Lightolier SC User Manual

Cleanlite Enclosed Industrial Fluorescent SC Series
Page 1 of 2 Damp and Wet Locations, 1, 2 or 3 Lamp T5 or T8
Features
• UL-Listed for damp and wet locations.
• For industrial or commercial applications.
• Crisp modular design.
• Available in 4' one piece body.
• Continuous closed-cell gasketing at all seal points.
• Smooth one-piece water-clear acrylic lens.
• Lock-tight cam-action latches.
• Wet location fixtures available.
• Metal/gauge/construction meets NYC Code requirements.
Mounting Methods Dimensions
fully enclosed and gasketed
crisp modular profile
heavy-duty cam-action latches
Job Information Type:
Job Name:
Cat. No.:
Lamp(s):
Volts/Ballast:
2/06
Lightolier www.lightolier.com
Technical Information: (978) 657-7600 • Fax (978) 658-0595 631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710 We reserve the right to change details of design, materials and finish. © 2005 a Genlyte company
Section 7/Folio Q30-21 Rev. C
Cleanlite Enclosed Industrial Fluorescent SC Series
Page 2 of 2 Damp and Wet Locations, 1, 2 or 3 Lamp T5 or T8
Model No. SC4DC232120SO
LER = FP - 72.8 IW - 53.8 BF - 0.87 Comparative yearly lighting energy cost per
1000 lumens = $3.30
Report Number: G92060 Catalog Number: SC4DC232120SO Lamps: F32T8 Luminaire: Cleanlite enclosed industrial with clear one-piece acrylic lens. Ballast: Triad B232I120RH-A Report is based on 2850 Lumens per lamp.
Efficiency: 79.0% CIE Type-Direct-Indirect
Plane: 0-Deg 90-Deg Spacing Criteria: 1.2 1.5 Shielding Angles: 90 90
COEFFICIENTS OF UTILIZATION –
ZONAL CAVITY METHOD. EFFECTIVE FLOOR CAVITY REFLECTANCE 0.20
RC 80 50 30
RW 70 50 30 50 30 10 50 30 10
01807571716865676462 02716458605651575349 03645649524742494440 04584942464035433834 05534336413430393329 06493931373026352925 07453528332722312622 08423225302420292319 09392922282218262117
10 37 27 20 25 20 16 24 19 16
LUMINANCE DATA IN CANDELA/SQ. METER
AVERAGE AVERAGE AVERAGE AVERAGE
IN DEG. 0-DEG. 45-DEG. 90-DEG.
45 4256. 4473. 5156. 55 3770. 4644. 5139. 65 3020. 4376. 4769. 75 1939. 3978. 4608. 85 903. 3389. 4159.
0
CANDELA DISTRIBUTION
0.0 45.0 90.0 FLUX
0 1032 1032 1032
5 1022 1034 1047
15 979 1020 1057
25 899 992 1068
35 785 940 1058
45 642 870 1070
55 473 818 983
65 290 667 806
75 124 493 653
85 27 311 458
90 12 231 367
ZONAL LUMEN SUMMARY
ZONE LUMENS % LAMP % FIXT
00-030 846 15.0 19.0 00-040 1431 25.0 32.0 00-060 2792 49.0 62.0 00-090 4170 73.0 92.0
90-180 350 6.0 8.0
00-180 4520 79.0 100.0
0
Model No. SC4DC354120PG
LER = FP - 66.0 IW - 154.9 BF - 1.0 Comparative yearly lighting energy cost per
1000 lumens = $3.64
Report Number: G2005352 Catalog Number: SC4DC354120PG Lamps: F54T5 HO Luminaire: Cleanlite enclosed industrial
with clear one-piece acrylic lens. Ballast: QTP2X54T5/UNV PSN Report is based on 4400 Lumens per lamp.
