Lincoln 1633-000-EA Service Manual

SERVICE MANUAL
(INTERNATIONAL)
IMPINGER CONVEYOR OVENS
LOW PROFILE 1600 INTERNATIONAL ADVANTAGE
Lincoln Foodservice Products, LLC
1111 North Hadley Road
Fort Wayne, Indiana 46804
United States of America
Phone: (800) 374-3004
U.S. Fax: (888) 790-8193 • Int’l Fax: (260) 436-0735
Technical Service Hot Line
(800) 678-9511
www.lincolnfp.com
1600expadv REV: 1/8/07
SERVICE AND PARTS MANUAL
1600 INTERNATIONAL ADVANTAGE
SEQUENCE OF OPERATIONS ..............................................................................................3
SCHEMATIC............................................................................................................................ 5
TROUBLESHOOTING GUIDE ................................................................................................ 6
REMOVAL, INSTALLATION & ADJUSTMENTS................................................................. 12
GENERAL PARTS................................................................................................................. 20
ADVANTAGE SERIES..........................................................................................................20
CONTROL BOX, RIGHT PARTS...........................................................................................22
CONTROL BOX, LEFT PARTS............................................................................................. 24
OVEN BACK PARTS .............................................................................................................26
CONVEYOR PARTS ............................................................................................................. 28
2
Low Profile – 1600 Advantage Series Service Manual – International
SEQUENCE OF OPERATIONS
MODEL 1633-000-EA 230 VAC 50HZ NATURAL GAS MODEL 1634-000-EA 230 VAC 50HZ L.P. GAS
POWER SUPPLY Electrical power to be supplied to the oven by a three conductor service.
Brown conductor is hot Blue conductor is neutral. Green conductor is ground.
CONTROL BOX AUTO COOL DOWN
When the temperature in either one of the control boxes reaches 120°F ±3° (49°C ± 1.7° ) , the cooling fan thermostats will switch power to the cooling fans . The thermostats will interrupt power to the cooling fans when the temperature falls to 100°F ± 3° (37°C ± 1.7° )
MAIN FAN CIRCUIT
Line voltage is permanently supplied to a normally open contact of the oven power switch. Line voltage is permanently supplied to the two normally open cooling fan thermostats, a normally open contact of the oven power relay. Closing the oven power switch supplies line voltage to oven power relay, its contacts now close, supplying line voltage to the two main fan motors and the two burner circuits. Closing the oven power switch also supplies line voltage to the control box cooling fans, the temp. display, and the conveyor circuit.
BURNER CIRCUIT
NOTE: This oven utilizes two complete burner/ temperature control systems. The sequence of operations is the same for each system. Closing the main fan switch supplies line voltage, through the oven power relay, through a three amp. fuse, through the gas pressure switch, through the main fan air pressure switch through the oven cavity hi-limit thermostat, to the ignition control. The combustion motor is energized. The normally open combustion air switch closes upon sensing air pressure. After a pre-purge period of between 30 and 60 seconds, the ignition transformer and the main gas valve are energized. Ignition should now occur.
TEMPERATURE CONTROL
Closing the oven power switch supplies line voltage, through the oven power relay, through a three amp. fuse, through the gas pressure switch, through the main fan air pressure switch through the oven cavity hi-limit thermostat, to the temperature control board. The 1.0K temperature pot. is adjusted to desired temperature. The thermocouple will provide varying millivolts to the temperature control. The temperature control supplies line voltage to the solenoid valve at intermittent intervals to maintain desired temperature.
CONVEYOR DRIVE
Closing the oven power switch supplies line voltage, through the oven power relay, through the electromagnetic filter to the conveyor control. AC volts are converted to DC volts and are supplied to the conveyor motor at terminals A+ and A-.
Low Profile – 1600 Advantage Series Service Manual – International
3
Adjustments of the speed control potentiometer will change resistance at terminals P1 and P2 varying the DC voltage to the motor. The speed of the conveyor motor will increase or decrease as the DC voltage from the board increases or decreases respectively.
