Lincoln 1204 Service Manual

SERVICE MANUAL
(DOMESTIC)
IMPINGER CONVEYOR OVENS
MODEL SERIES 1000 & 1200
Lincoln Foodservice Products, LLC
1111 North Hadley Road
Fort Wayne, Indiana 46804
Phone : (800) 374-3004
U.S. Fax: (888) 790-8193 • Int’l Fax: (260) 436-0735
Technical Service Hot Line
(800) 678-9511
www.lincolnfp.com
L-371088 REV: 3/27/09
TABLE OF CONTENTS
TABLE OF CONTENTS............................................................................................................................................. 2
SEQUENCE OF OPERATIONS 1000/1001/1004/1005/1200/1201/1204/1205 ....................................................... 3
SEQUENCE OF OPERATIONS 1022 / 1023 / 1202 / 1203...................................................................................... 4
SEQUENCE OF OPERATIONS 1040 / 1041 / 1240 / 1241...................................................................................... 5
SCHEMATIC / 1000, 1001 ........................................................................................................................................ 8
SCHEMATIC / 1004, 1005 ........................................................................................................................................ 9
SCHEMATIC / 1022, 1023 – S/N Q19077 & BELOW ............................................................................................. 10
SCHEMATIC / 1022, 1023 – S/N Q19078 & ABOVE.............................................................................................. 11
SCHEMATIC / 1040, 1041 – S/N Q14279 & BELOW ............................................................................................. 12
SCHEMATIC / 1040, 1041 – S/N Q14280 & ABOVE.............................................................................................. 13
SCHEMATIC / 1200, 1201 ...................................................................................................................................... 14
SCHEMATIC / 1202, 1203 S/N Q14790 & BELOW ................................................................................................ 15
SCHEMATIC / 1202, 1203 S/N Q14791 & ABOVE................................................................................................. 16
SCHEMATIC / 1204, 1205 ...................................................................................................................................... 17
SCHEMATIC / 1240, 1241 – S/N Q14279 & BELOW ............................................................................................. 18
SCHEMATIC / 1240, 1241 – S/N Q14280 & ABOVE.............................................................................................. 19
TROUBLESHOOTING GUIDE 1000 & 1200 .......................................................................................................... 20
GAS OVENS ........................................................................................................................................................ 20
TROUBLESHOOTING GUIDE ................................................................................................................................ 25
ELECTRIC OVENS MODEL SERIES 1000 & 1200............................................................................................ 25
REMOVAL, INSTALLATION & ADJUSTMENTS .................................................................................................... 32
PARTS / MODEL SERIES 1000 & 1200 - GENERAL............................................................................................. 60
BLOW UP / 1000, 1200 – GENERAL...................................................................................................................... 61
PARTS / ACCESS DOOR & 1050 DOOR............................................................................................................... 62
BLOW UP / ACCESS DOOR & 1050 DOOR .......................................................................................................... 63
PARTS / MODEL 1000,1001,1050,1051,1004, &1005 – S/N 100 TO 4389........................................................... 64
BLOW UP / 1000, 1001, 1050, 1051, 1004, & 1005 S/N 100 TO 4389 .................................................................. 65
PARTS / MODEL 1000,1001,1004, AND 1005 S/N 4390 & ABOVE
BLOW UP 1000, 1001, 1004, 1005 S/N 4390 & ABOVE........................................................................................ 67
PARTS / 1022-1023................................................................................................................................................. 68
BLOW UP / 1022, 1023 ........................................................................................................................................... 69
PARTS / 1040-1041................................................................................................................................................. 70
BLOW UP / 1040, 1041 ........................................................................................................................................... 71
PARTS / 1200, 1201, 1204 AND 1205 .................................................................................................................... 72
BLOW UP / 1200, 1201, 1204, 1205....................................................................................................................... 73
PARTS / 1202-1203................................................................................................................................................. 74
BLOW UP / 1202, 1203 ........................................................................................................................................... 75
PARTS / 1240-1241................................................................................................................................................. 76
BLOW UP / 1240, 1241 ........................................................................................................................................... 77
PARTS / OVEN BACK - GAS.................................................................................................................................. 78
BLOW UP / OVEN BACK – GAS ............................................................................................................................ 79
PARTS / OVEN BACK- ELECTRIC......................................................................................................................... 80
BLOW UP / OVEN BACK – ELECTRIC .................................................................................................................. 81
PARTS / CONVEYOR MOTOR ASSEMBLY S/N 4390 & ABOVE ......................................................................... 82
BLOW UP / CONVEYOR MOTOR ASSEMBLY S/N 4390 & ABOVE .................................................................... 83
PARTS / SERIES 1000 – CONVEYOR................................................................................................................... 84
BLOW UP / SERIES 1000 CONVEYOR ................................................................................................................. 85
PARTS / SERIES 1200 - CONVEYOR CONTROL................................................................................................. 86
BLOW UP / SERIES 1200 – CONVEYOR CONTROL ........................................................................................... 87
PARTS / SERIES 1200 – CONVEYOR................................................................................................................... 88
BLOW UP / SERIES 1200 – CONVEYOR .............................................................................................................. 89
......................................................................
66
2
Impinger I -–1000 Series Service Manual - Domestic
SEQUENCE OF OPERATIONS 1000/1001/1004/1005/1200/1201/1204/1205
MODEL 1000 - 120/230 VAC - 60HZ - NATURAL GAS MODEL 1001 - 120/230 VAC - 60HZ - L.P. GAS MODEL 1004 - 120/230 VAC - 60HZ - NATURAL GAS MODEL 1005 - 120/230 VAC - 60HZ - L.P. GAS MODEL 1200 - 120/230 VAC - 60HZ - NATURAL GAS/DUAL BELT MODEL 1201 - 120/230 VAC - 60HZ - L.P. GAS/DUAL BELT MODEL 1204 - 120/230 VAC - 60HZ - NATURAL GAS/DUAL BELT MODEL 1205 - 120/230 VAC - 60HZ L.P.GAS/DUAL BELT
POWER SUPPLY Electrical Power to be supplied to the Oven by a four conductor service. . Voltage
from the black conductor to the white conductor is 120 VAC. Black conductor is Hot Red conductor is Hot White conductor is Dedicated Neutral
Green conductor is Ground CONTROL BOX AUTO COOL DOWN
MAIN FAN CIRCUIT Electrical power is permanently supplied to the normally open contacts of the Double
TRANSFORMER (12.6 VAC)
BURNER CIRCUIT Closing th e Fan Swit ch and the normally open Burner Swit ch su pplies 1 20 VAC
CONVEYOR DRIVE(S/N 100 to 4389)
(S/N 4390 and UP) Closing the fan switch an d the normally open conveyor switch supplies 120 VAC t o
When the te mperature i n the Co ntrol Box rea ches 120°F + 3 °, the Co oling Fan
Thermostat will swit ch power to the Cont rol B ox Cooling Fan. The Thermostat will
interrupt power to the Cooling Fan when the Control Box temperature falls to 100°F +
3°.
