Use “Ask the Experts” at lincolnelectric.com
A Lincoln Service Representative will contact you
no later than the following business day.
For Service outside the USA:
Email: globalservice@lincolnelectric.com
THANK YOU FOR SELECTING
A QUALITY PRODUCT BY
LINCOLN ELEC TRIC.
PLEASE EXAMINE CARTON AND EQUIPMENT FOR
DAMAGE IMMEDIATELY
When this equipment is shipped, title passes to the purchaser
upon receipt by the carrier. Consequently, claims for material
damaged in shipment must be made by the purchaser against the
transportation company at the time the shipment is received.
SAFETY DEPENDS ON YOU
Lincoln arc welding and cutting equipment is designed and built
with safety in mind. However, your overall safety can be increased
by proper installation ... and thoughtful operation on your part.
DO NOT INSTALL, OPERATE OR REPAIR THIS EQUIPMENT
WITHOUT READING THIS MANUAL AND THE SAFETY
PRECAUTIONS CONTAINED THROUGHOUT. And, most importantly,
think before you act and be careful.
WARNING
This statement appears where the information must be followed
exactly to avoid serious personal injury or loss of life.
CAUTION
This statement appears where the information must be followed
to avoid minor personal injury or damage to this equipment.
KEEP YOUR HEAD OUT OF THE FUMES.
DON’T get too close to the arc.
se corrective lenses if necessary
U
to stay a reasonable distance
away from the arc.
READ and obey the Safety Data
Sheet (SDS) and the warning label
that appears on all containers of
welding materials.
USE ENOUGH VENTILATION or
exhaust at the arc, or both, to
keep the fumes and gases from
your breathing zone and the general area.
IN A LARGE ROOM OR OUTDOORS, natural ventilation may be
adequate if you keep your head out of the fumes (See below).
USE NATURAL DRAFTS or fans to keep the fumes away
from your face.
If you de velop unusual symptoms, see your supervisor.
Perhaps the welding atmosphere and ventilation system
should be checked.
WEAR CORRECT EYE, EAR &
BODY PROTECTION
PROTECT your eyes and face with welding helmet
properly fitted and with proper grade of filter plate
(See ANSI Z49.1).
PROTECT your body from welding spatter and arc
flash with protective clothing including woolen
clothing, flame-proof apron and gloves, leather
leggings, and high boots.
PROTECT others from splatter, flash, and glare
with protective screens or barriers.
IN SOME AREAS, protection from noise may be appropriate.
BE SURE protective equipment is in good condition.
Also, wear safety glasses in work area
AT ALL TIMES.
SPECIAL SITUATIONS
DO NOT WELD OR CUT containers or materials which previously
had been in contact with hazardous substances unless they are
properly cleaned. This is extremely dangerous.
DO NOT WELD OR CUT painted or plated parts unless special
precautions with ventilation have been taken. They can release
highly toxic fumes or gases.
Additional precautionary measures
PROTECT compressed gas cylinders from excessive heat,
mechanical shocks, and arcs; fasten cylinders so they cannot fall.
BE SURE cylinders are never grounded or part of an
electrical circuit.
REMOVE all potential fire hazards from welding area.
ALWAYS HAVE FIRE FIGHTING EQUIPMENT READY FOR
IMMEDIATE USE AND KNOW HOW TO USE IT.
Safety 01 of 04 - 06/15/2016
SECTION A:
WARNINGS
CALIFORNIA PROPOSITION 65 WARNINGS
Diesel Engines
Diesel engine exhaust and some of its constituents are known
to the State of California to cause cancer, birth defects, and other
reproductive harm.
Gasoline Engines
The engine exhaust from this product contains chemicals known
to the State of California to cause cancer, birth defects, or other
reproductive harm.
ARC WELDING CAN BE HAZARDOUS. PROTECT
YOURSELF AND OTHERS FROM POSSIBLE SERIOUS
INJURY OR DEATH. KEEP CHILDREN AWAY.
PACEMAKER WEARERS SHOULD CONSULT WITH
THEIR DOCTOR BEFORE OPERATING.
Read and understand the following safety highlights. For
additional safety information, it is strongly recommended
that you purchase a copy of “Safety in Welding & Cutting ANSI Standard Z49.1” from the American Welding Society,
P.O. Box 351040, Miami, Florida 33135 or CSA Standard
W117.2-1974. A Free copy of “Arc Welding Safety” booklet
E205 is available from the Lincoln Electric Company,
22801 St. Clair Avenue, Cleveland, Ohio 44117-1199.
BE SURE THAT ALL INSTALLATION, OPERATION,
MAINTENANCE AND REPAIR PROCEDURES ARE
PERFORMED ONLY BY QUALIFIED INDIVIDUALS.
SAFETY
1.d. Keep all equipment safety guards, covers
and devices in position and in good repair.
Keep hands, hair, clothing and tools away
from V-belts, gears, fans and all other
moving parts when starting, operating or
repairing equipment.
1.e. In some cases it may be necessary to remove safety guards to
perform required maintenance. Remove guards only when
necessary and replace them when the maintenance requiring
heir removal is complete. Always use the greatest care when
t
working near moving parts.
1.f. Do not put your hands near the engine fan. Do not attempt to
override the governor or idler by pushing on the throttle control
rods while the engine is running.
1.g. To prevent accidentally starting gasoline engines while turning
the engine or welding generator during maintenance work,
disconnect the spark plug wires, distributor cap or magneto wire
as appropriate.
1.h. To avoid scalding, do not remove the radiator
pressure cap when the engine is
hot.
ELECTRIC AND
MAGNETIC FIELDS MAY
BE DANGEROUS
2.a. Electric current flowing through any conductor
causes localized Electric and Magnetic Fields (EMF).
Welding current creates EMF fields around welding cables
and welding machines
FOR ENGINE POWERED
EQUIPMENT.
1.a. Turn the engine off before troubleshooting
and maintenance work unless the
maintenance work requires it to be running.
1.b. Operate engines in open, well-ventilated
areas or vent the engine exhaust fumes outdoors.
1.c. Do not add the fuel near an open flame
welding arc or when the engine is running.
Stop the engine and allow it to cool before
refueling to prevent spilled fuel from
vaporizing on contact with hot engine parts
and igniting. Do not spill fuel when filling
tank. If fuel is spilled, wipe it up and do not start engine until
fumes have been eliminated.
2.b. EMF fields may interfere with some pacemakers, and
welders having a pacemaker should consult their physician
before welding.
2.c. Exposure to EMF fields in welding may have other health effects
which are now not known.
2.d. All welders should use the following procedures in order to
minimize exposure to EMF fields from the welding circuit:
2.d.1. Route the electrode and work cables together - Secure
them with tape when possible.
2.d.2. Never coil the electrode lead around your body.
2.d.3. Do not place your body between the electrode and work
cables. If the electrode cable is on your right side, the
work cable should also be on your right side.
2.d.4. Connect the work cable to the workpiece as close as possible to the area being welded.
2.d.5. Do not work next to welding power source.
Safety 02 of 04 - 06/15/2016
SAFETY
ELECTRIC SHOCK
CAN KILL.
3.a. The electrode and work (or ground) circuits are
electrically “hot” when the welder is on. Do
not touch these “hot” parts with your bare skin or wet clothing.
Wear dry, hole-free gloves to insulate hands.
3.b. Insulate yourself from work and ground using dry insulation.
Make certain the insulation is large enough to cover your full area
f physical contact with work and ground.
o
In addition to the normal safety precautions, if
welding must be performed under electrically
hazardous conditions (in damp locations or while
wearing wet clothing; on metal structures such as
floors, gratings or scaffolds; when in cramped
positions such as sitting, kneeling or lying, if there
is a high risk of unavoidable or accidental contact
with the workpiece or ground) use the following
equipment:
• Semiautomatic DC Constant Voltage (Wire) Welder.
