U.S. Fax: (888) 790-8193 • Int’l Fax: (260) 436-0735
Technical Service Hot Line
(800) 678-9511
www.lincolnfp.com
1100advexport REV 1/5/07
SEQUENCE OF OPERATIONS
(For serial numbers before 2038616 w/ analog control)
MODEL 1154-000-EA NAT. GAS 230 VAC 50 HZ. 1 PHASE
MODEL 1155-000-EA LP GAS 230 VAC 50 HZ. 1 PHASE
POWER SUPPLY
Electrical power to be supplied to the oven by a three conductor service.
CONTROL BOX AUTO COOL DOWN
When the temperature in the control box reaches 120° F, ± 3° (48.9°C, ± 1.7°C), the cooling fan thermostat will
switch power to the control box cooling fan. The thermostat will interrupt power to the cooling fan when the control
box temperature falls to 100° F, ± 3° (37.8°C, ± 1.7°C).
MAIN FAN CIRCUIT
Power is permanently supplied through the 10A oven fuse, through the normally closed control box hi-limit
thermostat (opens at 140° F, 60° C) to the normally open double pole oven fan switch and to the cooling fan.
Closing the oven fan switch supplies line voltage to the main fan motor. Closing the fan switch also supplies
voltage to the cooling fan. The conveyor, burner and temperature display are also energized.
BURNER CIRCUIT
Closing the oven fan switch supplies line voltage through the normally open gas pressure switch (located in the
gas valve and closed when gas pressure is present), through the normally open air pressure switch (closed by air
pressure from the main fan), through the normally closed oven cavity hi-limit thermostat (opens at 662° F, 350°C
which is manually resettable after a drop in temperature of 18° F, 10° C), and to the ignition control.
IGNITION CONTROL
The ignition control switches line voltage to the combustion blower motor, the combustion air switch switches from
normally closed to normally open upon sensing air pressure in the burner housing. After a pre-purge period of
between 30 and 60 seconds, the spark generator is energized, the main gas valve and the burner pilot light are
energized, and ignition should now occur.
TEMPERATURE CONTROL
Closing the oven fan switch supplies line voltage to the temperature control. The 1K ohm temperature pot. is
adjusted to desired temperature. The thermocouple will provide varying millivolts to the temperature control. The
temperature control supplies line voltage to the temperature regulation valve at intermittent intervals to maintain
desired temperature. The heat lamp is energized with the temperature regulation valve.
CONVEYOR DRIVE
Closing the oven fan switch supplies line voltage to the motor control board. AC volts are converted to DC volts
and are supplied to the conveyor motor at terminals A+ and A-. Adjustment of the speed control potentiometer will
change resistance at terminals P1 and P2, varying the DC voltage to the motor. The speed of the conveyor motor
will increase or decrease as the DC voltage from the board increase or decreases respectively.
NOTE: The conveyor control uses a sensor and magnet, mounted on the conveyor motor, that senses the motor
speed. Any change in motor load (± RPM) is detected by the sensor and the voltage to the motor is adjusted
accordingly.
TEMPERATURE DISPLAY
Closing the switch supplies line voltage to primary of the temperature display transformer. The secondary of this
transformer supplies 12VAC to the temperature display. The thermocouple supplies DC millivolts to the
temperature display. The display converts this millivolt reading to a temperature reading.
2
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l
SEQUENCE OF OPERATIONS
MODEL 1164-000-EA 400/230 VAC 50 HZ. 3 PHASE
POWER SUPPLY
Electrical power to be supplied to the oven by a four conductor service.
Brown conductor is Hot.
Black conductor is Hot.
Black conductor is Hot.
Green conductor is ground.
CONTROL BOX AUTO COOL DOWN
When the temperature in the control box reaches 120° F, ± 3° (48.9°C, ± 1.7°C), the cooling fan thermostat will
switch power to the control box cooling fan. The thermostat will interrupt power to the cooling fan when the control
box temperature falls to 100° F, ± 3° (37.8°C, ± 1.7°C).
MAIN FAN CIRCUIT
Power is permanently supplied through the normally closed oven cavity hi-limit, through the 10A fuse, through the
normally closed control box hi-limit thermostat, to the normally open main fan switch. Power is also supplied to the
normally open cooling fan thermostat. Closing the main fan switch supplies 230 VAC to the main fan motor, the
cooling fan motor, to the primary of the temperature display transformer and to the heat and conveyor circuits.
