Lightolier Power Connect RD Cable User Manual

POWER-CONNECT
RD CABLE
Page 1 of 2 LIGHTING DISTRIBUTION CABLES, “D” SERIES
APPLICATION DIMENSIONS
Job Information Type:
Job Name:
Cat. No.:
Volts/Ballast:
Lightolier a Genlyte Thomas Company www.lightolier.com
Technical Information: (978) 657-7600 • Fax (978) 658-0595 631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710 We reserve the right to change details of design, materials and finish. © 2002 Genlyte Thomas Group LLC (Lightolier Division) A0902 OPTIONS/ACCESSORIES/Folio OA40-16
Features
• Pre-wired with female (power out) connector and fixture taps that are #18 AWG TFN solid copper conductors, connected to “Poke­Home” connectors. Opposite end has 6" leads and 1/2" K.O. connec­tor for mounting to a junction box in a standard 1/2" (7/8" diameter) knockout.
• Suitable for use in return air spaces above suspended ceilings in accordance with 1999 N.E.C. 300-22 (c) and 604-3.
• Rated for 20 amp 120 and 277 volt lighting circuits.
• Connector polarized and color-coded for voltage function to prevent mismating of components.
• #12 AWG THHN stranded copper, 600 volt.
• Pin and socket contacts.
• Meets UL requirements for making or breaking under load.
• I.B.E.W./UL and C-UL labeled.
3/4"
5/8"
2-5/16"
“D” Series Distribution cable distributes the lighting circuit(s) to the first lighting fixture on the flexible wiring system from a hardwired system. It is quickly or easily field-installed by plugging ballast leads into “Poke-Home” connectors, no wire nuts required. Snaps into 1/2" knockout. "D" Series distribution cables add a maximum of 7/8" to fixture height, available in 1, 2 or 3 circuits.
POWER-CONNECT
RD CABLE
Page 2 of 2 LIGHTING DISTRIBUTION CABLES, “D” SERIES
Lightolier a Genlyte Thomas Company www.lightolier.com
Technical Information: (978) 657-7600 • Fax (978) 658-0595 631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710 We reserve the right to change details of design, materials and finish. © 2002 Genlyte Thomas Group LLC (Lightolier Division) A0902 OPTIONS/ACCESSORIES/Folio OA40-16
Job Information Type:
SPECIFICATIONS
• UL and C-UL Listed.
• I.B.E.W. labeled.
• Suitable for use in return air spaces above suspended ceilings in accor­dance with 1999 N.E.C. 300-22 (c) and 604.3.
• Meets UL requirements for making or breaking under load.
• Pin and socket contacts.
• Rated for 20 amp 120 and 277 volt lighting circuits.
• Connector polarized and color-coded for voltage function to prevent mismat­ing of components.
• #12 AWG THHN stranded copper, 600 volt.
• Pre-wired with female (power-out) connector and fixture taps that are #18 AWHG TFN solid copper conductors, connected to “Poke-Home” connectors.
• Opposite end has 6" leads and 1/2" K.O. connector for mounting to a junc­tion box in a standard 1/2" (7/8" diameter) knockout.
WIRING DIAGRAM WIRING
ORDERING INFORMATION
Explanation of Catalog Number. Example: LP–RD–12–1D–09
RDLP
TYPE:
RD =Lighting
Distribution
Cable
LOL POWER
CONNECT
WIRING
CONFIGURATION: 1D - 1 Circuit 2D - 2 Circuit 3D - 3 Circuit ND - 2 Cir., 2 Neu.
VOLTAGE: 12 - 120v 27 - 277v
LENGTH:
05 - 5' 09 - 9' 15 - 15' 25 - 25'
––
ONE CIRCUIT
ONE CIRCUIT TAP TWO CIRCUIT TAP
TWO CIRCUIT TAP
TWO CIRCUIT
THREE CIRCUIT
(TYPICAL)
• Black lead to outboard ballast lead.
• Red lead to inboard ballast lead.
• White lead to white ballast leads.
Loading...