Lightolier SX User Manual

POWER-CONNECT
RC CABLE
Page 1 of 2 EZ-CONNECT CABLES, “D” SERIES
APPLICATION DIMENSIONS
Job Information Type:
Job Name:
Cat. No.:
Volts/Ballast:
Lightolier a Genlyte Thomas Company www.lightolier.com
Technical Information: (978) 657-7600 • Fax (978) 658-0595 631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710 We reserve the right to change details of design, materials and finish. © 2002 Genlyte Thomas Group LLC (Lightolier Division) A0902 OPTIONS/ACCESSORIES/Folio OA40-10
Features
• Combination of external fixture adapter and armored cable.
• Cables can be rotated 180° in either direction for proper cable orien­tation to prevent strain on connection.
• Suitable for use in return air spaces above suspended ceilings in accordance with 1999 N.E.C. 300-22 (c) and 604-3.
• Rated for 20 amp 120 and 277 volt lighting circuits.
• Connector polarized and color-coded for voltage function to prevent mismating of components.
• #12 AWG THHN stranded copper, 600 volt.
• Fixture taps that are #18 AWG TFN solid copper conductors, con­nected to “Poke-Home” connectors.
• Positive latching steel spring latches engage with easy push action.
• Pin and socket contacts.
• Meets UL requirements for making or breaking under load.
• I.B.E.W./UL and C-UL labeled.
9/16"
5/8"
*When installed, RC cable adds 7/8" to fixture height.
Quick and easy field-installed by plugging ballast leads into “Poke Home” connectors, no wirenuts required. Snaps into standard 1/2" knockout. EZ-Connect cables add maximum of 7/8" to fixture height, available in 1, 2 or 3 circuits.
3/4"
2-5/16"
1-11/16"
POWER-CONNECT
RC CABLE
Page 2 of 2 EZ-CONNECT™CABLES, “D” SERIES
Lightolier a Genlyte Thomas Company www.lightolier.com
Technical Information: (978) 657-7600 • Fax (978) 658-0595 631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710 We reserve the right to change details of design, materials and finish. © 2002 Genlyte Thomas Group LLC (Lightolier Division) A0902 OPTIONS/ACCESSORIES/Folio OA40-10
Job Information Type:
SPECIFICATIONS
• UL and C-UL Listed.
• IBEW labeled.
• Suitable for use in return air spaces above suspended ceilings in accordance with 1999 N.E.C. 300-22 (c) and 604.3.
• Meets UL requirements for making or breaking under load.
• Pin and socket contacts.
• Rated for 20 amp 120 and 277 volt lighting circuits.
• Connector polarized and color-coded for voltage function to prevent mismat­ing of components.
• #12 AWG THHN stranded copper, 600 volt.
• Fixture taps that are #18 AWG TFN solid copper conductors, connected to “Poke-Home” connectors.
• Positive latching steel spring latches engaged with easy push action.
WIRING DIAGRAM WIRING
ORDERING INFORMATION
Explanation of Catalog Number. Example: LP–RC–12–1D–05
RCLP
TYPE:
RC =EZ-Connect™
Cable
LOL POWER
CONNECT
WIRING
CONFIGURATION: 1D - 1 Circuit 2D - 2 Circuit 3D - 3 Circuit ND - 2 Cir., 2 Neu.
VOLTAGE: 12 - 120v 27 - 277v
LENGTH:
05 - 5' 07 - 7' 09 - 9' 11 - 11' 13 - 13' 17 - 17' 21 - 21' 25 - 25' 30 - 30'
THREE CIRCUIT
TWO CIRCUITONE CIRCUIT
(Typical)
• Black lead to outboard ballast lead.
• Red lead to inboard ballast lead.
• White lead to white ballast leads.
a b c d e
black white
blue
ground
red
WIRING COLOR LEGEND
Panelboard Switching (Typical)
Local Switching (Typical)
5
GROUND
4
3
WHITE
2
POWER IN
BLACK
1
abd
5
4
3
2
POWER OUT
1
RED
5
GROUND
4
3
WHITE
2
POWER IN
BLACK
1
a
bd
5
4
3
2
POWER OUT
1
e
RED
5
GROUND
4
BLUE
3
NEUTRAL
2
POWER IN
BLACK
1
5
4
3
2
1
e
a
bd
POWER OUT
Loading...