Lilytech ZL-7801C Instruction Manual And User Handbook

1st
ZL-7801C
ZL-7801C
Intelligent
Intelligent
Controller
Controller
Instruction
Instruction
Manual
Feature
ZL-7801C is intelligent temperature and humidity controller, adopt compact design and IP65 level front panel, convenient
operation and easy installation. It used for artificial chamber, greenhouses, incubator and stores humidity and temperature control.
Technical Specification
Power Supply: AC185 ~ 245V 50HZ Input Signal:A temperature and humidity Length: 1.5m
Setting Range:5 95 RH / -2060 Load Current: R1 R3 load current 10A/250Vac,R2load current
16A/250Vac 、 R4 、 R5 load current 3A/250Vac
(Resistive load)
Working Temperature:-206010 90 RH (Without dewing) Protection Degree: IP65 (front panel )
Whole machines dimension: 78* 34.5* 71mm Case: PC + ABS Fire Proof
Drilling template: 71* 29mm
Display indication
Display Sign Instruction
Eco mode:When 30 seconds without buttons, digital tube display brightness to reduce power consumption.
Icon
FunctionOnOff
Blinking
Temp. Load
R3
On
Off
Load protecting delay
Cooling
Cooling
Not cooling
Set cooling temp.
Heating
Heating
Not heating
Set heating temp.
Humidity load
(R2)
On
Off
Load protecting delay
HumidifyOnOff
Set humidify humidity
Dehumidify
On
Off
Set dehumidify humidity
Repairing
----
No fault
Faulty
Warning
----
No Warning
Warning
Temp. display
Display
Not display
Set temperature, warning
Humidity
display
Display
Not display
Set humidity, warning
E1
Fault
----
----
Sensor fault
E2
Fault
----
----
Dewing alarm
E3
Fault
----
----
Temperature exceed up limit
E4
Fault
----
----
Temperature exceed down limit
E5
Fault
----
----
Humidity exceed up limit
E6
Fault
----
----
Humidity exceed down limit
UnL
In
Restore Defaults
----
----
2nd
Key Operation
Temperature and humidity setting
KeepingSpressed for 3s to enter temperature and humidity setting mode, digital shows set temperature.
PressPchoose humidity and temperature value circular, pressorchange the value(Keepingor
pressed, it will be adjusted quickly)
After setting, press〖S〗to exit and saving parameters. Do not press any key for 30 seconds; the device will leave the set mode
without saving the set data.
Set system parameters
KeepingPpressed for 3s to enter parameters setting mode, digital shows parameter code, at the same time pressor
to choose parameter code.
PressSto shows its value. Pressorto set its value.
Keep depressingPfor 3 seconds, the set parameters will be saved, the mode exits.
If do not press any key for 30 seconds, the mode will exit without saving all the set data.
ZL-7801C Parameter code and setting instruction:
No
Paramete
r code
Function
Setting
Range
Note
Factory
Setting
01
U10
Cooling/Heating
C/H
C:CoolingH:Heating
C
02
U11
Temperature
difference
0.1 ~ 20
2
03
U12
Temperature load time
delay protection
0 ~ 30min
3
04
U13
Temperature correct
-9.9~+9.9℃0
05
U20
Humidification/
Dehumidity
H/P
H:HumidificationP
Dehumidity
P
06
U21
Humidity difference
0.1 ~ 20 %
5
07
U22
Humidity load time
delay protection
0 ~ 30min
3
08
U23
Humidity correct
-9.9~+9.9%
0
09
U40
Timing 1 unit 1
0 ~ 2
0:sec1:min2:hour
1
10
U41
Timing 1 Load 1
1 ~ 9999
120
11
U42
Timing 1 unit 2
0 ~ 2
0:sec1:min2:hour
1
12
U43
Timing 1 Load 2
1 ~ 9999
120
13
U45
Timing 2 unit 1
0 ~ 2
0:sec1:min2:hour
1
14
U46
Timing 2 Load 1
1 ~ 9999
120
15
U47
Timing 2 unit 2
0 ~ 2
0:sec;1:min;2:hour
1
16
U48
Timing 2 Load 2
1 ~ 9999
120
17
U50
Temp. And humidity
display delay
1 ~ 30
Normal display no
warning
2
18
U60
Timing 2
mutifunctional
1 ~ 3
1,timing, 2,timing
protection
1
19
U61
Upper limit
temperature
-20 ~ 120 ℃
120
20
U62
Lower limit
-20 ~ 120 ℃
-20
3rd
temperature
21
U63
Upper limit humidity
0 ~ 100 %
100
22
U64
Lower limit humidity
0 ~ 100 %
0
23
U99
Passwords
0000 ~ 9999
0000:no passwords
0000
Control function instruction
Temperature control
Cooling control:
When the temperature≥【setting temp.】+【temperature difference】,and temperature load (R3) stop time meet【temp. load
delay protection】,temp. Load on;
When the temperature≤【setting temp.】,temp. Load (R3) off;
Heating control:
When the temperature≤【setting temp.】-【temperature difference】,and temperature load stop time meet【temp. Load delay
protection】, temp. Load (R3) on;
when the temperature≥【setting temp.】, temp. Load (R3) off.