NOTE: The conveyor control uses a sensor and magnet, mounted on the conveyor motor that senses motor speed. Any change in motor load ( ± RPM ) is detected by the sensor and the voltage to the motor is adjusted accordingly.
TEMPERATURE DISPLAY
Closing the power switch supplies line voltage to the primary of the temperature display transformer. The secondary of this transformer supplies 12 VAC to the temperature display. The thermocouple supplies DC millivolts to the temperature display. The display converts this millivolt reading to a temperature reading.
4
Low Profile – 1600 Advantage Series Service Manual – International
SCHEMATIC MODELS 1633-000-EA AND 1634-000-EA
Low Profile – 1600 Advantage Series Service Manual – International
5
TROUBLESHOOTING GUIDE
MODEL 1633-000 EA NATURAL GAS 230 VAC 50 HZ 1 PHASE MODEL 1634-000-EA L.P. GAS 230 VAC 50 HZ 1 PHASE
NOTE: When checking components on left side of unit, be sure to check for proper connections in power connector, ( marked P. C. on schematic diagram ) located inside motor cover.
SYMPTOM POSSIBLE CAUSE EVALUATION
Oven fan will Incoming power supply Check breakers/ reset if required not run call Power company if needed Oven fan switch Check continuity between switch terminals. Thermostat, hi-limit Terminals are normally closed, if open, reset thermostat and test oven for proper operation. If it will not reset, replace thermostat. Fan fuse Check, replace if necessary. Fuse holder Check, replace if necessary. Oven fan relay Check for power to coil of oven fan relay. If no voltage is present, trace wiring back to hi-limit thermostat. Check for supply voltage at terminal #6 of the relay. If no voltage is present, trace wiring back to fuse holder. If voltage is present, at the relay coil, check to insure the contacts are closing. Capacitor(s) Check for opens, shorts, or grounds. Motor (s) Check for opens, shorts, or grounds. No control box cooling Fan switch (SEE OVEN Hi-limit FAN WILL Oven fan relay NOT RUN.) Cooling fan(s) Supply voltage should now be at these motors. If voltage is present, check motor for open, shorts, or grounds. WITH POWER OFF: check for locked rotor. No automatic control Incoming power supply Check circuit breakers, reset if needed. box cooling Call power company if needed. Cooling fan thermostats Thermostat closes at 120°F and opens at 100°F. With the cooling fan thermostat preheated, check for continuity. If switch is open, replace. Cooling fan(s) Supply voltage should now be at these motors. If voltage is present, check motor for opens, shorts or grounds. WITH POWER OFF: Check for locked rotor.
Oven will not heat Gas supply Check for adequate gas supply to oven. Manual gas shut off valve Check to see that the manual gas shut off valve is open. Fan switch Check to see that the fan switch is on. Main oven fan Check if main oven fan is operating. if not, refer to “oven fan will not run”. NOTE: These ovens utilize 2 complete Burner/Temperature control systems. Each system will Follow the same troubleshooting sequence. Fuse, burner 3A. Check, replace if necessary.
