Lincoln 1200, 1000 User Manual

SERVICE MANUAL
(INTERNATIONAL)
IMPINGER CONVEYOR OVENS
MODEL SERIES 1000 & 1200
Lincoln Foodservice Products, LLC
Fort Wayne, Indiana 46804
United States of America
Phone : (800) 374-3004
U.S. Fax: (888) 790-8193 • Int’l Fax: (260) 436-0735
Technical Service Hot Line
(800) 678-9511
www.lincolnfp.com
1000serviceexp REV: 1/5/07
TABLE OF CONTENTS
TABLE OF CONTENTS..............................................................................................................................................2
SEQUENCE OF OPERATIONS 1002/1003...............................................................................................................3
SEQUENCE OF OPERATIONS 1106........................................................................................................................4
SEQUENCE OF OPERATIONS 1028 / 1029 / 1228 / 1229 ......................................................................................5
SEQUENCE OF OPERATIONS 1030........................................................................................................................6
SEQUENCE OF OPERTIONS 1032 ..........................................................................................................................7
SEQUENCE OF OPERATIONS / 1033, 1034, 1046, 1047 .......................................................................................8
SEQUENCE OF OPERATIONS 1042 / 1043 / 1242 / 1243 ....................................................................................10
SCHEMATIC / 1002, 1003 .......................................................................................................................................12
SCHEMATIC / 1006 TO SERIAL NUMBERS Q14279.............................................................................................13
SCHEMATIC / 1028, 1029, S/N Q19071 & BELOW ................................................................................................14
SCHEMATIC / 1028, 1029, S/N Q19078 & ABOVE.................................................................................................15
SCHEMATIC / 1030, TO S/N Q17170......................................................................................................................16
SCHEMATIC / 1030, S/N Q17171 & ABOVE...........................................................................................................17
SCHEMATIC / 1032. S/N Q19077 & BELOW ..........................................................................................................18
SCHEMATIC / 1032, S/N Q19078 & ABOVE...........................................................................................................19
SCHEMATIC / 1033, 1034, 1046, 1047 ...................................................................................................................20
SCHEMATIC / 1042, 1043, S/N Q14279 & BELOW ................................................................................................21
SCHEMATIC / 1042, 1043, S/N Q14280 & ABOVE.................................................................................................22
SCHEMATIC / 1228. 1229, S/N Q14790 & BELOW ................................................................................................23
SCHEMATIC / 1228, 1229, S/N Q14791 & ABOVE.................................................................................................24
SCHEMATIC / 1242, 1243 .......................................................................................................................................25
TROUBLESHOOTING GUIDE 1000 & 1200 / GAS OVENS ..................................................................................26
TROUBLESHOOTING GUIDE 1000 & 1200 SERIES / ELECTRIC OVENS...........................................................39
TROUBLESHOOTING / GAS OVENS 1033, 1034, 1046, 1047..............................................................................46
REMOVAL, INSTALLATION & ADJUSTMENTS .....................................................................................................53
MODEL SERIES 1000 &1200...............................................................................................................................53
PARTS / MODEL SERIES 1000 & 1200 - GENERAL..............................................................................................80
BLOW UP / 1000, 1200 – GENERAL.......................................................................................................................81
PARTS / MODEL 1002-1003 , S/N 2584 TO 4389 ..................................................................................................82
BLOW UP / 1002, 1003 – S/N 2584 to 4389............................................................................................................83
PARTS / MODEL 1002-1003, S/N 4390 & UP .........................................................................................................84
BLOW UP / 1002, 1003 – S/N 4390 & ABOVE ........................................................................................................85
PARTS / MODEL 1006 .............................................................................................................................................86
BLOW UP / 1006 ......................................................................................................................................................87
PARTS / 1028-1029-1032 ........................................................................................................................................88
BLOW UP / 1028, 1029, 1032..................................................................................................................................89
PARTS/ MODEL 1030 ..............................................................................................................................................90
BLOW UP / 1030 ......................................................................................................................................................91
PARTS / 1042, 1043.................................................................................................................................................92
BLOW-UP / 1042, 1043 ............................................................................................................................................93
PARTS / 1033, 1034, 1046, 1047.............................................................................................................................94
BLOW-UP / 1033, 1034, 1046, 1047........................................................................................................................95
PARTS / 1228-1229..................................................................................................................................................96
BLOW UP / 1228, 1229 ............................................................................................................................................97
PARTS / 1242, 1243.................................................................................................................................................98
BLOW - UP / 1242, 1243 ..........................................................................................................................................99
PARTS / OVEN BACK - GAS .................................................................................................................................100
BLOW UP / OVEN BACK – GAS ...........................................................................................................................101
PARTS / OVEN BACK- ELECTRIC........................................................................................................................102
BLOW UP / OVEN BACK – ELECTRIC .................................................................................................................103
PARTS / CONVEYOR MOTOR ASSEMBLY S/N 4390 & ABOVE ........................................................................104
BLOW UP / CONVEYOR MOTOR ASSEMBLY S/N 4390 & ABOVE ...................................................................105
PARTS / SERIES 1000 – CONVEYOR..................................................................................................................106
BLOW UP / SERIES 1000 CONVEYOR ................................................................................................................107
PARTS / SERIES 1200 - CONVEYOR CONTROL................................................................................................108
BLOW UP / SERIES 1200 – CONVEYOR CONTROL ..........................................................................................109
PARTS / SERIES 1200 – CONVEYOR..................................................................................................................110
BLOW UP / SERIES 1200 – CONVEYOR .............................................................................................................111
Impinger I -–1000 Series Service Manual - International 2
SEQUENCE OF OPERATIONS 1002/1003
MODEL 1002 - 240VAC - 50HZ - NATURAL GAS MODEL 1003 - 240VAC - 50HZ - L.P. GAS
POWER SUPPLY Electrical Power to be supplied to the Oven by a three conductor service.
Black conductor is Hot Red conductor is Neutral
Green conductor is Ground CONTROL BOX When the temperature in the Control Box reaches 120°F + AUTO COOL DOWN 3°, the Cooling Fan Thermostat will switch power to the Control Box Cooling Fan.
The Thermostat will interrupt power to the Cooling Fan when the Control Box temperature falls to 100°F + 3°.
MAIN FAN CIRCUIT Electrical power is permanently supplied to the normally open contacts of the Double
Pole Main Fan Relay, the Cooling Fan Thermostat, the normally open Double Pole Main Fan Switch, and the normally open Cool Down Thermostat (thermostat closes at 160°F and opens at140°F). Closing the Main Fan Switch supplies 240 VAC through a 3A Fuse to the primary of the control circuit Step down Transformer. The Transformer steps the voltage down to 120 VAC for the control circuit. 120 VAC is supplied to the coil of the Double Pole Main Fan Relay. The coil of the relay is energized. The normally open contacts now close, energizing the Main Fan Motor through one 10A Fuse. Closing the Fan Switch also supplies power to the Cooling Fan, Hour Meter (hour meter discontinued after S/N 3484), the 12.6 VAC Transformer, the Burner and Conveyor Switches.
