and test oven for proper
operation. If thermostat will not hold and control box
temperature is not exceeding 140°F (60°C), replace
thermostat.
check motors for shorts or opens. WITH POWER OFF:
Check for locked rotor.
Check circuit breakers, reset if required. Call the power
company if needed.
Check the cooling fan thermostat. (Thermostat closes at
120°F and opens at 100°F). With the cooling fan thermostat
preheated, check for continuity. If switch is open, replace.
Check for voltage on both sides of the switch. Terminals are
normally closed. If open, reset and test oven for proper
operation. If thermostat will not hold and control box
temperature is not exceeding 140°F (60°C), replace
thermostat.
4
Low Profile – 1600-000-A Advantage Series Service Manual – Domestic
Cooling Fan(s) 120 VAC should be at the motor. If voltage is present, check
motor for shorts, opens, or grounds. WITH POWER OFF:
check for locked rotor.
Oven will not heat
Gas Supply Check for adequate gas supply and closed manual gas valves.
Also, check flexible gas line connection.
Main Fan If not operating, refer to "Oven fan will not run".
NOTE: These ovens utilize 2 complete burner/temperature control systems. Each system will follow the same
troubleshooting sequence.
Centrifugal Switch of
Main Fan Motor
Check for 120 VAC supplied to the centrifugal switch, if
voltage is not present, trace the wiring back to the oven power
relay. Check for 120 VAC out of the centrifugal switch. If
voltage is supplied to the centrifugal switch, and motor is
running, but there is no voltage out of the centrifugal switch,
replace the fan motor.
(NOTE: See Schematic Diagram of proper wire numbers on
motors.)
Fuse, Burner 10A Check, replace if necessary.
Fuse holder Check, replace if necessary
Burner Blower Motor Check for 120 VAC supply to the burner blower motor, if 120
VAC is present and motor does not turn, replace the motor.
Burner Transformer Check for 120 VAC to primary of the 24 VAC burner
transformer. If voltage is not present, trace wiring back to the
fuse. If voltage is present, check for 24 VAC at the secondary,
if no secondary voltage is present, replace the transformer.
Centrifugal Switch of
Burner Blower Motor
Check for 24 VAC supply to the centrifugal switch of burner
blower motor (see Schematic for proper wire numbers). If no
voltage is present, trace wiring back to the transformer. If
voltage is present, check for 24 VAC at the output of the
centrifugal switch. If there is no output, and the burner blower
motor is running, replace the burner blower motor.
Ignition Control Check for 24 VAC supply to the ignition control at terminals
marked 24V and 24Vgnd. If voltage is not present, trace
wiring back to the centrifugal switch. Check for 120VAC
supply to the ignition control at terminals L1 and L2. If no
voltage is present, trace wiring back to fuse. If the above
checks are okay, proceed. The ignition control should switch
120VAC to the hot surface igniter, across the (2) terminals
marked HIS. If no voltage is present, replace the ignition
control.
Hot Surface Igniter
(Located inside Burner
Assy)
If 120 VAC is present at HSI terminals, visually check to see
that the hot surface igniter is heating (igniter may be viewed
through port glass in end of burner tube). The igniter should
glow bright red. Check all connections to be sure they are
tight. If the igniter does not heat, replace.
Ignition Control After 45 seconds of hot surface igniter pre-heat, the ignition
control will switch 24 VAC to the gas control valves. Check for
24 VAC output from the ignition control, and across terminals
marked "valve" and "valve gnd". If no voltage is present,
replace the ignition control.
NOTE: The ignition control contains a safety lockout circuit. If
a flame is not detected within 6 seconds after the gas control
valve is energized, the ignition control will lockout. To reset,
turn the power switch "off", wait 45 seconds and switch the
system "on" to retry ignition.