HEAT CIRCUIT
Closing the oven fan switch supplies 230VAC, through the normally open air pressure switch (closed by air
pressure from the main fan) to the electronic temperature control. The 1K ohm temperature potentiometer is
adjusted to desired temperature. The thermocouple will provide varying millivolts to the temperature control. The
temperature control then supplies 230 VAC to the coil of the contactor at intermittent intervals to maintain the
desired temperature. The heat lamp is energized with the contactor.
CONVEYOR DRIVE
Closing the oven fan switch supplies 230 VAC through the EMI filter to the motor control board. AC volts are
converted to DC volts and are supplied to the conveyor motor at terminals A+ and A-. Adjustment of the speed
control potentiometer will change resistance at terminals P1 and P2 varying the DC voltage to the motor. The
speed of the conveyor motor will increase or decrease as the DC voltage from the board increases or decreases
respectively.
NOTE: The conveyor control uses a sensor and magnet, mounted on the conveyor motor, that senses the motor
speed. Any change in motor load (± RPM) is detected by the sensor and the voltage to the motor is adjusted
accordingly.
TEMPERATURE DISPLAY
Closing the main fan switch supplies 230 VAC to the primary of the temperature display transformer. The
secondary of this transformer supplies 12 VAC to the temperature display. The thermocouple supplies DC
millivolts to the temperature display. The display converts this millivolt reading to a temperature reading.
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l
3
SCHEMATIC DIAGRAM
MODEL 1154-000-EA, 1155-000-EA
4
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l
SCHEMATIC DIAGRAM
MODEL 1164-000-EA
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l
5
TROUBLESHOOTING GUIDE
GAS OVENS
1154-000-EA NAT. GAS 230VAC 50 HZ. 1 PHASE
1155-000-EA LP GAS 230VAC 50 HZ. 1 PHASE
REFER TO PROPER SCHEMATIC FOR IDENTIFIED COMPONENTS
SYMPTOM POSSIBLE CAUSE EVALUATION
Oven fan will not run
No control box cooling
No automatic control box
cooling
Oven will not heat
Incoming power supply Check breakers, reset if required. Check power
plug to be sure it is firmly in receptacle.
Measure incoming power, call power co. if
needed
Fuse, 10A Check, replace if necessary.
Fuse holder Check, replace if necessary.
Hi-limit thermostat, control
box
Main fan switch With power off, Check continuity between
Main fan motor Check for opens, shorts or grounds. With
Capacitor Check for shorts or grounds.
Incoming power supply Check main circuit breakers, reset if required.
Main fan switch With power off, Check continuity between
Cooling fan Line voltage should now be at the cooling fan.
Incoming power supply Check main circuit breakers, reset if required.
Cooling fan thermostat Check the cooling fan thermostat (thermostat
Gas supply Check for adequate gas supply and be sure
Main fan If not operating, refer to “Main fan will not run”
Gas pressure switch This switch is located inside the gas valve and
Check for voltage on both sides of the switch.
Terminals are normally closed. If open, reset
and test oven for proper operation. If
thermostat will not hold, and control box
temperature is not exceeding 140° F (60° C)
replace thermostat.
switch terminals. Replace as needed.
power off, turn fan blade to check for locked
rotor.
WARNING: Capacitor has a stored charge,
discharge before testing.
Call power co. if needed.
switch terminals. Replace as needed.
If voltage is present, check motor for shorts or
opens. With power off, check for locked rotor.
Call power co. if needed.
closes at 120° F and opens at 100° F). With the
cooling fan thermostat preheated, check for
continuity. If switch is open, replace thermostat.
that manual gas shut off valve is open. Also
check flexible gas line connection.
should close when gas pressure is present.
WITH POWER OFF: Remove 3 prong plug (on
gas valve) and measure continuity between
terminals 2 and 3. If no continuity, check the
following: Proper gas pressure supply to gas
valve as marked on the oven specification
plate. Check for proper adjustment of gas
pressure switch, 10 for Nat. gas, 27 for LP gas
or 4.5 for town gas. Check the filter in gas
valve for blockage or damage. If above checks
are okay, but pressure switch is still not closed,
replace gas valve.