BURNER CIRCUIT
CONVEYOR DRIVE (S/N 100 to 4389)
(S/N 4390 and UP)
Closing the Fan Switch and the normally open Burner Switch supplies 120 VAC through the Air Pressure Switch, to the normally open contacts of the Burner Motor Relay, and the primary of the 24 VAC Step Down Transformer. The Transformer secondary supplies 24 VAC to the Relay Coil (the normally open contacts close within 30 seconds), and the normally open Centrifugal Switch. When the Relay contacts close, the Burner Blower Motor is energized. As this motor reaches approximately 1600 R.P.M., its internal centrifugal switch closes, supplying 24 VAC to the Gas Control Valve. When the Gas Control Valve is supplied with 24 VAC, the pilot valve is energized, and the igniter circuit is energized. Ignition should now occur. After pilot flame is proven, the main gas valve is energized. The Burner Indicator Light is also energized. Closing the Fan Switch and the normally open Conveyor Switch supplies 120 VAC through a 3A Fuse, to the Motor Control Board. AC volts are converted to D.C. volts and are supplied to the Conveyor Motor at board terminals A1 and A2 through a D.P.D.T. Reversing Switch. Adjustment of the Speed Control Potentiometer (500 ohm, 10 turn) will change resistance at terminals S1, S2, and S3 varying the D.C. voltage to the motor. The speed of the Conveyor Motor will increase or decrease as the D.C. voltage from the Motor Control Board increases or decreases respectively Closing the fan switch and the conveyor switch supplies 120 VAC to the Motor Control Board. AC volts are converted to DC volts and are supplied to the Conveyor Motor at terminals A+ and A-. Adjustment of the Speed Control Potentiometer (5,000 ohm 10 turn) will change resistance at terminals P1, P2, and P3 varying the DC voltage to the motor. The speed of the conveyor motor will increase or decrease as the DC voltage from the board increases or decreases respectively. As the motor turns, it drives both the reducer gear box and the tach. generator which supplies a voltage to the DC motor control board and is used as a reference for maintaining a constant conveyor speed
Impinger I -–1000 Series Service Manual - International 3
TIME TEMP DISPLAY The Time/Temp Display is energized when the Fan Switch is closed, supplying 120
VAC to the primary of the 12.6 volt Transformer. The secondary output of the transformer, normally 13 to 14 VAC (depending on input), with a center tap, is supplied to terminals 1,2, and 3 of the Time/Temp Display. The center tap is terminal
2. The display works on a balanced input and center tap voltage to each leg must be 1/2 the total reading.
The speed side of the Time/Temp. Display uses a slotted disc (cemented to tach. coupling) to break the infra-red light beam of the optical switch (mounted on gear motor) producing electrical pulses that are transmitted to the display. The display converts these pulses into a read-out of minutes and seconds.
The temperature portion of the display uses a Thermistor Probe to sense oven temperature. The thermistor outputs a resistance proportional to the oven temperature. This resistance is then converted by the display into a temperature reading.
SEQUENCE OF OPERATIONS 1106
MODEL 1006 - 240 VAC - 50HZ - 1 PHASE - NATURAL GAS
POWER SUPPLY Electrical Power to be supplied to the Oven by a three conductor service.
Red conductor is Hot
Black conductor is Neutral
Green conductor is Ground CONTROL BOX AUTO COOL DOWN
MAIN FAN CIRCUIT Electrical power is permanently supplied to the normally open contacts of the Double
TRANSFORMER (12.6 VAC)
BURNER CIRCUIT Closing the Fan Switch and the normally open Burner Switch supplies 120 VAC
CONVEYOR DRIVE (S/N 4390 AND UP)
When the temperature in the Control Box reaches 120°F + 3°, the Cooling Fan Thermostat will switch power to the Control Box Cooling Fan. The Thermostat will interrupt power to the Cooling Fan when the Control Box temperature falls to 100°F + 3°.
Pole Main Fan Relay, the Cooling Fan Thermostat, and through a 3A Fuse to the normally open Double Pole Main Fan Switch, and the normally open Cool Down Thermostat (thermostat closes at 160°F and opens at 140°F). Closing the Main Fan Switch supplies 240 VAC to the primary of the control circuit Step Down Transformer. (The transformer steps the voltage down to 120VAC for the control circuit) 120 VAC is supplied to the coil of the Main Fan Relay. The coil of the Relay is energized, the normally open contacts now close, energizing the Main Fan Motor through one 10A fuse. Closing the Fan Switch also supplies power to the Cooling Fan, the 12.6 VAC Transformer, the Burner and Conveyor Switches Upon closure of the Fan Switch, 120 VAC is supplied to the primary of the 12.6 VAC Transformer. The Transformer steps the voltage down to 12.6 VAC (normally 13 to 14 VAC) with a center tap, and supplies power to the Time/Temp Display. The voltage from each leg of the Transformer's secondary to the center tap should be one half of the secondary voltage.
through the Air Pressure Switch, to the normally open contacts of the Burner Motor Relay, and the primary of the 24 VAC Step Down Trans-former. The Transformer secondary supplies 24 VAC to the coil of the Burner Motor Relay (the normally open contacts close within 30 seconds), and through the Burner Air Pressure Switch to the normally open Centrifugal Switch. When the Relay contacts close, the Burner Blower Motor is energized. As this motor reaches approximately 1600 R.P.M., the Burner Air Pressure Switch closes, and the motor's internal centrifugal switch closes supplying 24 VAC to the Gas Control Valve. When the Gas Control Valve is supplied with 24 VAC, the pilot valve is energized, and the igniter circuit is energized. Ignition should now occur. After pilot flame is proven, the main gas valve is energized. The Burner Indicator Light is also energized. Closing the fan switch and the normally open conveyor switch supplies 120 VAC to the Motor Control Board .AC volts are converted to DC volts and are supplied to the Conveyor Motor at terminals A+ and A-. Adjustment of the Speed Control Potentiometer (5000 ohm 10 turn ) will change resistance at terminals P1, P2, and P3 varying the DC voltage to the motor. The speed of the conveyor motor will
Impinger I -–1000 Series Service Manual - International 4
increase or decrease as the DC voltage from the board increases or decreases respectively. As the motor turns, it drives both the reducer gearbox and the Tach. Generator. The Tach. Generator is a DC voltage generator, which supplies a voltage to the DC motor control board and is used as a reference for maintaining a constant conveyor speed.