• DC Manual (Stick) Welder.
• AC Welder with Reduced Voltage Control.
3.c. In semiautomatic or automatic wire welding, the electrode,
electrode reel, welding head, nozzle or semiautomatic welding
gun are also electrically “hot”.
3.d. Always be sure the work cable makes a good electrical
connection with the metal being welded. The connection should
be as close as possible to the area being welded.
3.e. Ground the work or metal to be welded to a good electrical (earth)
ground.
3.f. Maintain the electrode holder, work clamp, welding cable and
welding machine in good, safe operating condition. Replace
damaged insulation.
3.g. Never dip the electrode in water for cooling.
3.h. Never simultaneously touch electrically “hot” parts of electrode
holders connected to two welders because voltage
two can be the total of the open circuit voltage of both
welders.
3.i. When working above floor level, use a safety belt to protect
yourself from a fall should you get a shock.
between the
ARC RAYS CAN BURN.
4.a.Use a shield with the proper filter and cover plates to protect your
eyes from sparks and the rays of the arc when welding or
observing open arc welding. Headshield and filter lens should
conform to ANSI Z87. I standards.
4.b.Use suitable clothing made from durable flame-resistant material
to protect your skin and that of your helpers from the arc rays.
4.c.Protect other nearby personnel with suitable, non-flammable
screening and/or warn them not to watch the arc nor expose
themselves to the arc rays or to hot spatter or metal.
FUMES AND GASES
CAN BE DANGEROUS.
5.a. Welding may produce fumes and gases
hazardous to health. Avoid breathing these fumes and gases.
When welding, keep your head out of the fume. Use enough
ventilation and/or exhaust at the arc to keep fumes and gases
away from the breathing zone. When welding hardfacing
(see instructions on container or SDS) or on lead
or cadmium plated steel and other metals or
coatings which produce highly toxic fumes, keep
exposure as low as possible and within applicable
OSHA PEL and ACGIH TLV limits using local
exhaust or mechanical ventilation unless exposure
assessments indicate otherwise. In confined
spaces or in some circumstances, outdoors, a
respirator may also be required. Additional
precautions are also required when welding
on galvanized steel.
5. b. The operation of welding fume control equipment is affected by
various factors including proper use and positioning of the
equipment, maintenance of the equipment and the specific
welding procedure and application involved. Worker exposure
level should be checked upon installation and periodically
thereafter to be certain it is within applicable OSHA PEL and
ACGIH TLV limits.
5.c. Do not weld in locations near chlorinated hydrocarbon vapors
coming from degreasing, cleaning or spraying operations. The
heat and rays of the arc can react with solvent vapors to form
phosgene, a highly toxic gas, and other irritating products.
3.j. Also see It ems 6.c. and 8.
5.d. Shielding gases used for arc welding can displace air and
cause
injury or death. Always use enough ventilation, especially in
confined areas, to insure breathing air is safe.
5.e. Read and understand the manufacturer’s instructions for this
equipment and the consumables to be used, including the
Safety Data Sheet (SDS) and follow your employer’s safety
practices. SDS forms are available from your welding
distributor or from the manufacturer.
5.f. Also see item 1.b.
Safety 03 of 04 - 06/15/2016
SAFETY
WELDING AND CUTTING
SPARKS CAN CAUSE
FIRE OR EXPLOSION.
6.a. Remove fire hazards from the welding area. If
this is not possible, cover them to prevent the welding sparks
rom starting a fire. Remember that welding sparks and hot
f
materials from welding can easily go through small cracks and
openings to adjacent areas. Avoid welding near hydraulic lines.
Have a fire extinguisher readily available.
6.b. Where compressed gases are to be used at the job site, special
precautions should be used to prevent hazardous situations.
Refer to “Safety in Welding and Cutting” (ANSI Standard Z49.1)
and the operating information for the equipment being used.
6.c. When not welding, make certain no part of the electrode circuit is
touching the work or ground. Accidental contact can cause
overheating and create a fire hazard.
6.d. Do not heat, cut or weld tanks, drums or containers until the
proper steps have been taken to insure that such procedures
will not cause flammable or toxic vapors from substances inside.
They can cause an explosion even though they have been
“cleaned”. For information, purchase “Recommended Safe
Practices for the Preparation for Welding and Cutting of
Containers and Piping That Have Held Hazardous Substances”,
AWS F4.1 from the American Welding Society
(see address above).
6.e. Vent hollow castings or containers before heating, cutting or
welding. They may explode.
6.f. Sparks and spatter are thrown from the welding arc. Wear oil free
protective garments such as leather gloves, heavy shirt, cuffless
trousers, high shoes and a cap over your hair. Wear ear plugs
when welding out of position or in confined places. Always wear
safety glasses with side shields when in a welding area.
6.g. Connect the work cable to the work as close to the welding area
as practical. Work cables connected to the building framework or
other locations away from the welding area increase the
possibility of the welding current passing through lifting chains,
crane cables or other alternate circuits. This can create fire
hazards or overheat lifting chains or cables until they fail.
6.h. Also see item 1.c.
CYLINDER MAY EXPLODE IF
DAMAGED.
7.a. Use only compressed gas cylinders containing
the correct shielding gas for the process used
and properly operating regulators designed for
the gas and pressure used. All hoses, fittings,
tc. should be suitable for the application and
e
maintained in good condition.
7.b. Always keep cylinders in an upright position securely chained to
an undercarriage or fixed support.
7.c. Cylinders should be located:
•Away from areas where they may be struck or subjected
to physical damage.
•A safe distance from arc welding or cutting operations
and any other source of heat, sparks, or flame.
7.d. Never allow the electrode, electrode holder or any other
electrically “hot” parts to touch a cylinder.
7.e. Keep your head and face away from the cylinder valve outlet
when opening the cylinder valve.
7.f. Valve protection caps should always be in place and hand tight
except when the cylinder is in use or connected for use.
7.g. Read and follow the instructions on compressed gas cylinders,
associated equipment, and CGA publication P-l, “Precautions for
Safe Handling of Compressed Gases in Cylinders,” available from
the Compressed Gas Association, 14501 George Carter Way
Chantilly, VA 20151.
FOR ELECTRICALLY
POWERED EQUIPMENT.
8.a. Turn off input power using the disconnect
switch at the fuse box before working on
the equipment.
8.b. Install equipment in accordance with the U.S. National Electrical
Code, all local codes and the manufacturer’s recommendations.
6.I. Read and follow NFPA 51B “Standard for Fire Prevention During
Welding, Cutting and Other Hot Work”, available from NFPA, 1
Batterymarch Park, PO box 9101, Quincy, MA 022690-9101.
6.j. Do not use a welding power source for pipe thawing.
8.c. Ground the equipment in accordance with the U.S. National
Electrical Code and the manufacturer’s recommendations.
Refer to
http://www.lincolnelectric.com/safety
for additional safety information.
Safety 04 of 04 - 06/15/2016
VANTAGE 400
TABLE OF CONTENTS
Page
Installation ................................................................................................................................................Section A
General Description.......................................................................................................................................B-1
For Auxiliary Power .......................................................................................................................................B-1
Break in Period .............................................................................................................................................B-1
Auxiliary Power .............................................................................................................................................B-7
Simultaneous Welding and Power Loads...............................................................................................B-7
Parts List .......................................................................................................................................P-590
The VANTAGE 400 is a diesel engine powered DC multi-process
elding power source and 120 / 240 volt AC power generator.
w
The engine drives a generator that supplies three phase power
for the DC welding circuit, single phase and Three Phase power
for the AC auxiliary outlets. The DC welding control system uses
state of the art Chopper Technology (CT™) for superior welding
performance.
The Vantage 400 is fitted with a selectable VRD (Voltage Reduction
Device). The VRD operates in the CC-Stick mode reducing the OCV
to <13 volts, increasing operator safety when welding is performed in environments with increased hazard of electric shock.