6
Low Profile – 1600 Advantage Series Service Manual – International
Fuse holder Check, replace if necessary. Gas pressure switch Check for supply voltage to neutral (internal to gas valve) on both sides of switch. If voltage is present on one side of switch only, check the following. Check for proper gas pressure supply to gas valve.(Marked on oven spec. plate.) Check for proper adjustment of gas pressure switch. should be set at 10 Nat., 27 for L.P. or 4.5 for town gas. Check gas filter in gas valve for blockage or damage. (See Adjustment section for location.) If the above checks OK, but switch is still not closed replace gas valve. Oven air pressure switch Check for supply voltage on both sides of switch. If voltage is present on one side only, check for air tube blockage. Adjust air pressure switch. If the above
fails, replace air pressure switch. Hi-limit thermostat Terminals are normally closed. If open, reset and test oven for proper operation. If thermostat will not hold for maximum oven temperature, and oven is not exceeding maximum temperature dial setting, check for proper location of capillary bulb in its spring holder. If above checks OK, replace hi-limit. Ignition control Check for supply voltage to ignition control at terminal #1 and neutral. If voltage is not present, trace wiring back to hi-limit thermostat. Check for supply voltage at terminal #6 to neutral. If no voltage is present, wait 30 seconds and check reset button. If above fails, replace ignition control. Burner reset switch Switch is normally open. Check to see that the switch closes when reset button is pushed. Replace as needed. Burner blower motor Check for supply voltage to burner blower motor. WITH POWER OFF: Turn blower wheel to check for locked rotor. If supply voltage is present and motor does not run, replace motor. Burner blower motor Check for supply voltage switching to Air pressure switch terminal N. O. as the air pressure switch closes. Check for air tube blockage or misalignment, adjust air pressure switch. If the above fails, replace air pressure switch. Spark generator After a pre-purge time of 30 to 60 seconds after blower motor starts, check for supply voltage to spark generator. If voltage is not present, Check reset button located on rear of control box. If voltage is still not present, replace ignition control. If voltage is present, visually check for spark at igniter head. Igniter/sensor assembly Check for visible damage to igniter/ sensor assembly. If there is no visible damage to the components, and no spark,
Low Profile – 1600 Advantage Series Service Manual – International
7
replace the spark generator. If there is visible damage to the igniter/sensor assembly, replace. Also check for frayed or damaged wires in burner tube. Gas valve Check for supply voltage to gas valve. If there is no voltage present, check reset button, check all connections for tightness. If there still is no voltage at gas valve, replace ignition control. If there is voltage present, check for gas pressure at gas pressure tap located in gas piping at burner manifold. If there is no gas pressure, replace gas valve. Flame will not stay on Flame sensor To check for flame sensor operation, connect a digital multimeter (capable of measuring D.C. micro amps) in series with the flame sensor wire and ignition control. Sensor current is 3 micro amps D.C. minimum. NOTE: The D.C. micro amp test must be conducted with the oven in low flame (bypass) operation. Turn the temperature control to its lowest setting. If these readings are not achieved, replace igniter/sensor assy. Also, check for any type of damage to flame sensor wire and connections. Ignition control If there is sufficient flame sensor current, but the burner will not remain ignited, check the reset button on ignition control. NOTE: Check for proper polarity of the power supply. If all of the above are OK, replace ignition control. Pilot lamp is on, Temperature control Check for supply voltage across But no main flame terminals L2 and 240 on temperature control board. If no voltage is present, check wiring back to hi-limit thermostat. Turn the temperature adjustment knob to the maximum temperature position and check for supply voltage at the load terminal #7 and #8. If voltage is present and unit is not heating, refer to “temperature regulation valve” for next check. If voltage is not present, proceed. Thermocouple probe With power on and thermocouple leads attached to board, measure the millivolt out put of the thermocouple. Refer to the thermocouple chart in section D for proper readings. Temperature control WITH POWER OFF: Remove the Potentiometer potentiometer leads from the temperature control board. Place ohm meter test leads on the blue and green pot leads. Reading should be 1 K ohms. Place meter leads across the blue and purple pot leads and rotate knob from high to low. Repeat on green and purple leads. Check for even rise and fall of ohms reading to insure that there are no open or dead spots in the potentiometer. Check each lead to ground for shorts. Replace potentiometer
8
Low Profile – 1600 Advantage Series Service Manual – International
as needed. Temperature regulation If supply voltage is present on the valve temperature control board at the load terminals #7 and #8, check for voltage at temperature regulation valve. If voltage is present, listen for valve to open and close. Also, check for opens or shorts in the coil. Replace if required. Intermittent heating Thermal overload of The main fan motors and the burner main fan and burner blower motors are equipped with blower motors internal thermal protection and will cease to operate if overheating occurs. As the motors overheat and then cool, this will cause the units to cycle on and off intermittently. This may be caused by improper ventilation or lack of preventive maintenance. Also, most of the problems listed under “Oven will not heat” can cause intermittent failure. Conveyor will not run Power supply Check for supply voltage at terminals L1 and L2. If voltage is not present, check breakers. Fan switch See procedure for checking on page 6. Fuse, 10 Amp. Check and/or replace. Fuse holder Check and/or replace. Filter E.M.I. Check for supply voltage input to filter. If there is no voltage, trace wiring back to relay. If there is input voltage, check for output voltage. If there is input voltage but no output voltage, replace filter.