TlME/TEMP DISPLAY The Time/Temp. Display is energized when the Fan Switch is closed, supplying 120
VAC to the primary of the 12.6 volt Transformer. The secondary output of the transformer, normally 13 to 14 VAC (depending on input), with a center tap is supplied to terminals 1,2, and 3 of the Time/Temp Display. The center tap is terminal
2. The display works on a balanced input and center tap voltage to each leg must be 1,2 the total reading. The speed side of the Time/Temp. Display uses a slotted disc (cemented to tach. coupling) to break the infra-red light beam of the optical switch (mounted on gear motor) producing electrical pulses that are transmitted to the display. The display converts these pulses into a read-out of minutes and seconds. The temperature portion of the display uses a Thermistor Probe to sense oven temperature. The thermistor outputs a resistance proportional to the oven temperature. This resistance is then converted by the display into a temperature reading.
SEQUENCE OF OPERATIONS 1028 / 1029 / 1228 / 1229
MODEL 1028 - 380Y/220 VAC - 50 HZ - 3 PHASE MODEL 1029 - 415Y/240 VAC - 50 HZ - 3 PHASE MODEL 1228 - 380Y/220 VAC - 50 HZ - 3 PHASE - DUAL BELT MODEL 1229 - 415Y/240 VAC - 50 HZ - 3 PHASE - DUAL BELT
POWER SUPPLY Electrical Power to be supplied to the Oven by a five conductor service.
Black conductor is Hot
Red conductor is Hot
Orange conductor is Hot
White conductor is Dedicated Neutral
Green conductor is Ground
MAIN FAN CIRCUIT Electrical power is permanently supplied through 3, 50A fuses to the normally open
contacts of the Mercury Contactor. Power is also supplied through 1, 10A fuse to the normally open contact of the Main Fan Relay, through a 1A Fuse to the normally open Double Pole Main Fan Switch, and to the normally open Cool-Down Thermostat (thermostat closes at 160°F and opens at 140°F.) Closing the Main Fan Switch supplies 220 or 240 VAC to the primary of the control circuit Step Down Transformer. (The transformer steps the voltage down to 120 VAC for the control circuit.) 120 VAC is supplied to the coil of the Main Fan Relay. The coil of the relay is energized, the normally open contacts close, energizing the Main Fan Motor. Closing the Main Fan Switch also supplies power to the 12.6 VAC Transformer, the Control
Box Cooling Fan, and the Heat and Conveyor Switches. TRANSFORMER (12.6 VAC)
HEAT CIRCUIT Closing the Fan Switch and the normally open Heat Switch supplies 120 VAC
TEMPERATURE CONTROL
Upon closure of the Fan Switch, 120 VAC is supplied to the primary of the 12.6 VAC
Transformer. The Transformer steps the voltage down to 12.6 VAC (normally 13 to
14 VAC) with a center tap, and supplies power to the Time/Temp. Display. The
voltage from each leg of the Transformer's secondary to the center tap should be
one half of the secondary voltage.
through the normally open Air Pressure Switch, and the normally closed Hi-Limit
Thermostat (manually re-settable, opens at 190°F) and, the 3A Fuse, to the L1
terminal of the Temperature Control Board, the coil of the Mercury Contactor, and to
the Heat Indicator Light.
When the Heat Switch is closed, 120 VAC is supplied to the Temperature Control.
The Temperature Control Potentiometer (2.5K ohm) is adjusted to desired
temperature. The Thermocouple will provide varying millivolts to the Temperature
Controller. The Temperature Controller switches the L 2 line of the Contactor coils at
intermittent intervals to maintain desired temperatures.
Impinger I -–1000 Series Service Manual - International 5
CONVEYOR DRIVE (S/N 100 to 4389)
(S/N 4390 and UP 1000 Series) (S/N 4390 to 14790 1200 Series)
(S/N 14791 & Above 1200 Series See Page 9
NOTE The 1200 Series Ovens utilize 2 complete conveyor drive systems. TIME TEMP DISPLAY(S/N 4390 & Above1000 Series) S/N 4390-147901200 Series)
(T/T Display S/N Q14791& Above1200 Series See Page 9
NOTE The 1200 Series Ovens use a Double Pole Double Throw Switch to connect the two
Closing the Fan Switch and the normally open Conveyor Switch supplies 120 VAC
through a 3A Fuse, to the Motor Control Board. AC volts are converted to D.C. volts
and are supplied to the Conveyor Motor at board terminals A1 and A2 through a
D.P.D.T. Reversing Switch. Adjustment of the Speed Control Potentiometer (500
ohm, 10 turn) will change resistance at terminals S1, S2, and S3 varying the D.C.
voltage to the Conveyor Motor. The speed of the Conveyor Motor will increase or
decrease as the D.C. voltage from the Motor Control Board increases or decreases
respectively.
Closing the fan switch and the normally open Conveyor switch supplies 120 VAC to
the Motor Control Board. AC volts are converted to DC volts and are supplied to the
Conveyor Motor at terminals A+ and A-. Adjustment of the Speed Control
Potentiometer (5,000 ohm 10 turn ) will change resistance at terminals P1, P2, and
P3 varying the DC voltage to the motor. The speed of the conveyor motor will
increase or decrease as the DC voltage from the board increases or decreases
respectively. As the motor turns, it drives both the reducer gearbox and the tach.
generator. The tach. generator is a DC voltage generator which supplies a voltage to
the DC motor control board and is used as a reference for maintaining a constant
conveyor speed.
The Time/Temp. Display is energized when the Fan Switch is closed, supplying 120
VAC to the primary of the 12.6 volt Transformer. The secondary output of the
transformer, normally 13 to 14 VAC (depending on input), with a center tap, is
supplied to terminals 1,2, and 3 of the Time/Temp. Display. The center tap is
terminal 2. The display works on a balanced input and center tap voltage to each leg
must be 1/2 the total reading.
The speed side of the Time/Temp. Display uses a slotted.disc (cemented to tach.
coupling) to break the infra-red light beam of the optical switch (mounted on gear
motor) producing electrical pulses that are transmitted to the display. The display
converts these pulses into a read-out of minutes and seconds.
The temperature portion of the display uses a Thermistor Probe to sense oven
temperature. The thermistor outputs a resistance proportional to the oven
temperature. This resistance is then converted by the display into a temperature
reading.
Optical Encoder Assemblies to the Time/Temp. Display. By activating the switch,
either the front or rear belt speed can be shown by the Time/Temp. Display.
SEQUENCE OF OPERATIONS 1030
MODEL 1030 - 220 VAC - 50HZ - 1 PHASE
POWER SUPPLY Electrical Power to be supplied to the Oven by a three conductor service.