FOR AUXILIARY POWER:
Start the engine and set the IDLER control switch to the desired
operating mode. Full power is available regardless of the welding
control settings providing no welding current is being drawn.
ENGINE OPERATION
Before Starting the Engine:
PRODUCT DESCRIPTION
• Be sure the machine is on a level surface.
• Open side engine door and remove the engine oil dipstick and
wipe it with a clean cloth. Reinsert the dipstick and check the
level on the dipstick.
• Add oil (if necessary) to bring the level up to the full mark. Do
not overfill. Close engine door.
• Check radiator for proper coolant level. (Fill if necessary).
• See Engine Owner’s Manual for specific oil and coolant recommendations.
Full Pressure K2410-3 EPA Tier 4 Interim CompliantMechanical Fuel Pump, Auto air bleedMechanical
with Full Flow Filter K2410-4 EPA Tier 4 Interim Compliant system, Electric shutoff solenoid,
K2410-7 EPA Tier 4 Final Compliant Indirect fuel injector.
AIR CLEANER ENGINE IDLER MUFFLER ENGINE PROTECTION
Low noise Muffler: Shutdown on low oil
Single ElementAutomatic Idler Top outlet can be rotated. pressure & high engine
Made from long life, aluminized steel. coolant temperature
ENGINE WARRANTY: 2 years / 2000 hours, all non-electric components, 3 years major non-electric components .
See Perkins warranty for details.
MACHINE SPECIFICATIONS
RECEPTACLES AUXILIARY POWER CIRCUIT BREAKER OTHER CIRCUIT BREAKERS
(2) 120VAC Duplex (5-20R) GFCI protected
(1) 120/240VAC Dual Voltage (1) 50AMP for Dual Voltage and for 10AMP for 42V Wire Feeder Power
(Full KVA (14-50R)14-50R) 3-Phase (3-pole)
(1) 240VAC 3-Phase (15-50R)
1. Output rating in watts is equivalent to volt-amperes at unity power factor. Output voltage is within ± 10% at all loads up to rated capacity. When
welding, available auxiliary power will be reduced.
* To Top of enclosure, add 10.68”(271.3mm) to top of exhaust pipe. Add 6.67”(169.4mm) to top of Lift Bail.
2. Reduced to less than 30V in the CC-stick Mode when VRD (VOLTAGE REDUCTION DEVICE) is on.
Two 20AMP for Two Duplex Receptacle 10AMP for Battery Charging Circuit
A-1
SAFETY PRECAUTIONS
(
VRD)-VOLTAGE REDUCTION DEVICE
S
WITCH IS LOCATED IN THIS AREA.
REMOVE 4 FRONT PANEL
S
CREWS TO ACC ESS
(VRD) SWITCH
WARNING
o not attempt to use this equipment until you have thor-
D
oughly read the engine manufacturer’s manual supplied
with your welder. It includes important safety precautions,
detailed engine starting, operating and maintenance instructions, and parts lists.
See additional warning information at front of this
operator’s manual.
Only qualified personnel should install,
use, or service this equipment.
VRD (VOLTAGE REDUCTION DEVICE)
The VRD feature provides additional safety in the CC-Stick mode especially
in an environment with a higher risk of electric shock such as wet areas and
hot humid sweaty conditions.
The VRD reduces the OCV (Open Circuit Voltage) at the welding output terminals while not welding to less than 30V DC when the resistance of the
output circuit is above 200 (ohms).
The VRD requires that the welding cable connections be kept in good electrical condition because poor connections will contribute to poor starting.
Having good electrical connections also limits the possibility of other safety
issues such as heat-generated damage, burns and fires.
The machine is shipped with the VRD switch in the “Off” position. To turn it
“On” or “Off”.
• Turn the engine “Off”.
• Disconnect the negative battery cable.
• Lower the control panel by removing 4 front panel screws. (See Figure
A.1)
• Place the VRD switch in the “On” or “Off” position. (See Figure A.1)
With the VRD switch in the “On” position, the VRD lights
are enabled.
INSTALLATIONVANTAGE 400
IGURE A.1
F
LOCATION AND VENTILATION
The welder should be located to provide an unrestricted flow of
clean, cool air to the cooling air inlets and to avoid restricting the
cooling air outlets. Also, locate the welder so that the engine
exhaust fumes are properly vented to an outside area.
STACKING
VANTAGE 400 machines cannot be stacked.
ANGLE OF OPERATION
Engines are designed to run in the level condition which is where
the optimum performance is achieved. The maximum angle of
continuous operation is 25 degrees in all directions, 35 degrees
Intermittent (less than 10 minutes continuous) in all directions. If
the engine is to be operated at an angle, provisions must be
made for checking and maintaining the oil level at the normal
(FULL) oil capacity in the crankcase.
When operating the welder at an angle, the effective fuel capacity will be slightly less than the amount specified.
LIFTING
The VANTAGE 400 weighs approximately 1345lbs. (611kg.) with
a full tank of fuel 1230lbs.(559kg) less fuel. A lift bail is mounted
to the machine and should always be used when lifting the
machine.
A-2
WARNING
• Lift only with equipment of adequate lifting capacity.
• Be sure machine is stable when lifting.
• Do not lift this machine using lift bail if it
is equipped with a heavy accessory such
as trailer or gas cylinder.
. Proper placement of the equipment on the trailer to insure stability side to
3
side and front to back when being moved and when standing by itself
while being operated or serviced.
4. Typical conditions of use, i.e., travel speed; roughness of surface on
which the trailer will be operated; environmental conditions; like mainte-
ance.
n
5. Conformance with federal, state and local laws.
1) Consult applicable federal, state and local laws regarding specific requirements for use on public highways.
(
(1)
NOTE: This machine is furnished with a wet charged battery; if unused
for several months, the battery may require a booster charge. Be careful
to charge the battery with the correct polarity. (See Battery in
“Maintenance Section”)
HIGH ALTITUDE OPERATION
At higher altitudes, output derating may be necessary. For maximum rating,
derate the machine 2.5% to 3.5% for every 1000 ft. (305m). Due to new
EPA and other local emissions regulations, modifications to the engine for
high altitude are restricted within the United States. For use above 6000
ft.(1828 m) an authorized Perkins engine field service shop should be contacted to determine if any adjustments can be made for operation in higher
elevations.
HIGH TEMPERATURE OPERATION
At temperatures above 104°F(40°C), Welder output derating is necessary.
For maximum output ratings, derate the welder output 2 volts for every
18°F
(10°
C) above 104°F(40°C).
Cold weather starting:
With a fully charged battery and the proper oil, the engine should start
satisfactorily down to -15°F(-26C°). If the engine must be frequently
started at or below 0°F (-18°C), it may be desirable to install cold-starting aides. The use of No. 1D diesel fuel is recommended in place of No.
2D at temperatures below 23°F (-5°C). Allow the engine to warm up
before applying a load or switching to high idle.
Use a recommended trailer for use with this equipment for road, in-plant
and yard towing by a vehicle(1). If the user adapts a non-Lincoln trailer, he
must assume responsibility that the method of attachment and usage does
not result in a safety hazard or damage the welding equipment. Some of the
factors to be considered are as follows:
1. Design capacity of trailer vs. weight of Lincoln equipment and likely additional attachments.
2. Proper support of, and attachment to, the base of the welding equipment
so there will be no undue stress to the framework.
• Stop engine and allow to cool before fueling
• Do not smoke when fueling.
• Fill fuel tank at a moderate rate and do not overfill.
• Wipe up spilled fuel and allow fumes to clear before
starting engine.
The VANTAGE 400 is shipped with the engine crankcase filled
with high quality SAE 10W-30 Oil that meets classification CG-4
or CH-4 for diesel engines. Check the oil level before starting
he engine. If it is not up to the full mark on the dip stick, add oil
t
as required. Check the oil level every four hours of running time
uring the first 50 running hours. Refer to the engine Operator’s
d
Manual for specific oil recommendations and break-in information. The oil change interval is dependent on the quality of the oil
and the operating environment. Refer to the Engine Operator’s
Manual for more details on the proper service and maintenance
intervals.