Pole Main F an Rel ay, the Cooli ng Fa n Thermo stat, the normall y open Main Fa n
Switch, and the n ormally open Cool Down Thermostat (thermostat closes at 160°F
and opens at 140 °F). Closing the Mai n Fan Switch energizes th e coil of the Relay.
The normally ope n contacts now close, energizing the Mai n Fan Motor thro ugh (2)
10A fuses, and the Coolin g Fan. Closing the Fan S witch also supplies power to the
Hour Meter (hour meter discontinued after S/N 3484), the 12.6 VAC Transformer, the
Burner and Conveyor Switches.
Upon closure of the Fan Switch, 120 VAC is supplied to the primary of the 12.6 VAC
Transformer. The Transformer steps the voltage down to 12.6 VAC (normally 13 to
14 VAC) with a ce nter t ap, and supplies p ower t o the Time/T emp Di splay. The
voltage from each leg of t he Tran sformer's secondary to the cent er tap should be
one half of the secondary voltage.
through the Air Pressure Switch, to th e normally open contacts of the Bu rner Motor
Relay, and t he prim ary o f the 24 VAC Step Do wn Tran sformer. The Tra nsformer
secondary supplies 2 4 VA C (through a 1A fu se on Model 100 4 and 1005) to the
Relay Coil (t he normally open conta cts close within 30 se conds), and the n ormally
open Centrifugal Switch. When the Relay contacts close, the Burner Blower Motor is
energized. As this motor reaches a pproximately1600 R.P.M., its internal centrifugal
switch closes, supplyin g 24 VAC to the Gas Control Valve. Whe n the G as Control
Valve is supplied with 24 VAC the pilot valve is e nergized, and the ignitor circuit is
energized. Ignition should now occur. After pilot flame is proven, the main gas valve
is energized. The Burner Indicator Light is also energized.
Closing the F an Switch an d the normall y open Conv eyor Switch supplies 120 VAC
through a 3A Fuse, to the Motor Control Board. AC volts are converted to D.C. volts
and a re supplied to the Conveyor mo tor at bo ard terminals A1 and A2 th rough a
D.P.D.T. Rev ersing Swit ch. Adjustmen t of the Speed Co ntrol P otentiometer (500
ohm, 10 turn ) will change re sistance a t terminals S1, S2, and S 3 varying the
voltage to the
the D.C. voltage from the Motor Control Board increases or decreases respectively.
the Motor Control Board. AC volts are converted to DC volts and are supplied to the
Conveyor M otor at term inals A+ an d A-. Adj ustment of th e Spee d Control
Potentiometer (5,000 ohm 10 tu rn ) will change resistance at term inals P1, P2, and
P3 varying t he DC volta ge to the m otor. The sp eed of th e conveyor m otor will
increase o r decrea se a s the DC volt age from th e board incre ases o r de creases
respectively. As the motor turns, it driv es both the reducer gearbox and the tach.
motor. The speed of the Conveyor Motor will increase or decrease
D.C.
as
Impinger I -–1000 Series Service Manual - Domestic
3
generator. The tach. generator is a DC voltage generator which supplies a voltage to
the DC moto r control bo ard and i s use d as a refe rence for m aintaining a constant
conveyor speed.
NOTE
TIME TEMP DISPLAY The Time/Temp. Display is energized when the Fan Switch is closed, supplying120
The 1200 Series Ovens utilize 2 complete conveyor drive systems.
VAC to the primary of the 12.6 volt Transformer The secondary output of the
transformer, normally 13 to 14 VAC (depending on input), with a center tap is
supplied at terminals 1,2, and 3 of the Time/Temp. Display. The center tap is
terminal 2. The display works on a balanced input and center tap voltage to each leg
must be 1/2 the total reading.
The speed side of the Time/Temp. Display uses a slotted disc (cemented to tach.
coupling) to break the infra-red light beam of the optical switch (mounted on gear
motor) producing electrical pulses that are transmitted to the display. The display
converts these pulses into a read-out of minutes and seconds. The temperature
portion of the display uses a Thermistor Probe to sense oven temperature. The
thermistor outputs a resistance proportional to the oven temperature. This resistance
is then converted by the display into a temperature reading.
NOTE: The 1200 Series Ovens use a Double Pole Double Throw Switch to connect
the two Opti cal Encode r Assemblies to the Time/Temp Di splay. By activatin g the
switch, either the front or rear belt speed can be shown by the Time/Temp Display.
SEQUENCE OF OPERATIONS 1022 / 1023 / 1202 / 1203
MODEL 1022 MODEL 1023 - 120/240 VAC - 3 PHASE MODEL 1202 - 120/208 VAC - 3 PHASE - DUAL BELT MODEL 1203 - 120/240 VAC - 3 PHASE - DUAL BELT
POWER SUPPLY Electrical Power to be supplied to the Oven by a five conductor service. Voltage from
the black conductor to the white conductor is 120 VAC.