Black conductor is Hot Red conductor is Neutra
Green conductor is Ground CONTROL BOX AUTO COOL DOWN
MAIN FAN CIRCUIT Electrical power is permanently supplied to the normally open contacts of the Double
TRANSFORMER (12.6 VAC)
When the temperature in the Control Box reaches 120°F + 3°, the Cooling Fan Thermostat will switch power to the Control Box Cooling Fan. The Thermostat will interrupt power to the Cooling Fan when the Control Box temperature falls to 100°F + 3°.
Pole Main Fan Relay, the Cooling Fan Thermostat, the normally open Main Fan Switch, and the normally open Cool Down Thermostat (thermostat closes at 160°F and opens at 140°F). Closing the Main Fan Switch supplies 220 VAC through a 3A Fuse to the (normally open) Burner Switch, and to the control circuit Step Down Transformer (the transformer steps the voltage down to 120 VAC for the control circuit) 120 VAC is supplied to the coil of the Main Fan Relay The coil is energized, the normally open contacts close, supplying 220 VAC through one 10A Fuse to the Main Fan Motor. 120 VAC is also supplied to the 12.6 VAC Transformer, the Temperature Controller and the Conveyor Switch. Upon closure of the Fan Switch, 120 VAC is supplied to the primary of the 12.6 VAC Transformer. The Transformer steps the voltage down to 12.6 VAC (normally 13 to
Impinger I -–1000 Series Service Manual - International 6
14 VAC) with a center tap, and supplies power to the Time/Temp Display. The voltage from each leg of the Transformer's secondary to the center tap should be one half of the secondary voltage
BURNER CIRCUIT Closing the normally open Burner Switch supplies 220 VAC, through the gas
pressure-proving switch, and through the Main Fan Air Pressure Switch, to the Ignition Control. The combustion motor relay is energized, its normally open contacts now close, supplying120 VAC to the combustion motor. The normally open combustion air switch closes upon sensing air. After pre-purge period of between 30 and 60 seconds, the Ignition Transformer is energized and the Main Gas Valve is
energized. Ignition should now occur. TEMPERATURE CONTROL
CONVEYOR DRIVE (S/N4390-Q17170)
(Conveyor Drive Q171701 & Above See Page 9) (Time/Temp Display Q17171 & Above See Page 9)
TIME/TEMP DISPLAY(Q17171 & Above See Page 9
Closing the Fan Switch supplies (through the Step down Transformer) 120 VAC to
the Temperature Control Board. The 2.5K ohm Temperature Potentiometer is
adjusted to desired temperature. The Thermocouple will provide varying millivolts to
the Temperature Controller. The Temperature Controller supplies 120 VAC to the
Solenoid Valve at intermittent intervals to maintain desired temperature.
Closing the fan switch and the normally open conveyor switch supplies 120 VAC to
the Motor Control Board. AC volts are converted to DC volts and are supplied to the
Conveyor Motor at terminals A+ and A-. Adjustment of the Speed Control
Potentiometer (5,000 ohm 10 turn) will change resistance at terminals P1, P2, and
P3 varying the DC voltage to the Conveyor Motor. The speed of the conveyor motor
will increase or decrease as the DC voltage from the board increases or decreases
respectively. As the motor turns, it drives both the reducer gearbox and the tach.
generator. The tach. generator is a DC voltage generator which supplies a voltage to
the DC motor control board and is used as a reference for maintaining a constant
conveyor speed.
The Time/Temp. Display is energized when the Fan Switch is closed, supplying 120
VAC to the primary of the 12.6 volt Transformer. The secondary output of the
transformer, normally 13 to 14 VAC (depending on input), with a center tap, is
supplied to terminals 1,2, and 3 of the Time/Temp. Display. The center tap is
terminal 2. The display works on a balanced input and center tap voltage to each leg
must be 1/2 the total reading.
The speed side of the Time Temp. Display uses a slotted disc (cemented to tach.
coupling) to break the infra-red light beam of the optical switch (mounted on gear
motor) producing electrical pulses that are transmitted to the display. The display
converts these pulses into a read-out of minutes and seconds.
The temperature portion of the display uses a Thermistor Probe to sense oven
temperature. The thermistor outputs a resistance proportional to the oven
temperature. This resistance is then converted by the display into a temperature
reading.
SEQUENCE OF OPERTIONS 1032
MODEL 1032 - 380Y/220 VAC - 50 HZ - 3 PHASE
POWER SUPPLY Electrical Power to be supplied to the Oven by a five conductor service
Black conductor is Hot Red conductor is Hot Orange conductor is Hot White conductor is Dedicated Neutral Green conductor is Ground
MAIN FAN CIRCUIT Electrical power is permanently supplied through 3, 50A fuses to the normally open
contacts of the Mercury Contactor. Power is also supplied through one 10A fuse to
the normally open contact of the Main Fan Relay, through a 1A Fuse to the normally
open Double Pole Main Fan Switch, and to the normally open Cool-Down
Thermostat (thermostat closes at 160°F and opens at 140°F.) Closing the Main Fan
Switch supplies 220VAC to the primary of the control circuit Step Down Transformer.
(The transformer steps the voltage down to 120 VAC for the control circuit.) 120 VAC
is supplied to the coil of the Main Fan Relay. The coil of the relay is energized, the
normally open contacts close, energizing the Main Fan Motor. Closing the Main Fan
Switch also supplies power to the 12.6 VAC Transformer, the Control Box Cooling
Impinger I -–1000 Series Service Manual - International 7
Fan, and the Heat and Conveyor Switches. TRANSFORMER (12.6 VAC)
HEAT CIRCUIT Closing the Fan Switch and the normally open Heat Switch supplies 120 VAC
TEMPERATURE CONTROL
CONVEYOR DRIVE (S/N 4390 AND UP)
TIME TEMP DISPLAY The Time/Temp. Display is energized when the Fan Switch is closed, supplying 120
Upon closure of the Fan Switch, 120 VAC is supplied to the primary of the 12.6 VAC
Transformer. The Transformer steps the voltage down to 12.6 VAC (normally 13 to
14 VAC) with a center tap, and supplies power to the Time/Temp Display. The
voltage from each leg of the Transformer's secondary to the center tap should be
one half of the secondary voltage.
through the normally open Air Pressure Switch, and the normally closed Hi-Limit
Thermostat (manually re-settable, opens at 368°C) through the 3A Fuse, to the
Temperature Control Board, the coil of the Mercury Contactor, and to the Heat
Indicator Light.
When the Heat Switch is closed, 120 VAC is supplied to the Temperature Control.