FUEL
USE DIESEL FUEL ONLY
WARNING
• Fill the fuel tank with clean, fresh fuel. The capacity of the
tank is 20 gals. (75.7 ltrs). When the fuel gauge reads
empty the tank contains approximately 2 gals. (7.6ltrs.) of
reserve fuel.
WARNING
NOTE: A fuel shut off valve is located on the pre-filter/sedi-
ment filter. Which should be in the closed position
when the welder is not used for extended periods of
time.
Using the clamp provided secure the outlet pipe to the outlet tube with
the pipe positioned such that it will direct the exhaust in the desired
direction. Tighten using a 9/16" socket or wrench.
SPARK ARRESTER
Some federal, state or local laws may require that gasoline or diesel
engines be equipped with exhaust spark arresters when they are operated in certain locations where unarrested sparks may present a fire
hazard. The standard muffler included with this welder does not qualify
as a spark arrester. When required by local regulations, a suitable spark
arrester, such as the K903-1 must be installed and properly maintained.
WARNING
An incorrect spark arrestor may lead to damage to the engine or
adversely affect performance.
The VANTAGE® 400 is equipped with a 6-pin and a 14-pin connector.
When in the ARC GOUGING or CV-WIRE modes and when a remote control
is connected to the 6-pin Connector, the auto-sensing circuit automatically
switches the OUTPUT control from control at the welder to remote control.
When in TOUCH START TIG mode and when a Amptrol is connected to the 6Pin Connector, the OUTPUT dial is used to set the maximum current range of
the CURRENT CONTROL of the Amptrol.
When in the CC-STICK or DOWNHILL PIPE mode and when a remote control
is connected to the 6-Pin or 14-Pin connector, the output control is used to
set the maximum current range of the remote.
WARNING
Air to cool the engine is drawn in the side and exhausted
through radiator & case back. It is important that the intake
and exhaust air is not restricted. Allow a minimum clearance of 1ft. (0.6m) from the case back and 16in.(406mm)
from either side of the base to a vertical surface.
The VANTAGE 400 is shipped with the negative battery cable disconnected. Make certain that the RUN-STOP switch is in the
STOP position. Remove the two screws from the battery tray
using a screwdriver or a 3/8" socket. Attach the negative battery
cable to the negative battery terminal and tighten using a 1/2"
socket or wrench.
EXAMPLE: When the OUTPUT CONTROL on the welder is set to 200 amps
the current range on the remote control will be Min.-200 amps, rather than
the full Min.-Max. amps. Any current range that is less than the full range
provides finer current resolution for more fine tuning of the output.
In the CV-WIRE mode, if the feeder being used has a voltage control when
the wire feeder control cable is connected to the 14-Pin Connector, the
auto-sensing circuit automatically makes OUTPUT CONTROL inactive and
the wire feeder voltage control active. Otherwise, the OUTPUT CONTROL is
used to preset the voltage.
The 14-pin connector is used to directly connect a wire feeder control cable.
In the CV-WIRE mode, when the control cable is connected to the 14-pin
connector, the auto-sensing circuit automatically makes the Output Control
inactive and the wire feeder voltage control active.
NOTE: When a wire feeder with a built in welding voltage control is
connected to the 14-pin connector, do not connect anything to the 6pin connector.
Because this portable engine driven welder creates
its own power, it is not necessary to connect its
frame to an earth ground, unless the machine is connected to
premises wiring (home, shop, etc.)
INSTALLATIONVANTAGE 400
current and duty cycle. Length refers to the distance from the
elder to the work and back to the welder. Cable diameters are
w
increased for long cable lengths to reduce voltage drops.
TABLE A.1
CABLE INSTALLATION
To prevent dangerous electric shock, other equipment to which
this engine driven welder supplies power must:
• Be grounded to the frame of the welder using a grounded
type plug or be double insulated.
WARNING
• Do not ground the machine to a pipe that carries explosive or combustible material.
When this welder is mounted on a truck or trailer, its frame
WARNING
must be electrically bonded to the metal frame of the vehicle. Use a #8 or larger copper wire connected between the
machine grounding stud and the frame of the vehicle. When
this engine driven welder is connected to premises wiring
such as that in a home or shop, its frame must be connected
to the system earth ground. See further connection instructions in the section entitled "Standby Power Connections"
as well as the article on grounding in the latest National
Electrical Code and the local code.
In general, if the machine is to be grounded, it should be connected with a #8 or larger copper wire to a solid earth ground
such as a metal water pipe going into the ground for at least ten
feet and having no insulated joints, or to the metal framework of
a building which has been effectively grounded.
The National Electrical Code lists a number of alternate means of
grounding electrical equipment. A machine grounding stud
marked with the symbol is provided on the front of the
welder.
TOTAL COMBINED LENGTH OF
ELECTRODE AND WORK CABLES
Cable Length
0-100 Ft. (0-30 meters)
100-150 Ft. (30-46 meters)
150-200 Ft. (46-61 meters)
Install the welding cables to your VANTAGE 400 as follows.
1. The engine must be OFF to install welding cables.
2. Remove the flanged nuts from the output terminals
3. Connect the electrode holder and work cables to the weld output terminals. The terminals are identified on the case front.
4. Tighten the flanged nuts securely.
5. Be certain that the metal piece you are welding (the “work”) is
properly connected to the work clamp and cable.
6. Check and tighten the connections periodically.
• Loose connections will cause the output terminals to over-
heat. The terminals may eventually melt.
Cable Size for
400 Amps
60% Duty Cycle
2 / 0 AWG
2 / 0 AWG
3 / 0 AWG
CAUTION
• Do not cross the welding cables at the output terminal
connection. Keep the cables isolated and separate from
one another.
The VANTAGE 400 is equipped with a toggle switch for selecting
"hot" welding terminal when in the "WELD TERMINALS ON"
position or "cold" welding terminal when in the "REMOTELY
CONTROLLED" position.
WELDING OUTPUT CABLES
With the engine off connect the electrode and work cables to the
output studs. The welding process dictates the polarity of the
electrode cable. These connections should be checked periodically and tightened with a 3/4" wrench.
Table A.1 lists recommended cable sizes and lengths for rated
Start the engine and set the “IDLER” control switch to the “High
Idle” mode. Voltage is now correct at the receptacles for auxiliary
power. This must be done before a tripped GFCI can be reset
properly. See the MAINTENANCE section for more detailed information on testing and resetting the GFCI.
The auxiliary power of the VANTAGE 400 consists of two 20
Amp-120 VAC (5-20R) duplex receptacles with GFCI protection,
one 50 Amp 120/240 VAC (14-50R) receptacle and one 50 Amp
240VAC Three-Phase (15-50R) receptacle.
The auxiliary power capacity is 12,000 watts Peak, 11,000 Watts
Continuous of 60 Hz, single phase power. The auxiliary power
capacity rating in watts is equivalent to volt-amperes at unity
power factor. The max permissible current of the 240 VAC output
A-5
INSTALLATIONVANTAGE 400
is 50amps.
The 240 VAC output can be split to provide two separate 120 VAC
utputs with a max permissible current of 50 Amps per output to
o
two separate 120 VAC branch circuits (these circuits cannot be
paralleled). Output voltage is within ± 10% at all loads up to rated
capacity.
The Three-Phases auxiliary power capacity is 17,000 watts peak,
19,000 watts continuous. The maximum current is 45 amps.