Gas Control Valves Check for 24 VAC supplied to the gas control valves. If
voltage is present, the valves should open. Check for gas
pressure at the pressure tap, located in the gas piping just
prior to the burner. If there is no gas pressure, and the voltage
is supplied to valves, check piping for obstructions. If there
Low Profile – 1600-000-A Advantage Series Service Manual – Domestic
5
Flame will not stay lit
Low flame is on, but
no main flame
are no obstructions, replace gas control valves.
Hot Surface Igniter The ignition control will keep the gas control valves energized
for 6 seconds. At the end of 6 seconds, the hot surface igniter
must sense a flame, or, the ignition control will go into lockout.
(The ignition control requires a minimum of 0.8 microamps
D.C.) To check the flame sensing operation, connect a digital
multimeter (capable of measuring D.C. micro-amps) between
the "ground" terminal on ignition control and the ground lead.
NOTE: This is a current measurement and the meter must be
connected in series. If these readings are not achieved, check
bypass orifice for obstructions, if bypass orifice is clear,
replace the hot surface igniter.
NOTE: The D.C. micro amp test must be conducted with the
oven in low flame (bypass) operation. Turn the temperature
control to its lowest setting.
Power Supply If there is sufficient micro-amp current, but the flame will not
stay lit, check for proper polarity of the 120 VAC power supply
Ignition Control If there is sufficient micro-amp current, and the 120 VAC
polarity is correct, but the flame will not stay lit, replace the
ignition control.
NOTE: Check for proper ground connection of the ignition
control.
NOTE: Flame should
be lit at this time.
Temperature Control Check for 120 VAC at terminal #7 to neutral on temperature
control. If no voltage, trace voltage back to fuse holder. Turn
the temperature adjustment knob to maximum temperature
position and check for 120 VAC at the load terminal #8 and
neutral. If 120 VAC is present and unit is not heating, refer to
"Temperature Solenoid Valve" for next check. If 120 VAC is
not present, proceed.
Thermocouple Probe WITH POWER ON AND THERMOCOUPLE LEADS
ATTACHED TO THE TEMPERATURE CONTROL BOARD:
Measure the D.C. millivolt output of these leads. Refer to
thermocouple chart on page 17 for proper readings. If these
readings are not achieved, replace the thermocouple.
Temperature Set
Potentiometer
Disconnect the potentiometer leads Disconnect the pot from
the board. Place ohm meter test leads on the blue and green
pot leads. Reading should be 1 K ohms. Place meter leads
across the blue and purple pot leads and rotate knob from high
to low. Repeat on green and purple leads. Check for even
rise and fall of ohms reading to insure that there are no open
or dead spots in the potentiometer. Check each lead to
ground for shorts. Replace pot if it does not meet the above
test
Temperature Solenoid
Valve
If 120 VAC is present on the temperature control board at load
terminal #8 to neutral, check for voltage at temperature
regulation valve. If voltage is present, listen for valve to open
and close. Also check for opens or shorts in the coil. Replace
as necessary.
6
Low Profile – 1600-000-A Advantage Series Service Manual – Domestic
Intermittent Heating Thermal/Overload of
Main Fan and Burner
Blower Motors
Conveyor will not run
Voltage Supply Check incoming voltage supply at line 1 to neutral. There
Fan Switch See procedure for checking at beginning of section.
10 Amp Fuse Check and/or replace.
Fuse holder Check and/or replace.
Speed Adjustment
Potentiometer
DC Motor Control
Board
Conveyor Gear Motor If DC voltage is present at A+ and A- and the motor does not
Conveyor Check for any mechanical misalignment. Also, check for worn
The main fan motors and the burner blower motors are
equipped with internal thermal protection and will cease to
operate if overheating occurs. As the motors overheat and
then cool, this will cause the units to cycle on and off
intermittently. Improper ventilation or preventive maintenance
may cause this. Also, most of the problems listed under
"Oven will not heat" can cause intermittent failure.
should be a voltage reading of 120 VAC. If not present, check
breakers.
