Lincoln 1164-000-EA, 1155-000-EA, 1154-000-EA User Manual

SERVICE MANUAL
(INTERNATIONAL)
IMPINGER ADVANTAGE DIGITAL SERIES
MODEL 1154-000-EA, 1155-000-EA,
WITH PUSH BUTTON CONTROLS
Lincoln Foodservice Products, LLC
1111 North Hadley Road
Fort Wayne, Indiana 46804
United States of America
Phone : (800) 374-3004
U.S. Fax: (888) 790-8193 • Int’l Fax: (260) 436-0735
Technical Service Hot Line
(800) 678-9511
www.lincolnfp.com
1100ExAdDig REV: 11/8/07
SEQUENCE OF OPERATIONS
IMPINGER II ADVANTAGE
SERIAL NUMBER 2038616 AND ABOVE
(OVENS WITH PUSH BUTTON CONTROLS)
MODEL 1154-000-EA NAT. GAS 230VAC 50 HZ. 1 PHASE MODEL 1155-000-EA LP GAS 230VAC 50 HZ. 1 PHASE
POWER SUPPLY Electrical power to be supplied to the oven by a three conductor service. CONTROL BOX AUTO COOL DOWN
MAIN FAN CIRCUIT Power is permanently supplied, through a 10 amp oven fuse, through a normally
BURNER CIRCUIT Closing the oven fan switch supplies line voltage through the normally open gas
IGNITION CONTROL The ignition control switches line voltage to the combustion blower motor. The
TEMPERATURE CONTROL Closing the oven fan switch supplies line voltage to the primary of the control
CONVEYOR DRIVE Closing the oven fan switch supplies line voltage to the conveyor motor and to the
When the temperature in the control box reaches 120°F ± 3°F (48.9°C ± 1.7°C), the cooling fan thermostat will switch power to the control box cooling fan. The thermostat will interrupt power to the cooling fan when the control box temperature falls to 100°F ± 3°F (37.8°C ± 1.7°C).
closed control box hi-limit thermostat (opens at 140°F, 60°C), to the normally open double pole oven fan switch and to the cooling fan. Closing the oven fan switch supplies line voltage to the main fan motor. Closing the main fan switch also supplies voltage to the cooling fan, the primary of the control transformer, the conveyor motor, and the burner system.
pressure switch (located in the gas valve and closed when gas pressure is present), through the normally open air pressure switch (closed by the air pressure from the main fan), through the normally closed oven cavity hi-limit thermostat (opens at 662°F, 350°C), and to the ignition control.
combustion air pressure switch swit ches from normally closed to normally open upon sensing air pressure in the burner housing. After a pre-purge period of between 30 and 60 seconds, the spark generator is energized, the main gas valve and the burner pilot light are energized, and ignition should now occur.
transformer. Secondary voltage, 24VAC, is supplied to the oven control. The oven control is set to desired temperature. The thermocouple will provide varying millivolts to the oven control. The oven control supplies line voltage to the temperature regulation valve at intermittent intervals to maintain the desired temperature. The display on the oven control will indicate when the temperature regulation valve is energized. NOTE: The display also indicates oven temperature.
primary of the control transformer. Secondary voltage, 24VAC, is supplied to the oven control. Setting the oven control to the desired time outputs voltage, through a reversing switch, to the conveyor motor. NOTE: The conveyor system uses a hall effect sensor and magnet to prove operation of the conveyor motor. If the conveyor motor is not running, “BELT JAM” is indicated on the display.
2
Impinger II – Advantage Digital Service Manual - International
SEQUENCE OF OPERATIONS
IMPINGER II ADVANTAGE
SERIAL NUMBER 2038616 AND ABOVE
(OVENS WITH PUSH BUTTON CONTROLS)
MODEL 1164-000-EA 400/230VAC 50HZ. 3 PHASE
POWER SUPPLY Electrical power to be supplied to the oven by a four conductor service.
Brown conductor is hot. Black conductor is hot. Black conductor is hot. Green conductor is ground.
MAIN FAN CIRCUIT Power is permanently supplied, through the 10 amp oven fuse, through the
normally closed control box hi-limit thermostat (opens at 140°F, 60°C), to the normally open oven fan switch. Power is also supplied to the normally open cooling fan thermostat. Closing the oven fan switch supplies line voltage to the main fan motor, the cooling fan, the primary of the control transformer and to the oven control.
HEAT CIRCUIT Closing the oven fan switch supplies line voltage, through the normally open air
pressure switch (closed by air pressure from the main fan) to the oven control. Line voltage is also supplied to the primary of the control transformer. Secondary voltage, 24VAC, is supplied to the oven control. The oven control is set to desired temperature. The thermocouple will provide varying millivolts to the oven control. The oven control supplies line voltage to the coil of the contactor at intermittent intervals to maintain the desired temperature. The display on the oven control will indicate when the contactor is energized. NOTE: The display also indicates oven temperature.