Humidity control
Dehumidifition control
when humidity ≥【setting humidity】+【humidity difference】, and humidity load (R2) stop time meet【humidity delay load
protection】, humidity load on
when humidity ≤【setting humidity】, humidity load (R2) off
Humidification control
When humidity ≤【setting humidity】-【humidity difference】, and humidity load (R2) stop time meet【humidity delay load
protection】, humidity load (R2) on
when humidity≥【setting humidity】, humidity load (R2) off
Dewing warning
When humidity get to dewpoint, after【dewing warning delay】controller enter dewing warning state. If【dewing warning way
is C, digital shows”E2” alarm, humidity load output stop, warning output (R1) on. If【dewing warning way】is V, digital
shows”99.9%”alarm, still output.
Timed control
Timing circle control:
When enter timing load 1 timing 1, timing load 1(R5) on, timing load 2 (R4) off.
When enter timing load 1 timing 2, timing load 2 (R4) on, timing load 1 (R5) off.
When enter timing on 2, timing load 3(R1) on.
When enter timing off 2, timing load 3(R1) off.
Load delay protection
Controller power is on, all load output (R2 R3) run after load delay protection
Running process, the temperature and humidity load (R2 R3) after downtime must be after load protection delay to start
again.
U
pper temperature and humisity limit protection
U60=3, R1 is timing relay. When temperature or humidity beyond the limit, R1 turn on, R2 R3 off, R4 R5 still the same
U60=2, R1 is timing function. When humidity or temperature beyond limit R1 turn on.
U60=1, R1 is timing function, limit protecting function stop.
Sensor
When the sensor broken controller shows”E1”, humidity and temperature load off, warning output on.
4th
When the display value is different from real value, it can be correct byhumidity(temperature) value
correctionrange is ±9.9%
Do not change Sensor or connecting ways, when the power is on
Factory setting:
Keep【P】and 】keys pressed for 5 seconds, the device displays “UnL”, press twice controller
will reset auto. Default password is「0000」.
Controller Installation
Warning
Avoid installing the device in the following environment:
● Relative humidity is greater than 90%, or possibly dewing.
● Strong vibration.
● Possibility be dropped, or within fog.
● Exposed to eroding and polluting gases (such as: air containing sulfur and ammonia, salty fog, smoky mist) to
prevent erosion and oxidation.
● Ambient containing explosive or inflammable materials/gases.
Installation Procedure
Insert the controller into hole (step one) Slide the bracket to fix the device (step two)
Electrical Connection
Warning
● Electrical wiring must be manipulated by certified electrician.
● Wrong power supply may damage the device and system seriously.
● Try with effort to layout the sensors and switches line apart from inductive load lines and power supply lines.
The sensors and switches lines are not allowed go with the power supply lines and inductive load lines in a
same pipeline, and are not allowed to pass near the contactor, breaker and the similar.
● Reduce the length of sensors’ wiring as possible, avoid forming a spiral shape near the power devices.
● Avoid direct contact with the internal electronic components.
● After finish and check the electrical wiring layout, before connect them to the device, please follow this
instruction: Pay attention the “electrical wiring diagram” below, wrong connection possibly damages the device
and the system, and may be dangerous to the user. All security and protecting device for the equipment are
necessary. They are very important to protect the equipment, and the user’s safety.
Electrical wiring diagram