6
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l
Air pressure switch Check air switch terminals for supply voltage to
terminals NO 2 and COM. If voltage is present
on one side only, check for air tube blockage or
misalignment. If these are okay, adjust switch
or replace if necessary.
Oven cavity hi-limit
thermostat
Terminals are normally closed, opens at 660° F
(350° C). If open, push in reset button and
retest. If thermostat will not hold for maximum
oven temperature, and oven is not exceeding
temperature dial setting, check for proper
location of capillary bulb in its spring holder. If
above checks are okay, replace hi-limit
thermostat.
Ignition control Check for proper supply voltage to ignition
control. Check for proper line voltage to the
burner blower motor. This can be checked at
motor connecting plug terminals 2 and 5. If
voltage is present, proceed with next step, if
not, wait 30 seconds, push reset button and try
to restart. If this fails, check wires from
thermostat and burner blower motor to the
ignition control. If all above checks okay,
replace ignition control.
Burner blower motor Check for supply voltage to motor. WITH
POWER OFF: Turn blower wheel to check for
locked rotor. If proper supply voltage is present
at motor connecting plug, terminals 2 and 5,
and motor does not run, replace motor.
Air pressure switch
(burner blower)
Check for proper supply voltage switching from
“NC” to “NO” on ignition control. Check for air
switch adjustment, air tube blockage or
misalignment. If these fail, replace air pressure
switch.
Spark generator A pre-purge time of 30 to 60 seconds occurs
after blower motor starts. Check for supply
voltage at spark generator. If voltage is not
present, check reset button for the ignition
control. If voltage is still not present, replace
ignition control. If there is input voltage but
there is no output voltage, replace spark
generator.
Igniter/sensor assembly Check this assembly for visible damage.
Replace as needed. If there is no visible
damage, check for supply voltage to
igniter/sensor assembly. If there is supply
voltage to igniter/sensor assembly, but there is
no spark, replace igniter/sensor assembly.
Gas valve Gas valve should open when proper supply
voltage is present. If no voltage is present,
check the reset button on ignition control, and
all connections for tightness. If there is still no
voltage at gas valve, replace the ignition
control. If there is voltage present, check for
gas pressure at the gas pressure tap (located
in the gas piping just prior to the burner). If
there is no gas pressure, replace the gas valve.
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l
7
Flame will not stay on
Flame sensor To check for flame sensor operation, connect a
Power supply Turn the temperature to the lowest temperature
Ignition control If there is sufficient flame sensor current, but
NOTE: Flame should be lit at
this time
Low flame is on, but no main
Temperature control Check for supply voltage at terminal #7 to L2
flame
Thermocouple With power on and thermocouple leads
Temperature potentiometer Disconnect the potentiometer leads from the
Temperature regulation valve If supply voltage is present on the temperature
Intermittent heating Thermal overload of main fan
and burner blower motors
8
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l
digital multimeter (capable of measuring DC
microamps) between the flame sensor wire and
terminal #1 on the ignition control. Sensor
current is to be 3 microamps, minimum. If
these readings are not achieved, replace
igniter sensor assembly. Also, check for any
type of damage to flame sensor wire and
connections. NOTE: The DC microamp test
must be conducted with the oven in low flame
(bypass) operation.
setting. If there is sufficient microamp current,
but the flame will not stay lit, check for proper
polarity of the power supply.
the burner will not remain ignited, check the
reset button on ignition control. If all above test
okay, replace ignition control.
on temperature control. If there is no voltage,
trace wiring back to oven fan switch. Turn the
temperature adjustment knob to maximum
temperature position and check for supply
voltage at the load terminal #8 and L2. If
voltage is present and unit is not heating, refer
to “Temperature regulation valve” for next
check. If voltage is not present, proceed.
attached to the temperature control board:
Measure the DC millivolt output of these leads.
Refer to thermocouple chart in “removal and
installation” section for proper readings. If
these readings are not achieved, replace
thermocouple.
temperature control board. Place ohmmeter
test leads on the blue and green pot. leads.
