Suzhou Lily Tech. CO., Ltd.
Page 4, Total 7 Pages
Cool mode【t0 = C】
If Room temp. ≥ Set temp. +【t1】, and Temp. Output has stopped for【t2】, then Temp. Output will be energized.
If Room temp. ≤ Set temp., then Temp. Output will be de-energized.
Over hot protection
If Room temp. ≥ Set temp. +【t4】, then output R1 will be energized.
If Room temp. ≤ Set temp. +【t4】-【t5】, then output R1 will be de-energized.
This protection function is only effective in heat mode.
If【t4】=【t5】= 0.0, disable the protection function.
Humidity control
Humidify mode 【h0 = H】
If Room humidity ≤ Set humidity (HP) -【h1】, and Humi. Output (R2) has stopped for【h2】, then Humi. Output will be
energized.
If Room humidity ≥ Set humidity, then Humi. Output will be de-energized.
Dehumidify mode【h0 = P】
If Room humidity ≥ Set humidity +【h1】, and Humi. Output has stopped for【h2】, then Humi. Output will be energized.
If Room humidity ≤ Set humidity, then Humi. Output will be de-energized.
Over wet protection
If Room humidity ≥ Set humidity +【h4】, then output R1 will be energized.
If Room humidity ≤ Set humidity +【h4】-【h5】, then output R1 will be de-energized.
This protection function is only effective in humidify mode.
If【h4】=【h5】= 0.0, disable the protection function.
Timer output R4 and R5
R4 and R5 are controlled by parameter【u0】,【u1】and【u2
】
.
R4 and R5 will be energized for【u1
】
time alternatively. A period includes an R4 energized and an R5 energized.
There is a counter counting the times of the period. Every time after the power supplied, the counting value is reset to zero.
keeping 【S】and【▼
】
depressed simultaneously will show the counting value for 3 seconds.
If 【u2】> 0, when the counting value reaches 【u2
】
, R4 and R5 will stop energized, and display and will blink.
If 【u2
】
is set to zero,R4 and R5 will never stop energized.
Forced energized manually:
Keeping【▲
】
depressed for 2 seconds makes R5 being energized, until the key is released.
Keeping【▼
】
depressed for 2 seconds makes R4 being energized, until the key is released.
R4 and R5 could be used for incubator egg tray control.
Alarm
High temp. alarm: if Room temp. ≥ Set temp. (TP) +【t6】, display “tHi”. If【t6】= 0.0, the function disable.
Low temp. alarm: if Room temp. ≤ Set temp. -【t7】, display “tLo”. If【t7】= 0.0, the function disable.
High humidity alarm: if Room humidity ≥ Set humidity (HP) +【h6】, display “hH”. If【h6】= 0.0, the function disable.
Low humidity alarm: if Room humidity ≤ Set humidity -【h7】, display “hL”. If【h7】= 0.0, the function disable.
Sensor
The Room temp. can be calibrated. If Room temp. is 0.2℃ lower than real temp., set 【t3】= 0.2.
The Room humidity can be calibrated. If Room humidity is 2%RH higher than real, set 【h3】= -2.
When sensor fails, the Temp. and Humi. Output (R3, R2) will not be energized, and “E01” will display.
Note: do not plug in/off the sensor when power supplied.