The Temperature Control Potentiometer (2.5K ohm) is adjusted to desired
temperature. The Thermocouple will provide varying millivolts to the Temperature
Controller. The Temperature Controller switches the L2 line of the Contactor coil at
intermittent intervals to maintain desired temperature.
Closing the fan switch and the normally open conveyor switch supplies 120 VAC to
the Motor Control Board AC volts are converted to DC volts and are supplied to the
Conveyor Motor at terminals A+ and A-. Adjustment of the Speed Control
Potentiometer (5,000 ohm 10 turn ) will change resistance at terminals P1, P2, and
P3 varying the DC voltage to the Conveyor Motor. The speed of the conveyor motor
will increase or decrease as the DC voltage from the board increases or decreases
respectively. As the motor turns, it drives both the reducer gear box and the tach.
generator. The tach. generator is a DC voltage generator which supplies a voltage to
the DC motor control board and is used as a reference for maintaining a constant
conveyor speed.
VAC to the primary of the12.6 volt Transformer. The secondary output of the
transformer, normally 13 to 14 VAC (depending on input), with a center tap, is
supplied to terminals 1,2, and 3 of the Time/Temp. Display. The center tap is
terminal 2.The display works on a balanced input and center tap voltage to each leg
must be 1/2 the total reading.
The speed side of the Time/Temp. Display uses a slotted disc (cemented to tach.
coupling) to break the infra-red light beam of the optical switch (mounted on gear
motor) producing electrical pulses that are transmitted to the display. The display
converts these pulses into a read-out of minutes and seconds.
The temperature portion of the display uses a Thermistor Probe to sense oven
temperature. The thermistor outputs a resistance proportional to the oven
temperature. This resistance is then converted by the display into a temperature
reading.
SEQUENCE OF OPERATIONS / 1033, 1034, 1046, 1047
MODEL 1033 / 220 VAC - 50HZ / NATURAL GAS MODEL 1034 / 220 VAC - 50HZ / L.P. GAS MODEL 1046 / 240 VAC - 50HZ / NATURAL GAS MODEL 1047 / 240 VAC - 50HZ / L.P. GAS
POWER SUPPLY Electrical Power to be supplies to the oven by a three-conductor service.
Brown conductor is Hot
Blue conductor is Neutral
Green conductor is Ground CONTROL BOX AUTO COOL DOWN
MAIN FAN CIRCUIT Electrical power is permanently supplied to the normally open contacts of the oven
When the temperature in the Control Box reaches 120°F± 3°, the Cooling Fan
Thermostat will switch power to the Control Box Cooling Fan. The Thermostat will
interrupt power to the Cooling Fan when the Control Box temperature falls to
100°F±3°.
fan motor relay, the Cooling Fan Thermostat, and the normally open Oven Fan
Switch. Closing the oven fan switch supplies 220 VAC, through a 3 AMP Fuse, to the
primary of the Power Transformer (the transformer steps the voltage down to 120
VAC for the control circuit). 120 VAC is supplied to the Cooling Fan, the normally
open Conveyor Switch, the Electronic Temperature Control, and to the coil of the
Impinger I -–1000 Series Service Manual - International 8
oven start and cool down relay. Its normally open contacts close, supplying 220 VAC
to the Burner Switch and enabling the 20-minute Time Delay module. The 20-minute
Time Delay module supplies 120 VAC to the oven fan motor relay, these normally
open contacts now close, supplying 220 VAC to the Oven Fan Motor. TRANSFORMER(12.6V AC)
Upon closure of the Fan Switch, 120 VAC is supplied to the primary of the 12.6 VAC
Transformer. The Transformer steps the voltage down to 12.6 VAC (normally 13 to 14
VAC) with a center tap, and supplies power to the Time/Temp Display. The voltage
from each leg of the Transformer's secondary to the center tap should be one half of
the secondary voltage. BURNER CIRCUIT Closing the normally open burner switch supplies 220 VAC through the oven air
pressure switch, the gas inlet pressure switch, the normally closed high limit
thermostat (opens at 368°C) to the ignition control. The combustion motor is now
energized. The normally open burner blower air pressure switch closes upon sensing
air pressure. After a pre-purge period of 30-60 seconds, the main gas valve and the
spark generator are energized. Ignition should now occur. After proving the pilot
flame, and a 30 second delay, the gas control relay and the burner indicator lamp are
energized. TEMPERATURE CONTROL
Closing the Fan Switch supplies (through the Step Down Transformer) 120 VAC to
the Temperature Control Board. The Temperature Potentiometer is adjusted to
desired temperature. The Thermocouple will provide varying millivolts to the
Temperature Controller. The Temperature Controller supplies 120 VAC to the
Solenoid Valve at intermittent intervals to maintain desired temperature. (An
electronic flame monitor proves main flame operation in the 1033-1034 models) CONVEYOR DRIVE Closing the Oven Fan Switch supplies 120 VAC, through the Power Transformer, to
the normally open Conveyor Switch. Closing the Conveyor Switch supplies 120 VAC,
through a 3 AMP Fuse, to the primary of the Conveyor Control Transformer. The
secondary of this Transformer supplies 10 VAC and 29 VAC to the Conveyor Control.
The conveyor control supplies voltage pulses to the Conveyor Control. The Conveyor
Control Potentiometer varies the frequency of these pulses. The motor speed will
increase or decrease, as the frequency of the pulses increase or decrease
respectively. TIME TEMP DISPLAY Closing the Oven Fan Switch supplies 120 VAC, through the Power Transformer, to
the primary of the Time/Temp. Transformer. The secondary output of the
Transformers, 12.5 to 15 VAC with a center tap, is supplies to terminals 1, 2, and of
the Time/Temp. Display. The display works on a balanced input, and the center tap
voltage to each leg must be 1/2 the total reading.The speed side of the Time/Temp.
Display is supplied, by the Conveyor Control, with the frequency of the pulses to the
Conveyor Motor. This frequency is converted by the Time/Temp. Display into a read
out of minutes and seconds. NOTE: The Conveyor Control uses a sensor and
magnet, mounted on the Conveyor Motor that senses when the motor is not turning. If
the motor is not turning, the Time/Temp Display will show --:-- in the window. The
temperature portion of the display uses a Thermistor Probe to sense oven
temperature. The Thermistor outputs a resistance proportional to oven temperature.
This resistance is then converted by the Display into a temperature reading.
OR:
The temperature portion of the display uses a "J" type thermocouple to measure oven
temperature. The thermocouple generates D.C. millivolts proportional to oven
temperature. This millivolt reading is then converted by the display into a temperature
reading.