CONVEYOR CONTROL Closing the oven fan switch supplies line voltage to the conveyor motor and to the
primary of the control transformer. Secondary voltage, 24VAC, is supplied to the oven control. Setting the oven control to the desired time outputs voltage, through a reversing switch, to the conveyor motor. NOTE: The conveyor system uses a hall effect sensor and magnet to prove operation of the conveyor motor. If the conveyor motor is not running, “BELT JAM” is indicated on the display.
Impinger II – Advantage Digital Service Manual - International
3
SCHEMATIC DIAGRAM
MODEL 1154-000-EA, 1155-000-EA
SERIAL NUMBER 2038616 TO 2045407
4
Impinger II – Advantage Digital Service Manual - International
SCHEMATIC DIAGRAM
MODEL 1154-000-EA, 1155-000-EA
SERIAL NUMBER 2045408 AND ABOVE
Impinger II – Advantage Digital Service Manual - International
5
SCHEMATIC DIAGRAM
MODEL 1164-000-EA
SERIAL NUMBER 2038616 AND ABOVE
6
Impinger II – Advantage Digital Service Manual - International
SCHEMATIC DIAGRAM
MODEL 1164-000-EA
SERIAL NUMBER 2053336 AND ABOVE (RoHS Compliant)
Impinger II – Advantage Digital Service Manual - International
7
TROUBLESHOOTING GUIDE
IMPINGER II ADVANTAGE
SERIAL NUMBER 2038616 AND ABOVE
(OVENS WITH PUSH BUTTON CONTROLS)
MODEL 1154-000-EA NAT. GAS 230VAC 50 HZ. 1 PHASE MODEL 1155-000-EA LP GAS 230VAC 50 HZ. 1 PHASE
REFER TO PROPER SCHEMATIC FOR IDENTIFIED COMPONENTS
SYMPTOM POSSIBLE CAUSE EVALUATION Oven fan will not run Incoming power supply Check breaker, reset if required. Check power plug to
be sure it is firmly in receptacle. Measure incoming
power, call power co. if needed. Fuse, 10 amp Check, replace if necessary. Fuse holder Check, replace if necessary. Hi-limit thermostat, control box Check for voltage on both sides of switch. Terminals are
normally closed. If open, reset and test oven for proper
operation. If thermostat will not hold, and control box
temperature is not exceeding 140°F (60°C), replace
thermostat. Switch, main fan With power off, check continuity between switch
terminals. Replace as needed. Motor, main fan Check for opens, shorts or grounds. With power off, turn
fan blade to check for locked rotor. Capacitor Check for shorts or grounds.
WARNING: Capacitor has a stored charge, discharge
before testing. No control box cooling Incoming power supply Check breaker, reset if required. Check power plug to
be sure it is firmly in receptacle. Measure incoming
power, call power co. if needed. Switch, main fan With power off, check continuity between switch
terminals. Replace as needed. Cooling fan Line voltage should now be at the cooling fan. If voltage
is present, check motor for opens, shorts or grounds.
With power off, check for locked rotor. No automatic control box cooling
Cooling fan thermostat Check the cooling fan thermostat (thermostat closes at
Cooling fan Line voltage should now be at the cooling fan. If voltage
Oven will not heat Serial Number 2045407 & Below Main fan If not operating, refer to “Oven fan will not run”. Gas pressure switch This switch is located inside the gas valve and should
Incoming power supply Check breaker, reset if required. Check power plug to
be sure it is firmly in receptacle. Measure incoming
power, call power co. if needed.
120°F and opens at 100°F). With the cooling fan
thermostat pre-heated, check for continuity. If
thermostat is open, replace cooling fan thermostat.
is present, check motor for opens, shorts or grounds.
With power off, check for locked rotor.
Gas supply Check for adequate gas supply and be sure that the
manual gas shut off valve is open. Also check flexible
gas line connection.
close when gas pressure is present.
WITH POWER OFF: Remove 3 prong plug (on gas
valve) and measure continuity between terminals 2 and
3. If no continuity, check the following: Proper gas
pressure supply to gas valve as marked on the oven
specification plate. Check for proper adjustment of the
gas pressure switch, 10 for Nat. gas, 27 for LP gas or
4.5 for town gas. Check the filter in gas valve for
8
Impinger II – Advantage Digital Service Manual - International
blockage or damage. If above checks are okay, but
pressure switch is still not closed, replace gas valve. Air pressure switch Check air switch terminals for supply voltage to
terminals NO2 and COM. If voltage is present on one
side only, check for air tube blockage or misalignment.
If these are okay, adjust air pressure switch or replace
if necessary. Oven cavity hi-limit thermostat
Terminals are normally closed, opens at 660°F (350°C).
If open, reset and test oven for proper operation. If
thermostat will not hold for maximum oven temperature,
and oven is not exceeding control setting, check for
proper location of capillary bulb in its spring holder. If
above checks are okay, replace hi-limit thermostat. Ignition control Check for proper supply voltage to ignition control.
Check for proper voltage to the burner blower motor.