Efficiency: 76.6% CIE Type-Direct-Indirect
Plane: 0-Deg 90-Deg Spacing Criteria: 1.2 1.5
COEFFICIENTS OF UTILIZATION –
ZONAL CAVITY METHOD. EFFECTIVE FLOOR CAVITY REFLECTANCE 0.20
RC 80 50 30
RW 70 50 30 50 30 10 50 30 10
01807672706764666461 02726559605551575349 03655649524642494441 04594942464035433834 05544436413430393329 06503932363026352925 07463528332723312622 08433225302420292420 09402923282218262118
10 38 27 21 25 20 16 24 19 16
LUMINANCE DATA IN CANDELA/SQ. METER
AVERAGE AVERAGE AVERAGE AVERAGE
IN DEG. 0-DEG. 45-DEG. 90-DEG.
45 9560. 10660. 10455. 55 8568. 10308. 10046. 65 6941. 10084. 10303. 75 4495. 10407. 9715. 85 2070. 7912. 6981.
0
CANDELA DISTRIBUTION
0.0 45.0 90.0 FLUX
0 2538 2538 2538
5 2507 2537 2569 242
15 2401 2525 2593 709
25 2213 2410 2569 1109
35 1943 2265 2516 1412
45 1602 2084 2336 1554
55 1194 1770 2050 1532
65 742 1439 1839 1372
75 320 1138 1433 1069
85 69 575 782 574
90 26 391 581
95 54 296 520 309
105 44 68 197 115
115 24 72 57 53
125 15 54 63 39
135 10 22 49 20
145 0 0 20 5
155 0 0 0 0
165 0 0 0 0
175 0 0 0 0
180 0 0 0 0
ZONAL LUMEN SUMMARY
ZONE LUMENS % LAMP % FIXT
00-030 2061 15.6 20.4 00-040 3473 26.3 34.3 00-060 6559 49.7 64.8 00-090 9574 72.5 94.7
90-120 477 3.6 4.7 90-130 516 3.9 5.1 90-150 541 4.1 5.3 90-180 541 4.1 5.3
00-180 10115 76.6 100.0
0
Ordering Information
Explanation of Catalog Number. Example: SC4DC232120SO
SC
Cleanlite:
Industrial
Fluorescent
for
Damp
Locations
4
Fixture Length
4 = 4' Length
Location:
D = Dry and
Damp Locations
W =Wet
Locations
C
Lens:
C = Clear
Options/Accessories
Tamperproof Latches: Suffix: TP. Optional Lenses: Lexan lenses or DR acrylic lens. Consult factory.
Specifications
Materials: Chassis shall be 20 gauge steel. Wireway Cover: Full length retained by fasteners for quick removal and
convenient servicing. Lens: One-piece flanged lens enclosure molded from .125" thick smooth water­clear virgin acrylic. Lens enclosure shall be heavy-duty enclosed and gasketed with closed-cell foam gasketing (permanently attached to fixture housing).
Latches: Lock-tight cam action. Finish: Chassis shall be phosphate primed and finished in baked white acrylic
enamel for not less than 86% reflectivity. Electrical: Thermally protected class “P” ballast C.B.M. approved, non PCB. If K.O. is within 3" of ballast, use wire suitable for at least 90°.
Labels: I.B.E.W./UL and ULc Listed.
32
Number of
Lamps in
Width:
1, 2 or 3 Lamps
Lightolier www.lightolier.com
Technical Information: (978) 657-7600 • Fax (978) 658-0595 631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710 We reserve the right to change details of design, materials and finish. © 2005 a Genlyte company
Lamp/Watts
(By others)
32 = 32W T8 28 = 28W T5 54 = 54W T5
(Nominal 48")
Voltage:
120, 277 or
UNV=120-277
Ballast Type:
1 & 2 Lamp Elec. T8 SO * H 1-3 Lamp Elec. T8 O3 * H3 * 1 & 2 Lamp 28W Elec. T5 P 1 & 2 Lamp 28W or 54W Elec. T5 PG †† 1-3 Lamp 54W Elec. T5 PU ††
LOL T8 Dimming PS* Other dimming options. Consult factory.
* Instant Start Standard† Instant Start (120, 277).
†† Program Rapid Start (UNV only).
NOTE: For T8 UNV, you must use H
Job Information Type:
Section 7/Folio Q30-21 Rev. C
<20THD <10THD
I
, H3 Ballast Code.
Options:
Add appropriate suffix to catalog
no, ie: (TP)
I *
I
Loading...