Skyway SKS2GPK232 or 332
Page 1 of 2 2' x 4' Recessed Fluorescent, Tri-Lens Frame
Static or Air Supply/Return, 2 or 3 Lamp T8
Features
• Aesthetically pleasing triple lens design.
• Curved high light transmission frost white acrylic side lenses.
• Clear acrylic conical prismatic center lens.
• Internal reflector coated with 95% reflective white paint.
• 75.3% efficient 2 Lamp 32 watt T8.
• 75.4% efficient 3 Lamp 32 watt T8.
• 5" deep body.
• Black housing exterior for cooler ballast operating temperature.
• Eyeleted heat removal vents in fixture ends.
• Hemmed over side rails for maximum safety.
• Fixture ends turned-in for safe handling.
• Built-in earthquake clips.
• Door jamb finished black on four sides for positive light stop.
• True mitered corner aluminum lens frame.
• Spring loaded rooster head latches.
• 18 gauge steel hinges.
• Construction to meet NYC Code Requirements or Chicago Plenum is available.
Mounting Methods Dimensions
24" (610mm)
2" max.
24"
Exposed T-grid ceiling.
G
earthquake clip installed (lay-in grid)
15/16"
9/16"
5"
(127mm)
2" max.
24" (610mm)
or
T
Drywall Kit, Catalog Number: FK92X4.
24"
Exposed Slot T-grid ceiling
Skyway
Fixture
15/16"
or
9/16"
Support (by others)
Drywall Kit
(See Options)
Drywall
(by others)
6" (152mm)
2" X 2-1/2" Access Plate with (2)
7/8" (73mm) Dia. KO’s
47-31/32" (1218mm)
Air supply slots
39-1/4" (997mm)
(SKA Only)
5"
(127mm)
Job Information Type:
Job Name:
For Factory Technical Information: (978) 657-7600 • Fax (978) 658-0595 08/10
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
www.lightolier.com © Philips Group
Cat. No.:
Lamp(s):
Volts/Ballast:
Section 5/Folio MA12-18 Rev. B

Skyway SKS2GPK232 or 332
Page 2 of 2 2' x 4' Recessed Fluorescent, Tri-Lens Frame
Static or Air Supply/Return, 2 or 3 Lamp T8
Model No. SKS2GPK232UNVC5
LER = FP - 69.3 IW - 51.9 BF - 0.77
Comparative yearly lighting energy cost per
1000 lumens = $3.46
Report Number: G2008169
Catalog Number: SKS2GPK232UNVC5
Lamps: (2) F32T8/ADV/841/ALTO
Luminaire: Skyway Recessed 2' x 4' fixture
prismatic acrylic lens assembly.
Ballast: INC-2P32-LW-SC
Report is based on 3100 Lumens per lamp.
Efficiency: 75.3%
CIE Type-Direct-Indirect
Plane: 0-Deg 90-Deg
Spacing Criteria: 1.2 1.3
Shielding Angles: 90 90
Plane: 0-Deg 90-Deg
Luminous Length: 45.600 21.600
COEFFICIENTS OF UTILIZATION –
ZONAL CAVITY METHOD. EFFECTIVE
FLOOR CAVITY REFLECTANCE 0.20
RC 80 50 30
RW 70 50 30 50 30 10 50 30 10
01 83 80 77 75 73 71 72 70 69
02 76 70 66 66 63 60 64 61 58
03 70 63 57 59 55 51 57 54 50
04 64 56 50 53 48 44 52 47 44
05 60 51 44 48 43 39 47 42 39
06 55 46 39 44 38 34 43 38 34
07 51 42 35 40 35 31 39 34 31
08 48 38 32 37 31 28 36 31 28
09 45 35 29 34 29 25 33 28 25
10 42 33 27 31 26 23 31 26 23
0
CANDELA DISTRIBUTION
0.0 45.0 90.0 FLUX
0 1990 1990 1990
5 1972 1975 1978 188
15 1875 1891 1913 535
25 1702 1765 1831 815
35 1464 1589 1647 979
45 1156 114 1063 867
55 732 714 643 630
65 406 401 354 400
75 205 185 170 207
85 48 35 31 46
90 000
ZONAL LUMEN SUMMARY
ZONE LUMENS % LAMP % FIXT
00-030 1537 24.8 32.9
00-040 2516 40.6 53.9
00-060 4013 64.7 86.0
00-090 4666 75.3 100.0
90-180 0000 0.0 000.0
00-180 4666 75.3 100.0
LUMINANCE DATA IN CANDELA/SQ. METER
AVERAGE AVERAGE AVERAGE AVERAGE
IN DEG. 0-DEG. 45-DEG. 90-DEG.
45 2572. 2478. 2365.
55 2008. 1958. 1764.
65 1511. 1493. 1318.
75 1246. 1124. 1033.
85 866. 632. 560.
Model No. SKS2GPK332UNVH3
LER = FP - 70.9 IW - 87.0 BF - 0.88
Comparative yearly lighting energy cost per
1000 lumens = $3.38
Report Number: G2008332
Catalog Number: SKS2GPK332UNVH3
Lamps: (3) F32T8/ADV/841/ALTO
Luminaire: Skyway Recessed 2' x 4' fixture
prismatic acrylic lens assembly.
Ballast: ICN-3P32-SC
Report is based on 3100 Lumens per lamp.