120 V DUPLEX RECEPTACLES AND GFCI
A GFCI protects, the two 120V Auxiliary Power receptacles. A
GFCI (Ground Fault Circuit Interrupter) electrical receptacle is a
device to protect against electric shock should a piece of defective equipment connected to it develop a ground fault. If this situation should occur, the GFCI will trip, removing voltage from the
output of the receptacle. If a GFCI is tripped see the MAINTENANCE section for detailed information on testing and resetting it.
A GFCI should be properly tested at least once every month.
The 120 V auxiliary power receptacles should only be used with
three wire grounded type plugs or approved double insulated
tools with two wire plugs. The current rating of any plug used
with the system must be at least equal to the current capacity of
the associated receptacle.
circuit breaker. Maximum rated load for each leg of the 240
AC auxiliary is 50 amperes. Loading above the rated output
V
will reduce output voltage below the allowable - 10% of rated
oltage which may damage appliances or other motor-driven
v
equipment and may result in overheating of the engine
and/or alternator windings.
Install a 50 amp, 120/240 VAC plug (NEMA Type 14-50P) to
•
the double-pole circuit breaker using No. 6, 4 conductor
cable of the desired length. (The 50 amp, 120/240 VAC plug
is available in the optional K802R plug kit or as part number
T12153-9.)
• Plug this cable into the 50 Amp, 120/240 Volt receptacle on
the case front.
NOTE: The 240 V receptacle has two 120 V circuits,
but are of opposite polarities and cannot be paralleled.
All auxiliary power is protected by circuit breakers.
The 120V has 20 Amp circuit breakers for each duplex receptacle. The 120/240V Single Phase and the 240V Three-Phases have
a 50 Amp 3-pole Circuit Breaker that disconnects both hot leads
and all Three Phases simultaneously.
STANDBY POWER CONNECTIONS
The VANTAGE 400 is suitable for temporary, standby or emergency power using the engine manufacturer’s recommended
maintenance schedule.
The VANTAGE 400 can be permanently installed as a standby
power unit for 240 VAC, 3 wire, single phase, 50 amp service.
Connections must be made by a licensed electrician who can
determine how the 120/240 VAC power can be adapted to the
particular installation and comply with all applicable electrical
codes.
• Install the double-pole, double-throw switch between the
power company meter and the premises disconnect. Switch
rating must be the same or greater than the customer’s
premises disconnect and service over current protection.
• Take necessary steps to assure load is limited to the capacity
of the generator by installing a 50 amp, 240 VAC double pole
A-6
CONNECTION OF VANTAGE 400 TO PREMISES WIRING
240 Volt
6
0 Hz.
3
-Wire
Service
POWER
COMPANY
METER
240 VOLT
120 VOLT
120 VOLT
L
OAD
N
NEUTRAL
BUS
G
ROUND
PREMISES
D
ISCONNECT AND
SERVICE
OVERCURRENT
P
ROTECTION
GND
N
NOTE: No. 6 COPPER CONDUCTOR CABLE SEE
NATIONAL ELECTRICAL CODE FOR ALTERNATE WIRE
SIZE RECOMMENDATIONS.
240 VOLT
G
ROUNDED CONDUCTOR
5
0AMP
240 VOLT
D
OUBLE
POLE
CIRCUIT
BREAKER
D
OUBLE POLE DOUBLE THROW
SWITCH RATING TO BE THE SAME
AS OR GREATER THAN PREMISES
S
ERVICE OVERCURRENT
P
ROTECTION.
50 AMP, 120/240
VOLT PLUG
NEMA TYPE 14-50
50 AMP, 120/240 VOLT
RECEPTACLE
INSTALLATIONVANTAGE 400
WARNING
• Only a licensed, certified, trained electrician should install the machine to a premises or residential electrical system. Be
certain that:
• The installation complies with the National Electrical Code and all other applicable electrical codes.
• The premises is isolated and no feedback into the utility system can occur. Certain state and local laws require the premis-
es to be isolated before the generator is linked to the premises. Check your state and local requirements.
• A double pole, double throw transfer switch in conjunction with the properly rated double throw circuit breaker is connect-
ed between the generator power and the utility meter.
A-7
INSTALLATIONVANTAGE 400
CONNECTION OF LINCOLN ELECTRIC WIRE
FEEDERS
Connection of LN-7 or LN-8 to the VANTAGE 400
1. Shut the welder off.
2. Connect the LN-7 or LN-8 per instructions on the appropriate
connection diagram in Section F.
3. Set the "WIRE FEEDER VOLTMETER" switch to either "+" or
"-" as required by the electrode being used.
4. Set the "MODE" switch to the "CV WIRE " position.
5. Set the "ARC CONTROL" knob to "0" initially and adjust to
suit.
6. Set the "WELD TERMINALS" switch to the "REMOTELY CON-
TROLLED" position.
7. Set the "IDLE" switch to the "HIGH" position.
Connection of LN-15 to the VANTAGE 400
4. Control Cable Model:
• Connect Control Cable between Engine Welder and Feeder.
• Set the "WELD TERMINALS" switch to "REMOTELY
CONTROLLED"
Set the MODE switch to the "CV-WIRE " position.
•
• Set the "WIRE FEEDER VOLTMETER" switch to either "+" or
"-" as required by the electrode polarity being used.
• Set the "ARC CONTROL" knob to "0" initially and adjust to
suit.
• Set the "IDLE" switch to the "AUTO" position.
• When the gun trigger is closed, the current sensing circuit
will cause the VANTAGE 400 engine to go to the high idle
speed, the wire will begin to feed and the welding process
started. When welding is stopped, the engine will revert to
low idle speed after approximately 12 seconds unless
welding is resumed.
1. Shut the welder off.
2. For electrode Positive, connect the electrode cable to the "+"
terminal of the welder and work cable to the "-" terminal of
the welder. For electrode Negative, connect the electrode
cable to the "-" terminal of the welder and work cable to the
"+" terminal of the welder.
3. Across The-Arc Model:
• Attach the single lead from the front of the LN-15 to work
using the spring clip at the end of the lead. This is a control
lead to supply current to the wire feeder motor; it does not
carry welding current.
• Set the "WELD TERMINALS" switch to "WELD TERMINALS
ON".
• When the gun trigger is closed, the current sensing circuit
will cause the VANTAGE 400 engine to go to the high idle
speed, the wire will begin to feed and the welding process
started. When welding is stopped, the engine will revert to
low idle speed after approximately 12 seconds unless
welding is resumed.
A-8
INSTALLATIONVANTAGE 400
WARNING
Connection of the LN-25 to the VANTAGE 400
Shut off welder before makin g any elec tri cal
connections.
The LN-25 with or without an internal contactor may be used
with the VANTAGE 400. See the appropriate connection diagram
in Section F.
NOTE: The LN-25 (K431) Remote Control Module and (K432)
Remote Cable are not recommended for use with the VANTAGE
400.
1. Shut the welder off.
2. For electrode Positive, connect the electrode cable from the
LN-25 to the "+" terminal of the welder and work cable to
the "-" terminal of the welder. For electrode Negative, connect the electrode cable from the LN-25 to the "-" terminal
of the welder and work cable to the "+" terminal of the
welder.
Spool Gun (K487-25) and Cobramatic to
VANTAGE 400
• Shut the welder off.
• Connect per instructions on the appropriate connection diagram in Section F.
Connection of PRINCE XL SPOOL GUN to the VANTAGE 400
Connection of the Prince XL Spool Gun requires the use of the
K1849-1 Adapter Module.
• Shut the Welder off.
• For electrode Positive, connect the electrode cable to the "+"
terminal of the welder and work cable to the "-" terminal of
the welder. For electrode Negative, connect the electrode
cable "-" terminal of the welder and work cable to the "+"
terminal of the welder.
• Connect the Control Cable of the Spool Gun to the Adapter
Module and connect the Control Cable of the Adapter Module
to the Welder.
3. Attach the single lead from the front of the LN-25 to work
using the spring clip at the end of the lead. This is a control
lead to supply current to the wire feeder motor; it does not
carry welding current.