Reading should be 1K ohms. Place meter
leads on the blue and purple pot. leads and
rotate knob from high to low. Repeat on green
and purple leads. Check for an even rise and
fall of ohms reading to insure that there are no
open or dead spots in the potentiometer.
Check each lead to ground for any short
circuits to ground. Replace as needed.
control board at load terminals #8 and L2,
check for voltage at temperature regulation
valve. If voltage is present, listen for valve to
open and close. Also check for opens or shorts
in the operating coil. Replace as needed.
The main fan motor and burner blower motor
are equipped with internal thermal protection
and will cease to operate if overheating occurs.
As these motors overheat and then cool, the
burners will cycle on and off intermittently.
Improper ventilation or a lack of preventive
maintenance may cause this condition. Also,
most of the problems listed under “Oven will
not heat” can cause intermittent failure.
Conveyor will not run
Power supply Check incoming power supply, If no voltage is
present, check circuit breakers.
Fan switch With power off, Check continuity between
switch terminals. Replace as needed.
Speed adjustment
potentiometer
This is a 0 to 10K ohm, 1 turn potentiometer.
With power off, remove the black and white
pot. leads from the motor control board at
terminals P1 and P2. Place the meter leads on
the black and white pot. leads. Rotating the
pot. slowly, from low to high, the meter reading
should show an even transition from 0 to 10K
ohms ± 5%. There should be no dead or open
spots throughout the rotation of the
potentiometer. Check both pot. leads to
ground. There should be no continuity to
ground. If any of the above checks fail, replace
the potentiometer.
DC motor control board Check for supply voltage input to the control
board at terminals L1 and L2. If voltage is not
present, check wiring back to the oven fan
switch. If supply voltage is present, check both
fuses on control board (8A line and 1A
armature). Check the DC voltage output at
terminals A+ and A-. If there is power in to the
control board but no power at A+ and A-, check
the following:
Hall effect sensor Disconnect the Hall effect sensor from the DC
motor control board. If the motor begins to run,
replace the Hall effect sensor.
DC motor control board If, after disconnecting the Hall effect sensor,
the motor is still not running, check for DC
voltage from terminals A+ and A-. If there is no
DC voltage, replace the DC motor control
board.
Circuit breaker If there is DC voltage output from the DC motor
control board, but the motor is still not running,
check the 0.4 Amp circuit breaker. Disconnect
wires from the circuit breaker and check for
continuity through the circuit breaker. Reset
circuit breaker or replace as needed.
Conveyor gearmotor Check the leads to the motor for evidence of
any shorts or opens, and each lead to ground.
If the motor fails the above tests, replace
motor. Rotate motor shaft to determine if there
is a locked rotor or a locked gearbox (use care
so that magnet and sensor are not damaged).
Check motor brushes for damage or excessive
wear, replace brushes if needed. Replace
motor if needed. Also check to be sure that the
conveyor drive coupling is tight and properly
engaged to the conveyor shaft.
Conveyor Check for any mechanical misalignment. Also,
check for worn bearings. A conveyor belt that is
too tight may cause excessive bearing wear
and sometimes, irregular speed.
Conveyor speed unsteady Power supply Check power supply at the DC motor control
board for supply voltage at terminals L1 and
L2. Supply voltage should be steady.
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l
9
Temperature display
inoperative
Temperature display
inaccurate, or erratic
10
Speed adjustment
potentiometer
This is a 0 to 10K ohm, 1 turn potentiometer.
With power off, remove the black and white
pot. leads from the motor control board at
terminals P1 and P2. Place the meter leads on
the black and white pot. leads. Rotating the
pot. slowly, from low to high, the meter reading
should show an even transition from 0 to 10K
ohms ± 5%. There should be no dead or open
spots throughout the rotation of the
potentiometer. Check both pot. leads to
ground. There should be no continuity to
ground. If any of the above checks fail, replace
the potentiometer.
Magnet Check to insure that the magnet (cemented to
shaft of conveyor drive motor) has not been
damaged, or come loose from the motor shaft.
Re-glue or replace as needed.
Hall effect sensor Check for any physical damage to hall effect
sensor (mounted on conveyor drive motor).
Check all wiring and connections for damage.
Replace as needed.
Hall effect sensor cable Check continuity through the wires in the cable.