Efficiency: 75.4%
CIE Type-Direct-Indirect
Plane: 0-Deg 90-Deg
Spacing Criteria: 1.2 1.3
Shielding Angles: 90 90
Plane: 0-Deg 90-Deg
Luminous Length: 45.600 21.600
COEFFICIENTS OF UTILIZATION –
ZONAL CAVITY METHOD. EFFECTIVE
FLOOR CAVITY REFLECTANCE 0.20
RC 80 50 30
RW 70 50 30 50 30 10 50 30 10
01 83 80 77 75 73 71 72 70 68
02 76 70 66 66 63 60 64 61 58
03 70 63 57 59 55 51 57 53 50
04 64 56 50 53 48 44 51 47 44
05 60 50 44 48 43 39 47 42 38
06 55 46 39 44 38 34 42 38 34
07 51 42 35 40 35 31 39 34 30
08 48 38 32 37 31 28 36 31 28
09 45 35 29 34 29 25 33 28 25
10 42 33 27 31 26 23 31 26 23
0
CANDELA DISTRIBUTION
0.0 45.0 90.0 FLUX
0 3104 3104 3104
5 3082 3082 3092 293
15 2940 2945 2951 831
25 2672 2662 2625 1222
35 2284 2184 2158 1382
45 1710 1657 1665 1284
55 1052 1099 990 955
65 608 639 565 626
75 323 296 284 333
85 90 74 66 88
90 15 16 8
ZONAL LUMEN SUMMARY
ZONE LUMENS % LAMP % FIXT
00-030 2346 25.2 33.5
00-040 3728 40.1 53.2
00-060 5967 64.2 85.1
00-090 7014 75.4 100.0
90-180 0000 0.0 000.0
00-180 7014 75.4 100.0
LUMINANCE DATA IN CANDELA/SQ. METER
AVERAGE AVERAGE AVERAGE AVERAGE
IN DEG. 0-DEG. 45-DEG. 90-DEG.
45 3804. 3686. 3704.
55 2885. 3014. 2715.
65 2263. 2379. 2103.
75 1963. 1895. 1726.
85 1624. 1336. 1191.
Ordering Information
Explanation of Catalog Number. Example: SKS2GPK232UNVHI
K
Center Lens:
K= Pattern 19
.156 Virgin
Acyrlic Lens
has side rails
Skyway
Recessed
Fluorescent
SK
SY
2
Body Style:
S = Static
A = Air
Standard Skyway
For NYC Code – I.B.E.W. Manufactured
Fixture
Width
Ceiling Type:
G = Standard
Grid
T = Slot Grid
P
Side Lens:
P= Frost White
Acrylic Lens
Options/Accessories
Fusing: Internal fast blow fusing: SUFFIX: A.
Internal slow blow fusing: SUFFIX: C.
Drywall Kit: Order Catalog Number: FK92X4.
Electrical Wiring Options: Consult factory.
For motion or light sensor: See Folio OA20-10 and OA20-30.
Specifications
Performance: In an installation of 2 lamp 32W luminaires in a room cavity ratio of 1,
with reflectance 80% ceiling, 50% wall, 20% floor, the C.U. shall not be less than .80.
To reduce glare the average brightness at 65° shall not exceed 1511 candelas per
square meter. To control veiling reflections, luminaire output in the 30°-90° zone shall
not be less than 67.1%.
Air Handling: (SKA only) side air passages for air supply or air return. Supply air is
discharged vertically. Optional side closure strips. Air return is also provided through the
lamp compartment through fixture body ends.
Materials: Chassis parts are die-formed code gauge cold rolled steel. Housing
hemmed over and housing ends turned-in for safe handling.
32
Lamp
Quantity
2=2 Lamp
3=3 Lamps
Specifications (continuned)
Finish: Chassis exterior–black baked polyester enamel. Cavity–white baked poly-
ester enamel minimum 86% reflectance. Rust preventative undercoating. Reflectors-
95% reflective white powder coated.
Lens: Proprietary high quailty frost white acrylic and clear conical prism lens assembly.
Electrical: Thermally protected class “P’ ballast C.B.M. approved, non PCB. If K.O. is
within 3" of ballast, use wire suitable for at least 90°.
UL Listed for damp locations.
Labels: I.B.E.W./UL and ULc Listed.
This product may have a mercury containing lamp. Manage in accord with Disposal
Laws. See: www.lamprecycle.org
Job Information Type:
Lamp:
(By Others)
32=T8 32W
(Nominal 48")
Voltage:
120, 277 or
UNV=120-277
1 or 2 Lamp Elec. T8 SO* H
1-3 Lamp Elec. T8 O3* H3* 0.88
Advance Optanium
1 or 2 Lamp Elec. T8 – C5* 0.77
1 - 3 Lamp Elec. T8 – C6* 0.77
LOL Dimming T8 PS* –
*Instant Start Standard
Other dimming options. Consult factory.
NOTE:
For T8 UNV, you must use H
Ballast Type:
<20THD <10THD Factor
I
OR H3 Ballast Code.
Add appropriate suffix
to catalog no., ie: (A)
Ballast
I* 0.88
Options:
For Factory Technical Information: (978) 657-7600 • Fax (978) 658-0595 08/10
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
www.lightolier.com © Philips Group
Section 5/Folio MA12-18 Rev. B