This is a 0 to 10 K ohm, 1 turn potentiometer. With power off,
remove the black and white pot leads from the motor control
board at terminals P1, P2. Place the meter leads on the black
lead (P2) and on the white lead (P1). Rotating the pot., slowly,
from low to high, the meter readings should show an even
transition from 0 to 10 K ohms ± 5%. There should be no
dead or open spots through out the 1 turn of the pot. Check
both leads to ground. There should be no continuity to
ground. If any of the above checks fail, replace the pot
Check for 120 VAC input to the control board at terminals L1
and L2. If not present, check wiring back to the fuse. If 120
VAC is present at L1 and L2, check both fuses on control
board (8A line and 1A armature), check the VDC output at
terminals A+ and A-. If 120 VAC is present at terminals L1
and L2, and DC voltage is present A+ and A-, but motor does
not run, check gear motor as follows.
run, first check the mini breaker and then the conveyor. Refer
to the next possible cause. Check the leads to the motor for
evidence of any shorts or opens, and each lead to ground.
Check motor brushes. From the top of the motor, rotate motor
shaft to determine if there is a locked rotor or a locked gear
box (use care so magnet and H.S. board are not damaged).
Replace motor as needed.
bearings. A conveyor belt that is over tightened will cause
excessive bearing wear and sometimes, irregular speed.
Low Profile – 1600-000-A Advantage Series Service Manual – Domestic
7
Conveyor speed
varying or intermittent
Power Supply Check power supply at the DC control board for the 120 VAC
at board terminals L1 and L2.
Motor Control Board Place the test meter probes on terminals A+ and A-. (With
speed potentiometer set to maximum speed (Approximately 2
min.) The meter reading should be approximately 100 VDC
(±3%), if voltage is not steady within limits, then the board is
probably bad. Always check the speed pot., be sure it is okay
before changing a board. This test is not always 100%
accurate as this test is not performed at operating speeds.
However, this test is the best method currently available.
DC Gearmotor If the DC control board is steady then the problem may be the
motor or gearbox. Check the brushes in the motor for
excessive arching and/or unusual wear. Check the motor and
gearbox from instruction located under "possible cause" listing
"conveyor gear motor."
Magnet Check to insure that the magnet (cemented to shaft of
conveyor drive motor) has not been damaged, or come loose
from motor shaft. Replace as needed.
Hall Effect Sensor Check for any physical damage to hall effect sensor (mounted
on conveyor drive motor.) Check all wiring and connections
for damage. Check all connections for tightness or proper
location. Replace as needed. Connect new hall effect to
system and check for steady operation.
8
Low Profile – 1600-000-A Advantage Series Service Manual – Domestic
Temp. display
inoperative
Temp. Display
inaccurate, erratic or
inoperative
Display Transformer Measure the transformer primary for a nominal 120 VAC input,
if voltage is not present, trace wiring back to the oven power
source. Measure the secondary output, which will normally be
12-15 VAC. Voltage across terminals 1 and 3 on the temp.
display should read 12-15 VAC. Terminals 1-2 and 2-3 should
be 1/2 the voltage reading to 1-3. If the above secondary
readings are not achieved, replace transformer.
Temp. Display If proper voltage is present at terminals 1, 2, and 3 on
temperature display, but the display is not lighted, recheck all
connections for tightness. If temperature display is still not
operating, replace the temperature display.
Thermocouple Connect the thermocouple of a pyrometer to the thermocouple
on the temperature control board. (Be sure to maintain proper
polarity of thermocouple leads--see Adjustment Section for
proper procedure.) The pyrometer will indicate oven
temperature. Measure DC millivolts of thermocouple at the
temperature display. See thermocouple chart in adjustment
section for proper readings. Replace thermocouple if proper
readings are not achieved. If readings are correct on the
thermocouple, replace temperature display.
Low Profile – 1600-000-A Advantage Series Service Manual – Domestic
9
Loading...
+ 19 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.