Impinger I -–1000 Series Service Manual - International 9
SEQUENCE OF OPERATIONS 1042 / 1043 / 1242 / 1243
MODEL 1042 - 240V - 50HZ - NATURAL GAS MODEL 1043 - 240V - 50HZ - L.P. GAS MODEL 1242 - 240V - 50HZ - NATURAL GAS/DUAL BELT MODEL 1243 - 240V - 50HZ - L.P.GAS/DUAL BELT
POWER SUPPLY Electrical Power to be supplied to the Oven by a three conductor service.
Black conductor is Hot Red conductor is Neutral
Green conductor is Ground CONTROL BOX AUTO COOL DOWN
MAIN FAN CIRCUIT Electrical power is permanently supplied to the normally open contacts of the Double
TRANSFORMER (12.6 VAC)
BURNER CIRCUIT Closing the Fan Switch and the normally open Burner Switch supplies 120 VAC
TEMPERATURE CONTROL
CONVEYOR DRIVE (S/N Q14790 & Below, 1200 series S/N Q14973 & Below, 1000 series)
(S/N Q14791 & Above, 1200 series S/N Q14974 & Above, 1000 series refer to Pg. 9)
When the temperature in the Control Box reaches 120°F + 3°, the Cooling Fan Thermostat will switch power to the Control Box Cooling Fan. The Thermostat will interrupt power to the Cooling Fan when the Control Box temperature falls to 100°F + 3°.
Pole Main Fan Relay, the Cooling Fan Thermostat, the normally open Double Pole Main Fan Switch, and the normally open Cool Down Thermostat (thermostat closes at 160°F and opens at 140°F). Closing the Main Fan Switch supplies 240 VAC through a 3A Fuse to the primary of the control circuit Step Down Transformer. The Transformer steps the voltage down to 120 VAC for the control circuit. 120 VAC is supplied to the coil of the Double Pole Main Fan Relay. The coil of the relay is energized. The normally open contacts now close, energizing the Main Fan Motor through one 10A Fuse. Closing the Fan Switch also supplies power to the Cooling Fan, the 12.6 VAC Transformer the Burner and Conveyor Switches. Upon closure of the Fan Switch, 120 VAC is supplied to the primary of the 12.6 VAC Transformer. The Transformer steps the voltage down to 12.6 VAC (normally 13 to 14 VAC) with a center tap, and supplies power to the Time/Temp Display. The voltage from each leg of the Transformer's secondary to the center tap should be one half of the secondary voltage.
through the Air Pressure Switch, to the Temperature Control Board, the normally open contacts of the Burner Motor Relay (Burner Motor Relay discontinued after S/N
14791) and the primary of the 24 VAC Transformer. The transformer's secondary supplies 24 VAC to the burner motor relay coil (the normally open contacts close within 30 seconds), and the normally open Centrifugal Switch. When the relay contacts close, the Burner Blower Motor is energized. As this motor reaches approx. 1,600 R.P.M its internal centrifugal switch closes, supplying 24 VAC to the Gas Control Valve. When the Gas Control Valve is supplied with 24 VAC, the pilot valve is energized, and the igniter circuit is energized. Ignition should now occur. After pilot flame is proven, the Main Gas Valve is energized. The Burner Indicator Light is also energized. Closing the Fan Switch and Burner Switch supplies 120 VAC to the Temperature Control Board. The 1K or 1000 ohm Temperature Potentiometer is adjusted to desired temperature. The Thermocouple will provide varying millivolts to the Temperature Controller. The Temperature Controller supplies 120 VAC to the Solenoid Valve at intermittent intervals to maintain desired temperature. Closing the fan switch and the normally open conveyor switch supplies 120 VAC to the Motor Control Board. AC volts are converted to DC volts and are supplied to the Conveyor Motor at terminals A+ and A-. Adjustment of the Speed Control Potentiometer (5,000 ohm 10 turn ) will change resistance at terminals P1, P2, and P3 varying the DC voltage to the motor. The speed of the conveyor motor will increase or decrease as the DC voltage from the board increases or decreases respectively. As the motor turns, it drives both the reducer gearbox and the tach. generator. The tach. generator is a DC voltage generator which supplies a voltage to the DC motor control board and is used as a reference for maintaining a constant conveyor speed.
Impinger I -–1000 Series Service Manual - International 10
TIME/TEMP DISPLAY(S/N Q14790 & Below, 1200 series S/N Q14973 & Below, 1000 series)
(S/N Q14791 & Above, 1200 series S/N Q14974 & Above, 1000 series refer to Pg.
9)
The Time/Temp. Display is energized when the Fan Switch is closed, supplying 120 VAC to the primary of the12.6 volt Transformer. The secondary output of the transformer, normally 13 to 14 VAC (depending on input), with a center tap, is supplied to terminals 1,2, and 3 of the Time/Temp. Display. The center tap is terminal 2. The display works on a balanced input and center tap voltage to each leg must be 1/2 the total reading. The speed side of the Time/Temp. Display uses a slotted disc (cemented to tach. coupling) to break the infra-red light beam of the optical switch (mounted on gear motor) producing electrical pulses that are transmitted to the display. The display converts these pulses into a read-out of minutes and seconds. The temperature portion of the display uses a Thermistor Probe to sense oven temperature. The thermistor outputs a resistance proportional to the oven temperature. This resistance is then converted by the display into a temperature reading.
Impinger I -–1000 Series Service Manual - International 11
SCHEMATIC / 1002, 1003
Impinger I -–1000 Series Service Manual - International 12
SCHEMATIC / 1006 TO SERIAL NUMBERS Q14279
Impinger I -–1000 Series Service Manual - International 13
SCHEMATIC / 1028, 1029, S/N Q19071 & BELOW
Impinger I -–1000 Series Service Manual - International 14
SCHEMATIC / 1028, 1029, S/N Q19078 & ABOVE
Impinger I -–1000 Series Service Manual - International 15
SCHEMATIC / 1030, TO S/N Q17170
Impinger I -–1000 Series Service Manual - International 16
SCHEMATIC / 1030, S/N Q17171 & ABOVE
Impinger I -–1000 Series Service Manual - International 17
SCHEMATIC / 1032. S/N Q19077 & BELOW
Impinger I -–1000 Series Service Manual - International 18
SCHEMATIC / 1032, S/N Q19078 & ABOVE
Impinger I -–1000 Series Service Manual - International 19
SCHEMATIC / 1033, 1034, 1046, 1047
Impinger I -–1000 Series Service Manual - International 20
SCHEMATIC / 1042, 1043, S/N Q14279 & BELOW
Impinger I -–1000 Series Service Manual - International 21
SCHEMATIC / 1042, 1043, S/N Q14280 & ABOVE
Impinger I -–1000 Series Service Manual - International 22
SCHEMATIC / 1228. 1229, S/N Q14790 & BELOW
Impinger I -–1000 Series Service Manual - International 23
SCHEMATIC / 1228, 1229, S/N Q14791 & ABOVE
Impinger I -–1000 Series Service Manual - International 24
SCHEMATIC / 1242, 1243
Impinger I -–1000 Series Service Manual - International 25
TROUBLESHOOTING GUIDE 1000 & 1200 / GAS OVENS
SYMPTOM POSSIBLE CAUSE EVALUATION
Oven fan will not run
NOTE:
No Main Fan Cool Down
No Control Box Cooling(For ovens equipped with Control Box Cooling Fan)
NOTE:
No automatic control box cooling (For ovens equipped with control box cooling fan)
Control box cooling fan continues to run Transformer, 24 VAC
Incoming Power Supply Check breakers/ Reset if required / Call Power Co.
if needed.