This can be checked at motor connecting plug
terminals 2 and 5. If voltage is present, proceed with
next step, if not, wait 30 seconds, push reset button
and try to restart. If this fails, check wires from
thermostat and burner blower motor to the ignition
control. If the above checks okay, replace ignition
control. Burner blower motor Check for supply voltage to motor. WITH POWER OFF:
Turn blower wheel to check for locked rotor. If supply
voltage is present at motor connecting plug terminals 2
and 5, and motor does not run, replace burner blower
motor. Air pressure switch
(burner blower)
Check for proper supply voltage switching from “NC” to
“NO” on ignition control. Check for air pressure switch
adjustment, air tube blockage or misalignment. If these
adjustments fail, replace air pressure switch. Spark generator A pre-purge time of 30 to 60 seconds occurs after
burner blower motor starts. Check for supply voltage at
spark generator. If voltage is not present, check reset
button for ignition control. If voltage is still not present,
replace ignition control. If there is input voltage to the
spark generator, but there is no high voltage output,
replace the spark generator. Igniter/sensor assembly Check this assembly for visible damage. Replace as
needed. If there is no visible damage, check for voltage
supply to igniter/sensor assembly. If there is voltage
supplied to the igniter/sensor, but there is no spark,
replace igniter/sensor assembly. Gas valve Gas valve should open when proper supply voltage is
present. If there is no voltage present, check reset
button on ignition control, and all connections for
tightness. If there is still no voltage to gas valve,
replace the ignition control. If there is voltage to the gas
valve, check for gas pressure at the gas pressure tap
(located in the gas piping just prior to the burner). If
there is no gas pressure, replace the gas valve. Flame will not stay on Flame sensor To check for flame sensor operation, connect a digital
multimeter (capable of measuring DC microamps)
between the flame sensor wire and terminal #1 on the
ignition control. Sensor current is to be 3 microamps,
minimum. If these readings are not achieved, replace
igniter/sensor assembly. Also check for any type of
damage to flame sensor wire and connections.
NOTE: The DC microamp test must be conducted with
the oven in low flame (bypass) operation.
Impinger II – Advantage Digital Service Manual - International
9
Power supply Set the temperature to the lowest temperature setting.
If there is sufficient microamp current, but the flame will
not stay lit, check for proper polarity of the power
supply. Ignition control If there is sufficient microamp current, and there is
proper polarity of the power supply, but the burner will
not stay lit, check the reset button on the ignition
control. If the above test is okay, replace the ignition
control. Oven will not heat Serial Number 2045408 & Above
Gas supply Check for adequate gas supply and be sure that the
manual gas shut off valve is open. Also check flexible
gas line connection. Main fan If not operating, refer to “Oven fan will not run”. Air pressure switch Check air switch terminals for supply voltage to
terminals C and NO. If voltage is present on one side
only, check for air tube blockage or misalignment. If
these are okay, adjust air pressure switch or replace if
necessary. Oven cavity hi-limit thermostat
Terminals are normally closed, opens at 350°C (660°F).
If open, reset and test oven for proper operation. If
thermostat will not hold for maximum oven temperature,
and oven is not exceeding control setting, check for
proper location of capillary bulb in its spring holder. If
above checks are okay, replace hi-limit thermostat. Ignition control Check for proper supply voltage to ignition control.
Check for proper voltage to the burner blower motor.
This can be checked at motor connecting plug terminal
5 and Neutral. If voltage is present, proceed with next
step, if not, wait 30 seconds, push reset button and try
to restart. If this fails, check wires from burner blower
motor to the ignition control. If the above checks okay,
replace ignition control. Burner blower motor Check for supply voltage to motor. WITH POWER OFF:
Turn blower wheel to check for locked rotor. If supply
voltage is present at motor connecting plug terminal 5
and Neutral, and motor does not run, replace burner
blower motor. Air pressure switch
(burner blower)
Check for proper supply voltage switching from “NC” to
“NO” on ignition control. Check for air pressure switch
adjustment, air tube blockage or misalignment. If these
adjustments fail, replace air pressure switch. Ignition control A pre-purge time of 30 to 60 seconds occurs after
burner blower motor starts. Check for high voltage
spark output from the ignition control. If there is no high
voltage spark output, check reset button for ignition
control. If there is still no high voltage output, replace
the ignition control. Igniter/sensor assembly Check this assembly for visible damage. Replace as
needed. If there is no visible damage, check for voltage
supply to igniter/sensor assembly. If there is voltage
supplied to the igniter/sensor, but there is no spark,
replace igniter/sensor assembly. Gas valve Gas valve should open as the ignition control generates
the high voltage spark. Place manometer on the
pressure tap fitting (located in the gas piping just prior
to the burner manifold) and check for gas pressure. If
valve does not open, check reset button on ignition
control, and all connections for tightness. If there is still
no gas pressure, remove the ignition control from the
gas valve. Check the coils of the gas valve for opens or
10
Impinger II – Advantage Digital Service Manual - International
Loading...
+ 22 hidden pages