MAIN FAN CIRCUIT Electrical power is permanently supplied through 6, 50A fuses to the normally open
contacts of the Mercury Contactors. Power is also supplied through 2, 15A fuses to
the normally open contacts of the Double Pole Main Fan Relay, the Double Pole
Main Fan Switch, and the normally open Cool-Down Thermostat (thermostat closes
at 160°F and opens at 140°F.) Closing the Main Fan Switch energizes the coil of the
Main Fan Relay. The normally open contacts now close, energizing the Main Fan
Motor, and the Control Box Cooling Fan. Closing the Fan Switch also supplies power
to the Hour Meter (hour meter discontinued after S/N 3484), the 12.6 VAC
Transformer, the Heat and Conveyor Switches. TRANSFORMER (12.6 VAC)
HEAT CIRCUIT Closing the Fan Switch and the normally open Heat Switch supplies 120 VAC
TEMPERATURE CONTROL
Upon closure of the Fan Switch, 120 VAC is supplied to the primary of the 12.6 VAC
Transformer. The Transformer steps the voltage down to 12.6 VAC (normally 13 to
14 VAC) with a center tap, and supplies power to the Time/Temp Display. The
voltage from each leg of the Transformer's secondary to the center tap should be
one half of the secondary voltage.
through the Air Pressure Switch and the normally closed Hi-Limit Thermostat
(manually re-settable, opens at 190°F) the 3A Fuse, to the L1 terminal of the
Temperature Control Board, the coils of the Mercury Contactors, and to the Heat
Indicator Light.
When the Heat Switch is closed, 120 VAC is supplied to the Temperature Control.
The Temperature Control Potentiometer (2.5K ohm) is adjusted to desired
temperature. The Thermocouple will provide varying millivolts to the Temperature
Controller. The Temperature Controller switches the L2 line of the Contactor coils at
intermittent intervals to maintain desired temperature.
- 120/208 VAC - 3 PHASE
Black conductor is Hot Red conductor is Hot Orange conductor is Hot White conductor is Dedicated Neutral Green conductor is Ground
4
Impinger I -–1000 Series Service Manual - Domestic
CONVEYOR DRIVE (S/N 100 to 4389)
(S/N 4390 and UP) Closing the fan switch and the normally open conveyor switch supplies 120 VAC to
NOTE* The 1200 Series Ovens utilize 2 complete conveyor drive systems. TIME/TEMP DISPLAY The Time/Temp Display is energized when the Fan Switch is closed, supplying 120
NOTE* The 1200 Series Ovens use a Double Pole Double Throw Switch to connect the two
Closing the Fan Switch and the normally open Conveyor Switch supplies 120 VAC
through a 3A Fuse, to the Motor Control Board. AC volts are converted to D.C. volts
and are supplied to the Conveyor Motor at board terminals A1 and A2 through a
D.P.D.T. Reversing Switch. Adjustment of the Speed Control Potentiometer (500
ohm, 10 turn) will change resistance at terminals S1, S2, and S3 varying the D.
voltage to the motor. The speed of the Conveyor Motor will increase or decrease as
the D.C. voltage from the Motor Control Board increases or decreases respectively.
the Motor Control Board. AC volts are converted to DC volts and are supplied to the
Conveyor Motor at terminals A+ and A-. Adjustment of the Speed Control
Potentiometer (5,000 ohm 10 turn) will change resistance at terminals P1, P2, and
P3 varying the DC voltage to the Conveyor Motor. The speed of the conveyor motor
will increase or decrease as the DC voltage from the board increases or decreases
respectively. As the motor turns, it drives both the reducer gearbox and the tach.
generator. The tach. generator is a DC voltage generator which supplies a voltage to
the DC motor control board and is used as a reference for maintaining a constant
conveyor speed.
VAC to the primary of the12.6 volt Transformer. The secondary output of the
transformer, normally 13 to 14 VAC (depending on input), with a center tap is
supplied to terminals 1,2, and 3 of the Time/Temp Display. The center tap is terminal
2. The display works on a balanced input and center tap voltage to each leg must be
1/2 the total reading.
The speed side of the Time/Temp. Display uses a slotted disc (cemented to tach.
coupling) to break the infra-red light beam of the optical switch (mounted on gear
motor) producing electrical pulses that are transmitted to the display. The display
converts these pulses into a read-out of minutes and seconds.
The temperature portion of the display uses a Thermistor Probe to sense oven
temperature. The thermistor outputs a resistance proportional to the oven
temperature. This resistance is then converted by the display into a temperature
reading.
Optical Encoder Assemblies to the Time/Temp. Display. By activating the switch,
either the front or rear belt speed can be shown by the Time/Temp. Display.
C.
SEQUENCE OF OPERATIONS 1040 / 1041 / 1240 / 1241
MODEL 1040 MODEL 1041 - 120/230 VAC - 60HZ - L.P. GAS MODEL 1240 - 120/230 VAC - 60HZ - NATURAL GAS/DUAL BELT MODEL 1241 - 120/230 VAC - 60HZ - L.P. GAS/DUAL BELT
POWER SUPPLY Electrical Power to be supplied to the Oven by a four conductor service. Voltage
from the black conductor to the white conductor is 120 VAC.
CONTROL BOX AUTO COOL DOWN
MAIN FAN CIRCUIT Electrical power is permanently supplied to the normally open contacts of the Double
When the temperature in the Control Box reaches 120°F ± 3°, the Cooling Fan
Thermostat will switch power to the Control Box Cooling Fan. The Thermostat will
interrupt power to the Cooling Fan when the Control Box temperature falls to 100°F +
3°.
Pole Main Fan Relay, the Cooling Fan Thermostat, the normally open Main Fan
Switch, and the normally open Cool Down Thermostat (thermostat closes at 160°F
and opens at 140°F). Closing the Main Fan Switch energizes the coil of the Relay.