(Export Ovens) For some export ovens, there is a control circuit
step-down transformer. This transformer steps down supply voltage to 120 VAC. If main fan will not run, the secondary of this transformer must be checked for 120 VAC output. Check specific oven
model schematic for circuit location. Oven Fan Fuse(s) Check and/or Replace Fuse Holder Check and/or Replace Fan Switch Check continuity between switch terminals. Main Relay Check continuity to 120 VAC coil. Check for power
to relay coil (120 VAC). Check for 208/240 VAC to
relay terminals. Visually check for contact pull-in. Fan Motor Check for opens, shorts, or grounds. WITH
POWER OFF: Turn Fan Blade to check for locked
rotor. Capacitor Check for opens, shorts, or grounds. Cool Down Thermostat Check cool down thermostat (thermostat closes at
160°F and opens at 140°F). Check for power (120
VAC) at cool down thermostat. With the cool down
thermostat pre-heated, check for continuity. If
switch is open, replace. Main Fan Relay
(Export Ovens) Axial Cooling Fan
Incoming Power Supply Check breakers/Reset if needed. Check for
Cooling Fan Thermostat Check cooling fan thermostat (thermostat closes at
Axial Cooling Fan Check for 120 VAC to cooling fan, if present and
Cooling Fan Thermostat See "Cooling Fan Thermostat"
Check for 120 VAC to primary of transformer. Check for 24 VAC from secondary of transformer. If there is primary voltage, but no secondary voltage, replace transformer. Manual Gas Shut-off Valve Check to see that manual shut-off valve is open. Fan Switch Check to see that fan switch is "on". Main Oven Fan Check if main oven fan is operating. If not, refer to
Check for power to Main Fan Relay. Visually check
for contact pull in.
(For ovens equipped with a control circuit step-
down transformer, the supply voltage for the
cooling fan is 240 VAC.)
WITH POWER OFF: check for locked rotor. Check
for power (120 VAC) to cooling fan. If 120 VAC is
present at the fan motor and the fan does not run,
replace fan assembly.
incoming power (120 VAC)at cooling fan
thermostat.
120°F and opens at 100°F). With cooling fan
thermostat pre-heated, check for continuity. If
switch is open, replace.
fan does not run, replace fan.
Check for adequate gas supply to oven.
"Oven fan will not run". Page 26.
Impinger I -–1000 Series Service Manual - International 26
NOTE:
For ovens with Johnson Controls Ignition Control
(For ovens with Honeywell Ignition control, See Pg. 28)
Burner Switch Check for 120 VAC to neutral on both sides of
switch. If switch is closed and 120 VAC is present
on one side only, replace the switch. Air Pressure Switch Check for 120 VAC on both sides of switch. If
voltage present on one side only, check for air tube
blockage. Adjust air switch. If above fails, replace
air pressure switch.
(Model 1004 & 1005) For oven models 1004 and 1005, there is a 1 Amp
fuse located between the 24 VAC output from the
transformer and the coil of the burner motor relay. If
there is 24 VAC output from the transformer, but no
burner motor relay action, check fuse and fuse
holder. Replace as necessary. Burner Motor Relay Delete burner motor relay refer to page 55. Burner Blower Motor Check for 120 VAC supply to burner blower motor.
If 120 VAC is present and motor does not run,
replace motor. WITH POWER OFF: turn blower
wheel to check for locked rotor. Centrifugal Switch of Burner Blower Motor
Check for 24 VAC output from secondary of
transformer. If voltage is present, check for 24 VAC
at pin 6 and the ground bar on ignition control and
valve assembly. If the burner blower motor is
running and there is no voltage at pin 6 and the
ground bar on the ignition control valve, replace the
burner blower motor. Ignition Control and Valve Assembly
Check for 24 VAC supply to the ignition control and
valve assembly at pin 6 and the ground bar. If
voltage is present, check for 24 VAC across pin #1
and the ground bar (pilot valve). If voltage is not
present, replace electronic control package. If the
pilot valve is energized, check to see that the high
voltage ignitor circuit is also energized. To check,
disconnect the ignitor lead from the bottom of
ignition control. Place female terminal of ignitor
lead approximately 1/8" from terminal post on
ignition control. Spark should jump the 1/8" gap. If
no spark is present, replace ignition control. No Pilot If the ignition control is supplied with 24 VAC, and
the pilot valve (internal to valve assembly) and
ignitor circuits are energized, visually check for pilot
flame. This may be done by opening the small
inspection door on the end of the burner, or by
opening the main oven door and looking under the
lower finger housings on the right side of the oven.
If no pilot flame is visible, check the following. Pilot Shut-off Valve Check to see that pilot shut-off valve is open (shut-
off valve is located between ignition control and
valve assembly and burner.) Pilot Tube Check for gas pressure at pilot tube. Disconnect
pilot tube at burner and connect manometer to pilot
tube. If no gas pressure is present, check for
blockage in pilot tube or pilot shut-off valve. If these
are clear, and there is gas supplied to the oven,
replace the ignition control and valve assembly. Pilot Orifice If there is gas pressure at the pilot tube, check the
pilot orifice for obstructions. Replace as need Burner Ignitor Check the burner ignitor head for any obstructions,
also check for frayed or broken wire, any type of
damage to spark gap (.100 in. 2.5 m.m.) If there is
visible damage, replace ignitor assembly.
Impinger I -–1000 Series Service Manual - International 27
Pilot flame but no main flame
For ovens with Honeywell ignition control
No Pilot
Flame Sensor (There should be a visible pilot flame at this time.)
To check for proper flame sensor operation,
connect a digital multimeter (capable of measuring
D. C. microamperes) in series between the flame
sensor wire (normally connected to terminal #4)
and terminal #4. NOTE: This is a current
measurement and the meter must be connected in
series. This procedure is for checking the pilot
flame only. Remove main valve wire (Red) from
terminal #3 on ignition control. With a visible pilot
flame, the current readings should be as follows:
Johnson G-65 control, 0.2 micro amp. D.C.
minimum/Johnson G-60 control, 0.7 micro amp.