4. Set the MODE switch to the "CV-WIRE " position.
5. Set the "WELD TERMINALS" switch to "WELD TERMINALS
ON"
6. Set the "ARC CONTROL" knob to "0" initially and adjust to
suit.
7. Set the "IDLE" switch to the "AUTO" position. When not
welding, the VANTAGE 400 engine will be at the low idle
speed. If you are using an LN-25 with an internal contactor,
the electrode is not energized until the gun trigger is closed.
8. When the gun trigger is closed, the current sensing circuit
will cause the VANTAGE 400 engine to go to the high idle
speed, the wire will begin to feed and the welding process
started. When welding is stopped, the engine will revert to
low idle speed after approximately 12 seconds unless welding is resumed.
• Connect the Gas Hose.
• Set the MODE switch to the "CV-WIRE " position.
• Set the "WELD TERMINALS" switch to "WELD TERMINALS
ON".
• Set the "ARC CONTROL" knob to "0" initially and adjust to
suit.
• Set the “IDLE” switch to the “HIGH” position.
CAUTION
If you are using an LN-25 without an internal contactor, the
electrode will be energized when the VANTAGE 400 is started.
Do not attempt to use this equipment until you have thoroughly read the engine manufacturer’s manual supplied
with your welder. It includes important safety precautions,
et ailed engine starting, operating an d maintenanc e
• Do not touch electrically live parts or electrode with skin
or wet clothing.
• Insulate yourself from work and ground
• Always wear dry insulating gloves.
• Always operate the welder with the hinged
door closed and the side panels in place.
• Read carefully the Safety Precautions page before operat-
ing this machine. Always follow these and any other safety procedures included in this manual and in the Engine
Instruction Manual.
GENERAL DESCRIPTION
The VANTAGE 400 is a diesel engine powered DC multi-process
welding power source and 120 / 240 volt AC power generator.
The engine drives a generator that supplies three phase power
for the DC welding circuit, single phase and Three Phase power
for the AC auxiliary outlets. The DC welding control system uses
state of the art Chopper Technology (CT™) for superior welding
performance.
Th e Van ta ge 400 is fitt ed with a sele ct ab le VRD(Voltage
Reduction Device). The VRD operates in the CC-Stick mode
reducing the OCV to <13 volts, increasing operator safety when
welding is performed in environments with increased hazard of
electric shock.
OPERATIONVANTAGE 400
ADD FUEL
WARNING
• Stop engine while fueling.
• Do not smoke when fueling.
• Keep sparks and flame away from
tank.
• Do not leave unattended while fueling.
• Wipe up spilled fuel and allow fumes
to clear before starting engine.
DIESEL FUEL
can cause fire.
• Do not overfill tank, fuel expansion
may cause overflow.
• Fill the tank. DO NOT FILL THE TANK TO THE POINT OF OVERFLOW.
• Replace the fuel cap and tighten securely.
• See Engine Owner’s Manual for specific fuel recommendations.
BREAK-IN PERIOD
The engine will use a small amount of oil during its “break-in”
period. The break-in period is about 50 running hours.
FOR AUXILIARY POWER:
Start the engine and set the IDLER control switch to the desired
operating mode. Full power is available regardless of the welding
control settings providing no welding current is being drawn.
ENGINE OPERATION
Before Starting the Engine:
• Be sure the machine is on a level surface.
• Open side engine door and remove the engine oil dipstick and
wipe it with a clean cloth. Reinsert the dipstick and check the
level on the dipstick.
• Add oil (if necessary) to bring the level up to the full mark. Do
not overfill. Close engine door.
• Check radiator for proper coolant level. (Fill if necessary).
• See Engine Owner’s Manual for specific oil and coolant
recommendations.
Check the oil every four hours during break-in. Change the oil
after the first 50 hours of operation and every 200 hours thereafter. Change the oil filter at each oil change.
CAUTION
During break-in, subject the Welder to moderate loads.
Avoid long periods running at idle. Before stopping the
engine, remove all loads and allow the engine to cool several minutes.
voltage or current as displayed on the digital meters for the five welding modes. When in the ARC GOUGING or CV-WIRE modes and when
a remote control is connected to the 6-Pin or 14-Pin Connector, the
auto-sensing circuit automatically switches the OUTPUT CONTROL
from control at the welder to the remote control.
The OUTPUT dial is used to preset the output
15
8
7
23
21
18
19
6
2. DIGITAL OUTPUT METERS-The digital meters allow the output
voltage (CV-WIRE mode) or current (CC-STICK,DOWN HILL PIPE and
TIG modes) to be set prior to welding using the OUTPUT control dial.
During welding, the meter display the actual output voltage (VOLTS)
and current (AMPS). A memory feature holds the display of both
meters on for seven seconds after welding is stopped. This allows
the operator to read the actual current and voltage just prior to when
welding was ceased.
When in the CC-STICK or DOWNHILL PIPE mode and when a remote
control is connected to the 6-Pin or 14-Pin connector, the output control is used to set the maximum current range of the remote.
EXAMPLE: When the OUTPUT CONTROL on the welder is set to 200
amps the current range on the remote control will be Min.-200 amps,
rather than the full Min.-Max. amps. Any current range that is less
than the full range provides finer current resolution for more fine tuning of the output.
In the CV-WIRE mode, if the feeder being used has a voltage control
when the wire feeder control cable is connected to the 14-Pin
Connector, the auto-sensing circuit automatically makes OUTPUT
CONTROL inactive and the wire feeder voltag e control active.
Otherwise, the OUTPUT CONTROL is used to preset the voltage.
When in the TOUCH START TIG mode and when an Amptrol is connected to the 6-Pin Connector, the OUTPUT dial is used to set the
maximum current range of the CURRENT CONTROL of the Amptrol.
While the display is being held the left-most decimal point in each
display will be flashing. The accuracy of the meters is +/- 3%.
4. ARC CONTROL- The ARC CONTROL dial is active in the CV-WIRE,
CC-STICK and DOWNHILL PIPE modes, and has different functions in
hese modes. This control is not active in the TIG mode and ARC
t
GOUGING mode.
CC-STICK mode: In this mode, the ARC CONTROL dial sets the short
ircuit current (arc-force) during stick welding to adjust for a soft or
c
crisp arc. Increasing the dial from –10 (soft) to +10 (crisp) increases
the short circuit current and prevents sticking of the electrode to the
plate while welding. This can also increase spatter. It is recommended
that the ARC CONTROL be set to the minimum number without electrode sticking. Start with a setting at 0.
DOWNHILL PIPE mode: In this mode, the ARC CONTROL dial sets the
short circuit current (arc-force) during stick welding to adjust for a soft
or a more forceful digging arc (crisp). Increasing the number from –10
(soft) to +10 (crisp) increases the short circuit current which results in a
more forceful digging arc. Typically a forceful digging arc is preferred for
root and hot passes. A softer arc is preferred for fill and cap passes
where weld puddle control and deposition ("stacking" of iron) are key to
fast travel speeds. It is recommended that the ARC CONTROL be set initially at 0.
CV-WIRE mode: In this mode, turning the ARC CONTROL clock wise
from –10 (soft) to +10 (crisp) changes the arc from soft and washed-in
to crisp and narrow. It acts as an inductance/pinch control. The proper
setting depends on the procedure and operator preference. Start with a
setting of 0.
5. WELD OUTPUT TERMINALS WITH FLANGE NUT- Provides a
connection point for the electrode and work cables.
6. GROUND STUD- Provides a connection point for connecting
the machine case to earth ground.
7. 14-PIN CONNECTOR- For attaching wire feeder control cables.
Includes contactor closure circuit, auto-sensing remote control circuit,
and 120V and 42V power. The remote control circuit operates the same
as the 6 Pin Amphenol.
8. 6-PIN CONNECTOR- For attaching optional remote control equip-
ment. Includes auto-sensing remote control circuit.