The normally open contacts now close, energizing the Main Fan Motor through two
10A fuses, and the Cooling Fan. Closing the Fan Switch also supplies power to the
12.6 VAC Transformer, the Burner and Conveyor Switches.
- 120/230 VAC - 60HZ - NATURAL GAS
Black conductor is Hot Red conductor is Hot White conductor is Dedicated Neutral Green conductor is Ground
Impinger I -–1000 Series Service Manual - Domestic
5
TRANSFORMER (12.6 VAC)
Upon closure of the Fan Switch, 120 VAC is supplied to the primary of the 12.6 VAC
Transformer. The Transformer steps the voltage down to 12.6 VAC (normally 13 to
14 VAC) with a center tap, and supplies power to the Time/ Temp. Display. The
voltage from each leg of the Transformer's secondary to the center tap should be
one half of the secondary voltage. BURNER CIRCUIT Closing the Fan Switch and the normally open Burner Switch supplies 120 VAC
through the Air Pressure Switch, to the Temperature Control Board, the normally
open contacts of the Burner Motor Relay (Burner Motor Relay discontinued after S/N
14791) and the primary of the 24 VAC Transformer. The transformer's secondary
supplies 24 VAC to the burner motor relay coil (the normally open contacts close
within 30 seconds), and the normally open Centrifugal Switch. When the relay
contacts close, the Burner Blower Motor is energized. As this motor reaches approx.
1,600 R.P.M its internal centrifugal switch closes, supplying 24 VAC to the Gas
Control Valve. When the Gas Control Valve is supplied with 24 VAC, the pilot valve
is energized, and the igniter circuit is energized. Ignition should now occur. After pilot
flame is proven, the Main Gas Valve is energized. The Burner Indicator Light is also
energized. TEMPERATURE CONTROL
Closing the Fan Switch and Burner Switch supplies 120 VAC to the Temperature
Control Board. The 1K or 1000 ohm Temperature Potentiometer is adjusted to
desired temperature. The Thermocouple will provide varying millivolts to the
Temperature Controller. The Temperature Controller supplies 120 VAC to the
Solenoid Valve at intermittent intervals to maintain desired temperature. CONVEYOR DRIVE (S/N Q14790 & Below, 1200 series S/N Q14973 & Below 1000 series)
Closing the fan switch and the normally open conveyor Switch supplies 120 VAC to
the Motor Control Board. AC volts are converted to DC volts and are supplied to the
Conveyor Motor, at terminals A+ and A-. Adjustment of the Speed Control
Potentiometer (5,000 ohm 10 turn) will change resistance at terminals P1, P2, and
P3 varying the DC voltage to the Conveyor Motor. The speed of the conveyor motor
will increase or decrease as the DC voltage from the board increases or decreases (S/N Q14791 & Above, 1200 series refer to Pg.
S/N Q14974 &
5 & 6 Above, 1000 series refer to Pg. 5 & 6 (STEPPER)
respectively. As the motor turns, it drives both the reducer gearbox and the tach.
generator. The tach. Generator is a DC voltage generator, which supplies a voltage
to the DC motor control board and is used as a reference for maintaining a constant
conveyor speed.
NOTE: The 1200 Series Ovens utilize 2 complete conveyor drive systems. TIME/TEMP DISPLAY(S/N Q14790 & Below, 1200 series S/N Q14973 & Below 1000 series)
The Time/Temp. Display is energized when the Fan Switch is closed, supplying 120
VAC to the primary of the12.6 volt Transformer. The secondary output of the
transformer, normally 13 to 14 VAC (depending on input), with a center tap, is
supplied to terminals 1,2, and 3 of the Time/Temp. Display. The center tap is
terminal 2. The display works on a balanced input and center tap voltage to each leg
must be 1/2 the total reading. (S/N Q14791 & Above, 1200 series refer to Pg.
S/N Q14974 &
5 & 6 Above, 1000 series refer to Pg. 5 & 6 (STEPPER)
The speed side of the Time/Temp. Display uses a slotted disc (cemented to tach.
coupling) to break the infrared light beam of the optical switch (mounted on gear
motor) producing electrical pulses that are transmitted to the display. The display
converts these pulses into a read-out of minutes and seconds. The temperature
portion of the display uses a Thermistor Probe to sense oven temperature. The
thermistor outputs a resistance proportional to the oven temperature. This resistance
is then converted by the display into a temperature reading. NOTE* The 1200 Series Ovens use a Double Pole Double Throw Switch to connect the two
Optical Encoder Assemblies to the Time/Temp. Display. By activating the switch,
either the front or rear belt speed can be shown by the Time/Temp Display . CONVEYOR DRIVE Closing the Oven Fan Switch supplies 120 VAC, through the Power Transformer, to
the normally open Conveyor Switch. Closing the Conveyor Switch supplies 120 VAC,
through a 3 AMP Fuse, to the primary of the Conveyor Control Transformer. The
secondary of this Transformer supplies 10 VAC and 29 VAC to the Conveyor
Control. The conveyor control supplies voltage pulses to the Conveyor Control. The
Conveyor Control Potentiometer varies the frequency of these pulses. The motor
speed will increase or decrease, as the frequency of the pulses increase or decrease
respectively.
6
Impinger I -–1000 Series Service Manual - Domestic
TIME TEMP DISPLAY Closing the Oven Fan Switch supplies 120 VAC, through the Power Transformer, to
the primary of the Time/Temp. Transformer. The secondary output of the
Transformers, 12.5to 15 VAC with a center tap, is supplies to terminals 1, 2, and3 of
the Time/Temp. Display. The display works on a balanced input, and the center tap
voltage to each leg must be 1/2 the total reading.
Impinger I -–1000 Series Service Manual - Domestic
7
SCHEMATIC / 1000, 1001
8
Impinger I -–1000 Series Service Manual - Domestic
SCHEMATIC / 1004, 1005
Impinger I -–1000 Series Service Manual - Domestic
9
SCHEMATIC / 1022, 1023 – S/N Q19077 & BELOW
10
Impinger I -–1000 Series Service Manual - Domestic
SCHEMATIC / 1022, 1023 – S/N Q19078 & ABOVE
Impinger I -–1000 Series Service Manual - Domestic
11
SCHEMATIC / 1040, 1041 – S/N Q14279 & BELOW
12
Impinger I -–1000 Series Service Manual - Domestic
SCHEMATIC / 1040, 1041 – S/N Q14280 & ABOVE
Impinger I -–1000 Series Service Manual - Domestic
13
SCHEMATIC / 1200, 1201
14
Impinger I -–1000 Series Service Manual - Domestic
SCHEMATIC / 1202, 1203 S/N Q14790 & BELOW
Impinger I -–1000 Series Service Manual - Domestic
15
SCHEMATIC / 1202, 1203 S/N Q14791 & ABOVE
16
Impinger I -–1000 Series Service Manual - Domestic
SCHEMATIC / 1204, 1205
Impinger I -–1000 Series Service Manual - Domestic
17
SCHEMATIC / 1240, 1241 – S/N Q14279 & BELOW
18
Impinger I -–1000 Series Service Manual - Domestic
SCHEMATIC / 1240, 1241 – S/N Q14280 & ABOVE
Impinger I -–1000 Series Service Manual - Domestic
19
TROUBLESHOOTING GUIDE 1000 & 1200
GAS OVENS
SYMPTOM POSSIBLE CAUSE EVALUATION
Oven fan will not run
NOTE:
No Main Fan Cool Down
No Control Box Cooling(For ovens equipped with Control Box Cooling Fan)
NOTE:
No automatic control box cooling (For ovens equipped with control box cooling fan)
Control box cooling fan continues to run Oven will not heat
Incoming Power Supply Check breakers/ Reset if required / Call Power Co.