D.C. minimum. If these values are not achieved,
replace flame sensor. Also check for any type of
damage to flame sensor wire and connections. Ignition Control and Valve Assembly
Centrifugal Switch of Burner Blower Motor
NOTE:
Ignition Control Check for 24 VAC supply to ignition control at
Pilot Shut-off Valve
Pilot Tube Check for gas pressure at pilot tube. Disconnect
Pilot Orifice If there is gas pressure at the pilot tube, check the
If there is a pilot flame, and there is sufficient micro
amp. current at terminal #4, check for 24 VAC
that the main valve (internal to valve assembly) has
opened. Connect a manometer to the manifold gas
pressure tap located on the back side of the ignition
control and valve assembly. If no gas is present,
replace ignition control and valve assembly.
Check for 24 VAC output from secondary of
transformer. If voltage is present, check for 24 VAC
at terminals marked "24V" and "24V gnd" on
Ignition Control. If the Burner Blower Motor is
running and there is no voltage at terminals 24V
and 24V gnd on the ignition control, replace the
Burner Blower Motor.
These Ignition Controls have a 30 second pre-
purge(Delay) and a 15 second lock-out time – The
Ignition Control will try for ignition for 15 seconds
and then shut-off. To Re-try for ignition, turn off
burner switch, wait 30 seconds and re-try ignition.
terminals "24V" and "24V gnd". If voltage is
present, check for 24V at terminal "P.V. (Pilot
Valve) and "gnd". If voltage is not present, replace
Ignition Control. If the pilot valve is energized,
check to see that the high voltage ignitor circuit is
also energized. To check, disconnect the ignitor
lead from the ignition control. Place the terminal of
ignitor lead approximately 1/8" from terminal post
on Ignition Control. Spark should jump the 1/8"
gap. If no spark is present, replace ignition control.
If the ignition control is supplied with 24 VAC and
the pilot valve (in gas valve) and ignitor circuits are
energized, visually check for pilot flame. This may
be done by opening the small inspection door on
the end of the burner, or by opening the main oven
door and looking under the lower finger housing in
the right side of the oven.
If no pilot flame is visible, check to see that the pilot
shut-off valve is open (shut-off valve is located
between gas valve and burner).
pilot tube at burner and connect manometer to pilot
tube. If no gas pressure is present, check for
blockage in pilot tube or pilot shut-off valve.
pilot orifice for obstructions. Replace as needed.
Impinger I -–1000 Series Service Manual - International 28
Burner Ignitor Check the burner ignitor head for any obstructions,
also check for frayed or broken wire, any type of
damage to spark gap (.100 in. 2.5 mm) If there is
visible damage, replace ignitor assembly.
Pilot flame but no main flame
Spark Ignitor (Flame Sensor) (There should be a visible pilot flame at this time).
NOTE: The Honeywell Ignition Control uses the
spark ignitor as the flame sensor. If spark
continues, check for proper ground connections at
Ignition Control. Check pilot orifice for any partial
blockage. If the above checks OK, replace ignition
control. If spark stops when pilot is lit, check for 24
VAC across M.V. - M.V/ P.V. terminals, if voltage is
not present, replace ignition control. If voltage is
present at terminals M.V. - M.V./P.V., the indicator
light on the control panel should be on, verify that
the main valve has opened, connect manometer to
manifold gas pressure tap (located on the back
side of the gas valve). If no gas is present, replace
gas valve.
Red Indicator Light is on, but no main flame(For ovens with
mechanical thermostat) (For ovens with Electronic Temperature Control)
Temperature Control Valve (Robert Shaw) Main Orifice Check for blockage of main orifice. If there is no
Temperature Control Potentiometer
Check for gas supply at temperature control. Check
for temperature control set above 300°F.
blockage to the main orifice, replace the
temperature control.
Check for 120 VAC across L1 and L2on
temperature control board. Potentiometer (1000
ohm,1 turn) WITH POWER OFF: check ohms
across red and black leads, the ohm reading
should be 0 to1000 ohms as the dial is turned.
From green to red, the reading should be 1000
ohms steady throughout the full turn of the dial.
NOTE: Ovens S/N Q18037 and above, the potentiometer is internal to temperature control. Proceed to next component.
Thermocouple Probe Remove thermocouple leads from the temperature
control board, and measure the millivolt output of
these leads. Refer to chart on page 59 in the
adjustment section for proper readings. Temperature Control Turn temperature control dial to full "on" position.
Measure for 120 VAC across terminals "N.O." and
"L2", if voltage is not present; replace control. Solenoid Valve If voltage is present at terminals "N.O." and "L2",
check for voltage at solenoid valve. If voltage is
present, listen for valve to open and close. Also,
check for opens and shorts in coil. If solenoid valve
is defective, replace
Intermittent Heating Both the main fan motor and burner blower motor
are equipped with thermo-protection and will cease
to operate when not cooled properly. This can
cause the units to cycle on and off intermittently.
Also, most of the problems listed under "oven will
not heat" can cause intermittent failures.
For continuing intermittent problems, a series of test lights may be made and installed in the ovens. The lights will allow the customer to advise the service technician a trouble code when the oven fails.
The lights should be connected in the following manner:
Light#l attached in 120VAC line after Air Pressure Switch. Light#2 attached after 120VAC contacts of Burner Motor Relay (or, refer to Bulletin #028 for Relay Removal). Light#3 in 24VAC Burner Transformer Secondary.
Impinger I -–1000 Series Service Manual - International 29
Light#4 in 24VAC at terminal #6 of Johnson control valve or "24V" on Honeywell Control. Light#5 in 24VAC at terminal #1 of Johnson control valve or "PV" on Honeywell Control. Light#6 in 24VAC at terminal #3 of Johnson control valve or "MV" on Honeywell Control. CODE: All lights off - lights of main power, main fan off, air pressure switch out. 1 on 2 off 3 on 4 off 5 off 6 off - Burner Motor Relay bad. 1 on 2 on 3 on 4 off 5 off 6 off - Burner Motor Centrifugal Switch bad. 1 on 2 on 3 on 4 on 5 off 6 off - Ignition Control bad. 1 on 2 on 3 on 4 on 5 on 6 off - Pilot Shield missing or warped, Flame Sensor bad, Pilot
- Orifice plugged, or Gas Valve bad. 1 on 2 on 3 on 4 on 5 on 6 on - Unit still not working Main Orifice plugged, Gas Valve bad,
- Temperature Control bad.
- However, Main Orifice would not be intermittent problem.
Impinger I -–1000 Series Service Manual - International 30
Loading...
+ 82 hidden pages