Check all wiring and connections for visible
damage. Replace as needed.
DC motor control board With motor running, measure DC voltage
across the red wire and black wire in the hall
effect cable (all wires must be connected
during this test). Voltage reading should be
approx. 12VDC and steady. If this reading is
not achieved, replace DC motor control board.
Hall effect sensor With the motor running at maximum speed,
measure the frequency across the white wire
and the black wire in the hall effect cable (all
wires must be connected during this test).
Reading should be approx. 327 Hz. And
steady. If there is no reading, replace hall effect
sensor. If the reading is unsteady, calibrate the
DC motor control board.
Display transformer Measure the transformer primary for supply
voltage input. If voltage is not present, trace
wiring back to the oven fan switch. Measure
the secondary output, which will normally be
12-15VAC. Voltage across terminals 1-3
should be 12-15VAC. Terminals 1-2 and 2-3
should be ½ the voltage reading 1-3. If the
above secondary readings are not achieved,
replace transformer.
Temperature display If proper voltage is present at terminals 1,2 and
3 on temperature display, but the display is not
lighted, recheck all connections for tightness. If
temperature display is still not operating,
replace the temperature display.
Thermocouple Place the thermocouple of a pyrometer into the
center of the top finger. The pyrometer will
indicate oven temperature. Measure DC
millivolts of thermocouple at the temperature
display. See thermocouple chart in “Removal
and Installation” section for proper readings.
Replace thermocouple if proper readings are
not achieved. If readings are correct on the
thermocouple, recalibrate or replace
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l
temperature display.
TROUBLESHOOTING GUIDE
ELECTRIC OVENS
MODEL 1164-000-EA 400/230 VAC 50 HZ. 3 PHASE
REFER TO PROPER SCHEMATIC FOR IDENTIFIED COMPONENTS
SYMPTOM POSSIBLE CAUSE EVALUATION
Oven fan will not run
No control box cooling
No automatic control box
cooling
Control box cooling fan
continues to run
Incoming power supply Check circuit breakers. Reset if required. Call
power company if needed.
Oven cavity hi-limit
thermostat
Fuse, 10 Amp Check, replace if necessary.
Fuse holder Check, replace if necessary.
Control box hi-limit thermostat Check for voltage on both sides of the switch.
Main fan switch With power off, Check continuity between
Main fan motor Check for opens, shorts or grounds. With
Capacitor Check for shorts or grounds.
Check for main fan operation. If not operating,
Cooling fan Line voltage should now be at the cooling fan.
Incoming power supply Check circuit breakers. Reset if required. Call
Oven cavity hi-limit
thermostat
Cooling fan thermostat Check the cooling fan thermostat (thermostat
Cooling fan Line voltage should now be at the cooling fan.
Cooling fan thermostat This normally open thermostat should close at
Terminals are normally closed. If open, reset
and test oven for proper operation. If
thermostat will not hold for maximum oven
temperature, and oven is not exceeding
temperature dial setting, check for proper
location of capillary bulb in its spring holder. If
above checks okay, replace hi-limit thermostat.
Terminals are normally closed. If open, reset
and test oven for proper operation. If
thermostat will not hold, and control box
temperature is not exceeding 140° F (60° C)
replace thermostat.
switch terminals. Replace as needed.
power off, turn fan blade to check for locked
rotor.
WARNING: Capacitor has a stored charge,
discharge before testing.
refer to “Oven fan will not run”.
If voltage is present, check motor for shorts or
opens. With power off, check for locked rotor.
power company if needed.
Terminals are normally closed. If open, reset
and test oven for proper operation. If
thermostat will not hold for maximum oven
temperature, and oven is not exceeding
temperature dial setting, check for proper
location of capillary bulb in its spring holder. If
above checks okay, replace hi-limit thermostat.
closes at 120° F and opens at 100° F). With the
cooling fan thermostat preheated, check for
continuity. If switch is open, replace thermostat.
If voltage is present, check motor for shorts or
opens. With power off, check for locked rotor.
120°F (48.9°C) and reopen at 100°F (37.8°C).
Replace as needed.
Impinger II – 1100-000-A Series (SN 2038615 & Below) Service Manual –Int’l
11
Loading...
+ 25 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.