if needed.
(Export Ovens) For some export ovens, there is a control circuit
step-down transformer. This transformer steps down supply voltage to 120 VAC. If main fan will not run, the secondary of this transformer must be checked for 120 VAC output. Check specific oven
model schematic for circuit location. Oven Fan Fuse(s) Check and/or Replace Fuse Holder Check and/or Replace Fan Switch Check continuity between switch terminals. Main Relay Check continuity to 120 VAC coil. Check for power
to relay coil (120 VAC). Check for 208/240 VAC to
relay terminals. Visually check for contact pull-in. Fan Motor Check for opens, shorts, or grounds. WITH
POWER OFF: Turn Fan Blade to check for locked
rotor. Capacitor Check for opens, shorts, or grounds. Cool Down Thermostat Check cool down thermostat (thermostat closes at
160°F and opens at 140°F). Check for power (120
VAC) at cool down thermostat. With the cool down
thermostat pre-heated, check for continuity. If
switch is open, replace. Main Fan Relay
(Export Ovens) Axial Cooling Fan
Incoming Power Supply Check breakers/Reset if needed. Check for
Cooling Fan Thermostat Check cooling fan thermostat (thermostat closes at
Axial Cooling Fan Check for 120 VAC to cooling fan, if present and
Cooling Fan Thermostat See "Cooling Fan Thermostat"
Gas Supply Check for adequate gas supply to oven. Manual Gas Shut-off Valve Check to see that manual shut-off valve is open. Fan Switch Check to see that fan switch is "on". Main Oven Fan Check if main oven fan is operating. If not, refer to
Burner Switch Check for 120 VAC to neutral on both sides of
Check for power to Main Fan Relay. Visually check
for contact pull in.
(For ovens equipped with a control circuit step-
down transformer, the supply voltage for the
cooling fan is 240 VAC.)
WITH POWER OFF: check for locked rotor. Check
for power (120 VAC) to cooling fan. If 120 VAC is
present at the fan motor and the fan does not run,
replace fan assembly.
incoming power (120 VAC)at cooling fan
thermostat.
120°F and opens at 100°F). With cooling fan
thermostat pre-heated, check for continuity. If
switch is open, replace.
fan does not run, replace fan.
"Oven fan will not run". Page 20.
switch. If switch is closed and 120 VAC is present
on one side only, replace the switch.
20
Impinger I -–1000 Series Service Manual - Domestic
Air Pressure Switch Check for 120 VAC on both sides of switch. If
Transformer, 24 VAC Check for 120 VAC to primary of transformer.
NOTE:
(Model 1004 & 1005) For oven models 1004 and 1005, there is a 1 Amp
Burner Motor Relay Delete burner motor relay refer to Section D, Page
Burner Blower Motor Check for 120 VAC supply to burner blower motor.
Centrifugal Switch of Burner Blower Motor
For ovens with Johnson Controls
Ignition Control and Valve Assembly
Ignition Control (For ovens with
Honeywell Ignition control, See Pg. 21)
No Pilot If the ignition control is supplied with 24 VAC, and
Pilot Shut-off Valve Check to see that pilot shut-off valve is open (shut-
Pilot Tube Check for gas pressure at pilot tube. Disconnect
Pilot Orifice If there is gas pressure at the pilot tube, check the
Burner
Ignitor Check the burner ignitor head for any obstructions,
Impinger I -–1000 Series Service Manual - Domestic
voltage present on one side only, check for air tube
blockage. Adjust air switch. If above fails, replace
air pressure switch.
Check for 24 VAC from secondary of transformer. If
there is primary voltage, but no secondary voltage,
replace transformer.
fuse located between the 24 VAC output from the
transformer and the coil of the burner motor relay. If
there is 24 VAC output from the transformer, but no
burner motor relay action, check fuse and fuse
holder. Replace as necessary.
34.
If 120 VAC is present and motor does not run,
replace motor. WITH POWER OFF: turn blower
wheel to check for locked rotor.
Check for 24 VAC output from secondary of
transformer. If voltage is present, check for 24 VAC
at pin 6 and the ground bar on ignition control and
valve assembly. If the burner blower motor is
running and there is no voltage at pin 6 and the
ground bar on the ignition control valve, replace the
burner blower motor.
Check for 24 VAC supply to the ignition control and
valve assembly at pin 6 and the ground bar. If
voltage is present, check for 24 VAC across pin #1
and the ground bar (pilot valve). If voltage is not
present, replace electronic control package. If the
pilot valve is energized, check to see that the high
voltage ignitor circuit is also energized. To check,
disconnect the ignitor lead from the bottom of
ignition control. Place female terminal of ignitor
lead approximately 1/8" from terminal post on
ignition control. Spark should jump the 1/8" gap. If
no spark is present, replace ignition control.
the pilot valve (internal to valve assembly) and
ignitor circuits are energized, visually check for pilot
flame. This may be done by opening the small
inspection door on the end of the burner, or by
opening the main oven door and looking under the
lower finger housings on the right side of the oven.