9. WELD TERMINALS CONTROL SWITCH- In the WELD TERMI-
NALS ON position, the output is electrically hot all the time. In the
REMOTELY CONTROLLED position, the output is controlled by a wire
feeder or amptrol device, and is electrically off until a remote switch is
depressed.
cator lights. A red light when lit indicates
reater than 30V and a green light when
Voltage) is equal to or
lit indicates
OCV(Open Circuit Voltage)
g
OCV (Open Circuit
is less than 30V.
The VRD “On/Off” switch inside the control panel must be “On”
for the VRD function to be active and the lights to be enabled.
When the machine is first started with VRD enabled, both lights
ill illuminate for 5 seconds.
w
These lights monitor the
OCV (Open Circuit Voltage)
and weld
voltage at all times. In the CC-Stick mode when not welding the
green light will illuminate indicating that the VRD has reduced
the OCV to less than 30V. During welding the red light will illuminate whenever the arc voltage is equal to or greater than 30V.
This means that the red and green light may alternate depending on the weld voltage. This is normal operation.
If the red light remains illuminated when not welding in the CCstick mode, the VRD is not functioning properly. Please refer to
your local field service shop for service.
If the VRD is turned “On” and the lights don’t come “On”, refer to
the trouble shooting section.
TABLE B.1
MODE VRD "ON"VRD "OFF"
CC-STICK OCV Green (OCV Reduced)
While Red or Green
Welding (Depends on Weld Voltage) *
CV-WIRE OCV Red (OCV Not Reduced)
Weld Terminals On
Red (OCV Not Reduced)
Weld Terminals Remotely Controlled
Gun Trigger Closed
Green (No OCV)
Weld Terminals Remotely Controlled
Gun Trigger OpenNo Lights
While Red or Green
Welding (Depends on Weld Voltage) *
PIPE OCV Green (No Output)
While Not Applicable (No Output)
Welding
ARC GOUGING
While Not Applicable (No Output)
Welding
TIG OCV Green (Process is Low Voltage)
While Green (Process is Low Voltage)
Welding
OCV Green (No Output)
VRD INDICATOR LIGHTS
* It is normal for the lights to alternate between colors while welding.
10. WIRE FEEDER VOLTMETER SWITCH:
Matches the polarity of the wire feeder voltmeter to the polarity
of the electrode.
11. VRD (Voltage Reduction Device) INDICATOR
LIGHTS- On the front panel of the VANTAGE 400 are two indi-
B-3
ANTAGE 400
V
OPERATION
ENGINE CONTROLS:
12. RUN/STOP SWITCH - RUN position energizes the engine prior
to starting. STOP position stops the engine. The oil pressure interlock switch prevents battery drain if the switch is left in the RUN
osition and the engine is not operating.
p
13. GLOW PLUG PUSH BUTTON -
• When pushed activates the glow plugs. Glow plug should not be
activated for more than 20 seconds continuously.
14. START PUSH BUTTON - Energizes the starter motor to crank
the engine.
15. IDLER SWITCH- Has two positions as follows:
1) In the HIGH position, the engine runs at the high idle speed
controlled by the engine governor.
2) In the AUTO position, the idler operates as follows:
• When switched from HIGH to AUTO or after starting the engine,
the engine will operate at full speed for approximately 12 seconds
and then go to low idle speed.
• When the electrode touches the work or power is drawn for lights
or tools (approximately 100 Watts minimum), the engine accelerates and operates at full speed.
• When welding ceases or the AC power load is turned off, a fixed
time delay of approximately 12 seconds starts. If the welding or
AC power load is not restarted before the end of the time delay,
the idler reduces the engine speed to low idle speed.
• The engine will automatically return to high idle speed when there
is welding load or AC power load reapplied.
16. ELECTRIC FUEL GAUGE- The electric fuel gauge gives accu-
rate and reliable indication as to how much fuel is in the fuel tank.
17. ENGINE HOUR METER- Displays the total time that the engine has
been running. This meter is useful for scheduling prescribed maintenance.
18. ENGINE PROTECTION LIGHT- A warning indicator light for Low
Oil Pressure and/or Coolant Over Temperature.The light is off when the
systems are functioning properly. The light will come on and the engine
TABLE B.2
TYPICAL VANTAGE 400 FUEL CONSUMPTION
Low Idle - No Load
1400 R.P.M.
High Idle - No Load
1880 R.P.M.
DC Weld Output
400 Amps @ 36 Volts
17,000 Watts 3 Phase
11,000 Watts 1 Phase
PERKINS 404C-22
Gal./Hr (Liters/Hr)
.26 (.97)
.42 (1.57)
1.18 (4.46)
1.24 (4.68)
.90 (3.42)
Running Time for
20 gallons / hours
76.92
47.62
16.95
16.13
22.22
will shutdown when there is Low Oil Pressure and/or the Coolant is Over
Temperature.
Note: The light remains off when the RUN-STOP switch is in the "ON"
position prior to starting the engine.However if the engine is not started
within 60 seconds the light will come on. When this happens the RUNSTOP switch must be returned to the "OFF" position to reset the engine
protection system and light.
19. BATTERY CHARGING LIGHT- A warning indicator light
for Low/No battery charge. The light is off when the systems are functioning properly. The light will come on if there is a Low/No battery con-
dition but the machine will continue to run.
Note: The light may or may not come on when the RUN-STOP switch is in
the "ON" position. It will come on during cranking and stay on until the
engine starts. After starting the engine the light will go off unless a Low/No
battery charge condition exists.
20. COOLANT TEMPERATURE GAUGE-A indicator of engine coolant
temperature.
21. OIL PRESSURE GAUGE- A indicator of engine Oil Pressure.
22. CIRCUIT BREAKER- For protection of Battery Charging Circuit.
23. CIRCUIT BREAKER- For protection of 42V Wire Feeder circuit.
STARTING THE ENGINE
1. Remove all plugs connected to the AC power receptacles.
2. Set IDLER switch to AUTO.
3. Press Glow Plug Button and hold 15 to 20 seconds.
4. Set the RUN/STOP switch to RUN.
5. Press START button until the engine starts or for up to 10 seconds.
Continue to hold the glow plug button for up to an additional 10 seconds.
6. Release the engine START button immediately when the engine
starts.
7. The engine will run at high idle speed for approximately 12 seconds
and then drop to low idle speed. Allow the engine to warm up at low
idle for several minutes before applying a load and/or switching to
high idle. Allow a longer warm up time in cold weather.
NOTE: This data is for reference only. Fuel consumption is
approximate and can be influenced by many factors, including
engine maintenance, environmental conditions and fuel quality.
B-4
ANTAGE 400
V
OPERATION
NOTE: If the unit fails to start turn Run/Stop switch to off and
repeat step 3 through step 7 after waiting 30 seconds.
CAUTION
• Do not allow the starter motor to run continuously
than 20 seconds.
• Do not push the START button while the engine is run-
ning because this can damage the ring gear and/or the
starter motor.
• IF the Engine Protection or Battery Charging Lights do
“not” turn off shortly after starting the engine shut off
the engine immediately and determine the cause.
NOTE: When starting for the first time, or after and extended
period of time of not operating, it will take longer than normal to
start because the fuel pump has to fill the fuel system. For best
results, bleed the fuel system as indicated in Maintenance
Section of this manual.
STOPPING THE ENGINE
Remove all welding and auxiliary power loads and allow the
engine to run at low idle speed for a few minutes to cool the
engine.
STOP the engine by placing the RUN-STOP switch in the STOP
position.
NOTE: A fuel shut off valve is located on the fuel pre-filter.
WELDER OPERATION
DUTY CYCLE
Duty Cycle is the percentage of time the load is being applied in a 10
minute period. For example a 60% duty cycle, represents 6 minutes
of load and 4 minutes of no load in a 10 minute period.