Speed adjustment This is a 0 to 10K ohm, 1 turn potentiometer potentiometer. With power off, remove the black and white pot leads from the conveyor control board at terminals P1 and P2. Place the meter leads on black lead (P2) and the white lead (P1). Rotating the pot. slowly, from low to high, the meter reading should show an even transition from 0 to 10K ohms ± 5%. There should be no dead or open spots through the one turn of the pot. Check both leads to ground. There should be no continuity to ground. If any of the above fail, replace the potentiometer. D.C. motor Check for supply voltage input to control board the control board at terminals L1 and L2 If not present, check wiring back to the filter. If supply voltage is present, check both fuses on the control board ( 8 Amp. line and 1Amp. armature). Check the D.C. voltage output at terminals A+ and A-. If A.C. voltage is at terminals L1 and L2, and no D.C. voltage is present at A+ and A-,
replace control board. If A.C. voltage is present and D.C. voltage is present but the motor will not run, check gear motor as follows:
Conveyor If D.C. voltage is present at A+ and A-
Low Profile – 1600 Advantage Series Service Manual – International
9
gear motor and the motor does not run, first check the mini breaker and then the conveyor. Refer to the next possible cause. Check the leads to the motor for evidence of any shorts or opens , and each lead to ground. Check motor brushes . From the top of the motor, rotate motor shaft to determine if there is a locked rotor or a locked gearbox (use care so magnet and Hall Effect sensor board are not damaged). Replace motor as needed. Conveyor Check for any mechanical misalignment. Also, check for worn bearings. A conveyor belt that is over tightened will cause excessive bearing wear and sometimes, irregular speed. Conveyor speed varying Power supply Check power supply at the D.C. control or intermittent board for supply voltage at board terminals L1 and L2. Motor control board Place the test meter probes on terminals A+ and A-. (with speed potentiometer set to maximum speed – approximately 2 min.). The meter reading should be approximately 100VDC(±3%), if voltage is not steady within limits, then the board is usually bad. Always check the speed potentiometer, be sure it is OK before changing a control board. This test is not always 100% accurate as this test is not performed at operating speeds, However, this test is the best method currently available. D.C. Gearmotor If the D.C. control board is steady, then the problem may be the motor or gearbox. Check the brushes in the motor for excessive arching or unusual wear. Check the motor and gearbox from instructions located on page 9 under “possible cause” listing “conveyor gear motor” Magnet Check to insure that the magnet (cemented to shaft of conveyor drive motor) has not been damaged, or come loose from the motor shaft. Replace as needed. Hall Effect Check for any physical damage to Sensor hall effect sensor (mounted on conveyor drive motor). Check all wiring and connections for tightness and proper location. Replace as needed. Connect new hall effect to system and check for steady operation. Temperature display Display transformer Measure the transformer primary inoperative for supply voltage input. If voltage is not present, trace wiring back to the fan relay. If voltage is present, measure the secondary output of the transformer. Voltage across terminals 1-3 should be 12-15VAC. Terminals 1-2 and 2-3 should be ½ the voltage reading from terminals 1-3. If the above
10
Low Profile – 1600 Advantage Series Service Manual – International
Loading...
+ 22 hidden pages