If no pilot flame is visible, check the following.
off valve is located between ignition control and
valve assembly and burner.)
pilot tube at burner and connect manometer to pilot
tube. If no gas pressure is present, check for
blockage in pilot tube or pilot shut-off valve. If these
are clear, and there is gas supplied to the oven,
replace the ignition control and valve assembly.
pilot orifice for obstructions. Replace as need
also check for frayed or broken wire, any type of
damage to spark gap (.100 in. 2.5 m.m.) If there is
visible damage, replace ignitor assembly.
21
Pilot flame but no main
flame
For ovens with Honeywell ignition control
No Pilot
Flame Sensor (There should be a visible pilot flame at this time.)
To check for proper flame sensor operation,
connect a digital multimeter (capable of measuring
D. C. microamperes) in series between the flame
sensor wire (normally connected to terminal #4)
and terminal #4. NOTE: This is a current
measurement and the meter must be connected in
series. This procedure is for checking the pilot
flame only. Remove main valve wire (Red) from
terminal #3 on ignition control. With a visible pilo
t flame, the current readings should be as follows: Johnson G-65 control, 0.2 micro amp. D.C. minimum/Johnson G-60 control, 0.7 micro amp. D.C. minimum. If these values are not achieved, replace flame sensor. Also check for any type of damage to flame sensor wire and connections.
Ignition Control and Valve Assembly
If there is a pilot flame, and there is sufficient micro amp. current at terminal #4, check for 24 VAC that the main valve (internal to valve assembly) has opened. Connect a manometer to the manifold gas pressure tap located on the back side of the ignition control and valve assembly. If no gas is present, replace ignition control and valve assembly.
Centrifugal Switch of Burner Blower Motor
Check for 24 VAC output from secondary of transformer. If voltage is present, check for 24 VAC at terminals marked "24V" and "24V gnd" on Ignition Control. If the Burner Blower Motor is running and there is no voltage at terminals 24V and 24V gnd on the ignition control, replace the Burner Blower Motor.
NOTE:
These Ignition Controls have a 30 second pre­purge(Delay) and a 15 second lock-out time – The Ignition Control will try for ignition for 15 seconds and then shut-off. To Re-try for ignition, turn off burner switch, wait 30 seconds and re-try ignition.
Ignition Control
Check for 24 VAC supply to ignition control at terminals "24V" and "24V gnd". If voltage is present, check for 24V at terminal "P.V. (Pilot Valve) and "gnd". If voltage is not present, replace Ignition Control. If the pilot valve is energized, check to see that the high voltage ignitor circuit is also energized. To check, disconnect the ignitor lead from the ignition control. Place the terminal of ignitor lead approximately 1/8" from terminal post on Ignition Control. Spark should jump the 1/8" gap. If no spark is present, replace ignition control. If the ignition control is supplied with 24 VAC and the pilot valve (in gas valve) and ignitor circuits
Pilot Shut-off Valve If no pilot flame is visible, check to see that the pilot
shut-off valve is open(shut-off valve is located between gas valve and burner).
Pilot Tube Check for gas pressure at pilot tube. Disconnect
pilot tube at burner and connect manometer to pilot tube. If no gas pressure is present, check for blockage in pilot tube or pilot shut-off valve.
Pilot Orifice If there is gas pressure at the pilot tube, check the
pilot orifice for obstructions. Replace as needed.
Burner Ignitor Check the burner ignitor head for any obstructions,
also check for frayed or broken wire, any type of damage to spark gap (.100 in. 2.5 mm) If there is visible damage, replace ignitor assembly.
22
Impinger I -–1000 Series Service Manual - Domestic
Spark Ignitor (Flame Sensor) (There should be a visible pilot flame at this time). Pilot flame but no main flame
NOTE: The Honeywell Ignition Control uses the spark ignitor as the flame sensor. If spark continues, check for proper ground connections at Ignition Control. Check pilot orifice for any partial blockage. If the above checks OK, replace ignition control. If spark stops when pilot is lit, check for 24 VAC across M.V. - M.V/ P.V. terminals, if voltage is not present, replace ignition control. If voltage is present at terminals M.V. - M.V./P.V., the indicator light on the control panel should be on, verify that the main valve has opened, connect manometer to
manifold gas pressure tap(located on the Red Indicator Light is on, but no main
flame(For ovens with
mechanical thermostat)
(For ovens with Electronic Temperature Control)
Temperature Control Valve (Robert Shaw) Main Orifice Check for blockage of main orifice. If there is no
Temperature Control Potentiometer
Check for gas supply at temperature control. Check
for temperature control set above 300°F.
blockage to the main orifice, replace the
temperature control.
Check for 120 VAC across L1 and L2on
temperature control board. Potentiometer (1000
ohm,1 turn) WITH POWER OFF: check ohms
across red and black leads, the ohm reading
should be 0 to1000 ohms as the dial is turned.
From green to red, the reading should be 1000
ohms steady throughout the full turn of the dial. NOTE: Ovens S/N Q18037 and above, the potentiometer is internal to temperature control. Proceed to next component.
Thermocouple Probe Remove thermocouple leads from the temperature
control board, and measure the millivolt output of
these leads. Refer to chart on page 38 in the
adjustment section for proper readings.
Temperature Control Turn temperature control dial to full "on" position.
Measure for 120 VAC across terminals "N.O." and
"L2", if voltage is not present; replace control.
Solenoid Valve If voltage is present at terminals "
N.O."and "L2", check for voltage at solenoid valve. If voltage is present, listen for valve to open and close. Also, check for opens and shorts in coil. If solenoid valve is defective, replace
Intermittent Heating Both the main fan motor and burner blower motor
are equipped with thermo-protection and will cease to operate when not cooled properly. This can cause the units to cycle on and off intermittently. Also, most of the problems listed under "oven will not heat" can cause intermittent failures.
For continuin
g intermittent problems, a series of test lights may be made and installed in the ovens. The lights will allow the customer to advise the service technician a trouble code when the oven fails.