ELECTRODE INFORMATION
For any electrode the procedures should be kept within the rating of the machine. For information on electrodes and their proper application see (www.lincolnelectric.com) or the appropriate
Lincoln publication.
for more
set to the minimum number without electrode sticking. Start with
the dial set at 0.
NOTE: Due to the low OCV with the VRD on, a very slight
delay during striking of the electrodes may occur. Due to the
equirement of the resistance in the circuit to be low for a
r
VRD to operate, a good metal-to-metal contact must be made
between the metal core of the electrode and the job. A poor
connection anywhere in the welding output circuit may limit
the operation of the VRD. This includes a good connection of
the work clamp to the job. The work clamp should be connected as close as practical to where the welding will be performed.
A. For New Electrodes
E6010 - Touch, Lift to Start the Arc
E7018, E7024 - Touch, Rock Back and Forth in Joint, Lift .
Once the arc is started, normal welding technique for the
application is then used.
B. For Re-Striking Electrodes
Some electrodes form a cone at the end of the electrode after
the welding arc has been broken, particularly iron powder
and low hydrogen electrodes. This cone will need to be broken off in order to have the metal core of the electrode make
contact.
E6010 - Push, Twist in Joint, Lift
E7018, E7024 - Push, Rock Back and Forth in Joint, Lift.
Once the arc is started, normal welding technique for the
application is then used.
For other electrodes the above techniques should be tried
first and varied as needed to suit operator preference. The
goal for successful starting is good metal to metal contact.
For indicator light operation, see table B.1.
DOWNHILL PIPE Welding
The VANTAGE 400 can be used with a broad range of DC stick electrodes. The MODE switch provides two stick welding settings as follows:
CONSTANT CURRENT (CC-STICK) WELDING
The CC-STICK position of the MODE switch is designed for horizontal
and vertical-up welding with all types of electrodes, especially low
hydrogen. The OUTPUT CONTROL dial adjusts the full output range
for stick welding.
The ARC CONTROL dial sets the short circuit current (arc-force) during
stick welding to adjust for a soft or crisp arc. Increasing the number
from -10(soft) to +10(crisp) increases the short circuit current and
prevents sticking of the electrode to the plate while welding. This can
also increase spatter. It is recommended that the ARC CONTROL be
This slope controlled setting is intended for "out-of-position" and
"down hill" pipe welding where the operator would like to control
the current level by changing the arc length.
The OUTPUT CONTROL dial adjusts the full output range for pipe
welding.
The ARC CONTROL dial sets the short circuit current (arc-force)
during stick welding to adjust for a soft or more forceful digging
arc (crisp). Increasing the number from -10(soft) to +10(crisp)
increases the short circuit current which results in a more forceful digging arc.
Typically a forceful digging arc is preferred for root and hot passes. A softer arc is preferred for fill and cap passes where weld
puddle control and deposition (“stacking” of iron) are key to fast
B-5
ANTAGE 400
V
travel speeds. This can also increase spatter.
It is recommended that the ARC CONTROL be set to the minimum
umber without electrode sticking. Start with the dial set at 0.
n
NOTE: With the VRD switch in the “ON” position there is no output in
the DOWNHILL PIPE mode.
For indicator light operation, see table
B.1.
TIG WELDING
The TOUCH START TIG setting of the MODE switch is for DC TIG
(Tungsten Inert Gas) welding. To initiate a weld, the OUTPUT CONTROL dial is first set to the desired current and the tungsten is
touched to the work. During the time the tungsten is touching the
work there is very little voltage or current and, in general, no tungsten contamination. Then, the tungsten is gently lifted off the work
in a rocking motion, which establishes the arc.
OPERATION
he VANTAGE 400 can be used in a wide variety of DC TIG weld-
T
ing applications. In general the ‘Touch Start’ feature allows contamination free starting without the use of a Hi-frequency unit. If
desired, the K930-2 TIG Module can be used with the VANTAGE
400. The settings are for reference.
ANTAGE 400 settings when using the K930-2 TIG Module with
V
an Amptrol or Arc Start Switch:
• Set the MODE Switch to the TOUCH START TIG setting.
• Set the "IDLER" Switch to the "AUTO" position.
• Set the "WELDING TERMINALS" switch to the "REMOTELY CONTROLLED" position. This will keep the "Solid State" contactor open
and provide a "cold" electrode until the Amptrol or Arc Start Switch
is pressed.
When in the TOUCH START TIG mode and when a Amptrol is
connected to the 6-Pin connector the OUTPUT CONTROL dial is
used to set the maximum current range of the current control of
the Amptrol.
When using the TIG Module, the OUTPUT CONTROL on the VANTAGE
400 is used to set the maximum range of the CURRENT CONTROL on
the TIG Module or an Amptrol if connected to the TIG Module.
NOTE: The TIG process is to receive a low voltage welding process.
There is no difference in operation with the VRD “On” or “Off” for
The ARC CONTROL is not active in the TIG mode. To STOP a
this mode. For indicator light operation, see table B.1.
weld, simply pull the TIG torch away from the work.
When the arc voltage reaches approximately 30 Volts the arc will
go out and the machine will reset the current to the Touch Start
level.
To reinitiate the arc, retouch the tungsten to the work and lift.
Alternatively, the weld can be stopped by releasing the Amptrol
or arc start switch.
WIRE WELDING-CV
Connect a wire feeder to the VANTAGE 400 according to the instructions
in INSTALLATION INSTRUCTIONS Section.
The VANTAGE 400 in the CV-WIRE mode, permits it to be used with a
broad range of flux cored wire (Innershield and Outershield) electrodes
and solid wires for MIG welding (gas metal arc welding). Welding can be
(1) When used with argon gas. The current ranges shown must be reduced when using argon/helium or pure helium shielding gases.
(2) Tungsten electrodes are classified as follows by the American Welding Society (AWS):
PureEWP
1% ThoriatedEWTh-1
2% ThoriatedEWTh-2
Though not yet recognized by the AWS, Ceriated Tungsten is now widely accepted as a substitute for 2% Thoriated Tungsten in AC and DC applications.
(3) DCEP is not commonly used in these sizes.
(4) TIG torch nozzle "sizes" are in multiples of 1/16ths of an inch:
(5) TIG torch nozzles are typically made from alumina ceramic. Special applications may require lava nozzles, which are less prone to breakage, but cannot withstand high temperatures and high duty cycles.
finely tuned using the ARC CONTROL. Turning the ARC CONTROL clockwise from –10 (soft) to +10 (crisp) changes the arc from soft and
washed-in to crisp and narrow. It acts as an inductance/pinch control.
The proper setting depends on the procedure and operator preference.
Start with the dial set at 0.
NOTE: In the CV-Mode with VRD “On”, the OCV(Open Circuit Voltage) is
not reduced. For indicator light operation, see table B.1.
ARC GOUGING
The VANTAGE 400 can be used for arc gouging. For optimal performance, set the MODE switch to
et the OUTPUT CONTROL knob to adjust output current to the desired
S
level for the gouging electrode being used according to the ratings in
the following Table B.4.
The ARC CONTROL is not active in the ARC GOUGING Mode. The
ARC CONTROL is automatically set to maximum when the ARC
GOUGING mode is selected which provides the best ARC GOUGING performance.
NOTE: With the VRD switch in the “ON” position there is no output in the Arc Gouging Mode. For indicator light operation, see
Table B.1.
ARC GOUGING.
TABLE B.4
Current Range (DC, electrode
positive)
Weld
Amps
0
100
200
300
400
500
PLUS
AUXILIARY POWER:
Start the engine and set the IDLER control switch to the desired
operating mode. Full power is available regardless of the welding
control settings providing no welding current is being drawn.
Simultaneous Welding and Auxiliary Power Loads
The a uxi liary power r ati ngs are wi th no weld ing l oad .
Simultaneous welding and power loads are specified in the following Table B.5.