The lights should be connected in the following manner:
Light#l attached in 120VAC line after Air Pressure Switch. Light#2 attached after 120VAC contacts of Burner Motor Relay (or, refer to Bulletin #028 for Relay Removal). Light#3 in 24VAC Burner Transformer Secondary. Light#4 in 24VAC at terminal #6 of Johnson control valve or "24V" on Honeywell Control. Light#5 in 24VAC at terminal #1 of Johnson control valve or "PV" on Honeywell Control. Light#6 in 24VAC at terminal #3 of Johnson control valve or "MV" on Honeywell Control.
CODE:
All lights off - lights of main power, main fan off, air pressure switch out. 1 on 2 off 3 on 4 off 5 off 6 off - Burner Motor Relay bad.
Impinger I -–1000 Series Service Manual - Domestic
23
1 on 2 on 3 on 4 off 5 off 6 off - Burner Motor Centrifugal Switch bad. 1 on 2 on 3 on 4 on 5 off 6 off - Ignition Control bad. 1 on 2 on 3 on 4 on 5 on 6 off - Pilot Shield missing or warped, Flame Sensor bad, Pilot
Orifice plu
-
1 on 2 on 3 on 4 on 5 on 6 on - Unit still not working Main Orifice plugged, Gas Valve bad,
-
Temperature Control bad.
However, Mai
-
gged, or Gas Valve
n Orifice would not be intermittent problem.
bad.
24
Impinger I -–1000 Series Service Manual - Domestic
TROUBLESHOOTING GUIDE
ELECTRIC OVENS MODEL SERIES 1000 & 1200
SYMPTOM POSSIBLE CAUSE EVALUATION
Oven fan will not run
NOTE:
No Main Fan Cool Down
No control box cooling
Oven will not heat
NOTE:
Incoming Power Supply Check breakers/Reset if required/ Call Power Co. if
needed.
(Export Ovens) For some export ovens, there is a control circuit
step-down transformer. This transformer steps down supply voltage to 120 VAC. If main fan will not run, the secondary of this transformer must be checked for 120 VAC output. Check specific oven
model schematic for circuit location. Oven Fan Fuse(s) Check and/or Replace Fuse Holder Check and/or Replace Fan Switch Check continuity between switch terminals. Main Relay Check continuity to 120 VAC coil. Check for power
to the relay coil (120 VAC). Check for 208/220/240
VAC to relay terminals. Visually check for contact
pull-in Fan Motor Check for opens, shorts, or grounds. WITH
POWER OFF: Turn Fan Blade to check for locked
rotor. Capacitor Check for opens, shorts, or grounds. Cool Down Thermostat Check cool down thermostat (thermostat closes at
160°F and opens at 140°F). Check for power (120
VAC) at cool down thermostat. With cool down
thermostat pre-heated, check for continuity. If
switch is open, replace.
Main Fan Relay Check for power to main fan relay. Visually check
for contact pull in. Axial Cooling Fan WITH POWER OFF: turn the fan blade to check for
locked rotor. Check for power (120 VAC) to cooling
fan. If 120 VAC is present at the fan motor and the
fan does not run, replace fan assembly. Main Oven Fan Check if main oven fan is operating. If not, refer to
"Oven fan will not run." Heat Switch Check for continuity between switch terminals with
switch on. Replace if defective. Air Pressure Switch Check for 120 VAC on both sides of switch. If
voltage present on one side only, check for air tube
blockage, adjust air switch. If above fails, replace
air pressure switch. Hi Limit Thermostat Terminals are normally closed. If open, reset and
test oven for proper operation. If thermostat will not
hold for maximum oven temperature, and oven is
not exceeding temperature dial setting, replace
thermostat (rated at 190°F). Hi Limit Thermostat (Model 1032)
3 Amp Temperature Control Fuse Fuseholder Check and/or replace.
Terminals are normally closed. If open, reset and
test oven for proper operation. If thermostat will not
hold for maximum oven temperature, and oven is
not exceeding temperature dial setting. Replace
the thermostat. Check for proper location of
sensing bulb in its spring holder. If hi-limit is still
tripping, replace (rated for 368°C).
Check and/or Replace
Impinger I -–1000 Series Service Manual - Domestic
25
Oven heats with switch off
Conveyor will not run (S/N 100-4389)
Temperature Control Board Check for 120 VAC input to temperature control
board. If not present, check wiring from fuse holder
to temperature control board. Turn the temperature
adjustment dial to the maximum temperature
position Check for 120 VAC at coil of mercury
contactor(s). Next, short the leads of thermocouple
on the temperature control board, check for 120
VAC at coil of mercury contactor(s). If voltage is
not present, replace temperature control board. If
voltage is present proceed. Temperature Control Potentiometer
Potentiometer is 0 to 2.5K ohm. WITH POWER
OFF: remove the leads from the temperature
control board terminals 1, 2, and 3 and measure
ohms from black to white leads. The ohm reading
should be 0 to approximately 2.5K ohms as the dial Thermocouple Probe Remove thermocouple leads from the temperature
control board, and measure the millivolt output of
the leads. Refer to chart in adjustment section for
proper millivolt readings. Mercury Contactor(s) Check for 120 VAC to the contactor coil. If voltage
is present and contactor will not activate, replace
the contactor(s). Also check each contactor for
proper high voltage input and output. 50 Amp Fuses If there is no high voltage input to the mercury
contactor(s), check the 50 amp fuses and replace if
necessary. Heater Elements Check the Amp. draw on each hot leg for proper
load. Check the specifications plate for rating
information. If the Amp. draw is low or high, check
the individual elements for opens, shorts, and
proper resistance . To check resistance of the
elements, turn off the power! Remove all leads
from the elements and use an accurate digital
VOM. The element resistance should be as
follows: 208V - 9.8 ohms approx. 220V - 10.5 ohms
approx. 240V - 13 ohms approx. If all readings are
not correct, replace elements as needed. Mercury Contactor(s) The mercury contactor has probably malfunctioned
in the closed position. If there is no voltage to the
operating coil, but there is high voltage at the
contactor output, replace the mercury contactor. Voltage Supply Check incoming voltage supply at line 1 to neutral.
There should be a voltage reading of 120 VAC. If
not present, check breakers. 3 Amp Fuse This conveyor fuse is located on the front panel.
Replace if defective. Fuse Holder Check and/or Replace. Conveyor Switch Same procedure as for fan switch. D. C. Motor Control Board
Check for 120 VAC input to D. C. control board
across L1 and L2. Check the 3 amp fuse on the D.
C. control board. Check for D. C. voltage at
terminal F1 a
nd F2. Voltage should be 10 VDC + 10 steady. If this voltage is not present, replace D. C. control board. Check for D. C. voltage output to the motor across terminals A1 and A2 (this voltage should be approx. 125 VDC at maximum conveyor motor speed).
26
Impinger I -–1000 Series Service Manual - Domestic
Speed Control Potentiometer This is a 0 to 400 ohm or 0 to 500 ohm, 10-turn
potentiometer. WITH POWER OFF: remove the red, white, and black leads from terminals S1, S2, S3. With a digital multimeter, check the ohm reading across the red to black leads. This ohm reading should be a steady 400-ohm, or 500-ohm, through the entire 10-turn rotation of the potentiometer. Check for shorts or opens or unsteady, ohm reading, if potentiometer is defective, replace. If the potentiometer checks OK, and there is no output at terminals A1 and A2, replace the D. C. control board.
Reversing Switch If there is D. C. voltage output from the motor
control board, but the conveyor drive motor is not running, check the D.P.D.T. reversing switch.
Conveyor Drive Motor Check the conveyor drive sprocket for tightness.
Disconnect the motor, check the red and black motor leads for opens, shorts or grounds. Check the brushes for excessive or abnormal wear. Replace as needed. Reconnect motor. Test for operation. If motor does not run, replace.
Conveyor will not run(S/N 4390 to Q190771000 Series) (S/N 4390­Q147901200 Series)
Voltage Supply Check incoming voltage supply at line 1 to neutral.
There should be a voltage reading of 120 VAC. If no present, check breakers. 3 Amp Fuse. This conveyor fuse is located on the front panel. Replace if defective.
Fuseholder Check and/or Replace. Fan Switch See procedure for checking on Page 20. Conveyor Switch Same procedure as for fan switch.
NOTE:
(Dual Belt Ovens) Dual belt ovens utilize 2 complete independent
conveyor drive systems. The trouble shooting procedures are the same as single belt ovens, except that the dual belt ovens use one each of the following: one "A" D. C. control board and one "B" D. C. control board.
Speed Adjustment Potentiometer
This is a 0 to 5 K ohm, 10 turn potentiometer With power off, remove the red, black and white pot leads from the motor control board at terminals P1, P2 and P3. With a digital multimeter, check the ohm reading across the red lead (P3) to the black lead (P1). This reading should be 5 K ohms ± 5% as the pot is rotated from low to high. Place the meter leads on the red lead (P3) and on the white lead (P2) Rotating the pot. slowly, from low to high, the meter reading should show an even transition from O to 5 K ohms ± 5%. There should be
DC Motor Control Board Check for 120 VAC input to the control board at
terminals L1 and L2. If not present, check the conveyor switch and wiring back to 3-amp fuse and then back to power source if necessary. If 120 VAC is present at L1 and L2, check the VDC output at terminals A+ and A-. If a DC voltage is not present, check the 4 amp and the 1 amp fuses on the control board. Also reset and check the mini breaker in the armature line to the gearmotor. If 120 VAC is present at terminals L1 and L2, but DC voltage is not present at A+ and A-, providing the 1 amp and 4 amp fuses are good, replace the board. If DC voltage is present at A+ and A-, but motor does not run, check gear motor as follows.
Impinger I -–1000 Series Service Manual - Domestic
27
Conveyor speed varying or intermittent
Conveyor will not run(S/N Q19078 & Up1000 Series) (S/N Q14791 & Up1200 Series)
Conveyor Gear Motor If DC voltage is present at A+ and A- and the motor
does not run, first check the mini breaker and then the conveyor. Refer to the next possible cause. Check the leads to the motor for evidence of any shorts or opens, and each lead to ground. If the motor fails the above tests, replace motor. Remove dust cover from the top of the motor and rotate motor shaft to determine if there is a locked rotor or a locked gear box (use care so encoder disc is not damaged).
Conveyor Check for any mechanical misalignment or
improper adjustment. Also check for worn bearings. The Installation and Operations Manual shows proper conveyor belt adjustment. A conveyor belt that is over tightened will cause excessive bearing wear and sometimes, irregular speed.
Power Supply Check power supply at the DC control board for the
120 VAC at board terminals L1 and L2. If voltage is not present, check main circuit breakers.
Tach generator and DC Motor Control Board
With the power to the DC motor control board turned off, remove the leads from terminals T1 and T2.Place the test leads of a digital meter on the tach leads, turn power on, and the meter reading should be approximately 30 to 35 VDC. This reading should be steady within ± 0.2 to 0.3 VDC. If this reading is not within +
0.5 VDC, place the test meter probes on terminals A+ and A-. The meter reading should be approximately 150 to 160 VDC and steady within approximately 2 VDC. If the tach. voltage is unsteady, and the board output is steady, check the coupling for loose set screws or any type of damage. If the coupling checks good, the tach. is usually bad. If the board voltage output is unsteady beyond limits, then the board is probably bad. Always check the speed pot. Be sure it is okay before changing a board or tach. This test is not always 100% accurate as this test is not performed at operating speeds. However, this test is the best method currently available. Readjustment should always be attempted at least once before replacement. See procedure for board adjustment on page 44.
DC Gearmotor If the DC control board is steady then the problem
may be the motor or gearbox. Check the brushes in the motor for excessive arching and/or unusual wear. Check the motor and gearbox from instruction located on page 27 under "possible cause" listing "Conveyor gear motor".
Voltage Supply Check incoming voltage supply at Line 1 to neutral.
There should be a voltage reading of 120 VAC.
Fan Switch See procedure for checking on page 20. Conveyor Switch Check for 120 VAC to conveyor switch. If no
voltage is present, trace wiring back to the fan switch. WITH POWER OFF: Check continuity between switch terminals.
Conveyor Fuse (3A) Check, replace if necessary. Fuseholder Check, replace if necessary.
28
Impinger I -–1000 Series Service Manual - Domestic
Loading...
+ 64 hidden pages