Lightolier LUPS User Manual

LUPS Series Uninterruptible Power Supplies LUPS
Page 1 of 2 550 - 1,500 VA Sine Wave UPS System
Operates incandescent, electronic ballast loads and HID lighting loads as well as critical loads requiring conditioned emergency power.
1.0”
6.6”
1
2.2 cm
4
How to Specify: LUPS
Series VA Rating Voltage Output Circuit
UPS
L
= Power Supply for 1000 = 1,000 VA A = 120 120 OCB3 = (1000, 1500 VA) Emergency Lighting 1500 = 1,500 VA B = 277 277
pplications
A
LUPSX = 10 Minute Backup LUPSY = 20 Minute Backup
3
8.7 cm
7
LUPS Uninterr
50 VA 1000 VA 1500 VA
Cabinet &
lectronics
E
ealed Lead
S Calcium Battery
9.0”
3
99.1 cm
uptible 550 = 550 VA Input Output OCB1 = (550 VA)
0 Minute 44 lbs. 59 lbs. 88 lbs.
1
ackup (19.9 kg) (26.8 kg) (39.9 kg)
B 20 Minute 54 lbs. 88 lbs. 108 lbs.
ackup (24.5 kg) (39.9 kg) (49.0 kg)
B 90 Minute 121 lbs. 203 lbs. 288 lbs.
Backup (55 kg) (92 kg) (131 kg)
5
223 lbs. 223 lbs. 262 lbs.
101 kg) (101 kg) (119 kg)
(
onfiguration Breakers
C
Overall Characteristics
• 83% throughput efficiency
• Single conversion UPS, No transfer time
• Operating temperature range of 32°F (0°C) to 104°F (40°C); 65°F (19°C) to 85°F (29°C) maximum for batteries
• Standard 90 minutes of operating time
• Full-time, isolating transformer
• Variable Range Regulator allows wider range of acceptable input voltage variation
• ANSI/IEEE C62.41 category A& B surge voltage withstand capability
Housing
• Free standing, NEMA 1 enclosure with locking doors
• Acid resistant powder coat finish
• Multiple conduit entries
Standard Metering/Controls
• AC input and output voltage AC input br
• AC output breaker
• Battery disconnect device
• Automatic battery monitor with alarm
• LED indicating lamps for system on, system on battery, low battery warning
eaker
Battery
Maintenance fr 10 years, and operating temperature range of 65°F (19°C) to 85°F (30°C)*.
* Increases or decreases in temperature will affect battery performance. Optimum battery performance
ealized at 77
r
ee, sealed lead calcium battery has an estimated service life of
°F (25°C). Batteries are rated at 100% capacity at 77°F (25°C).
Electronics
Input
• Input power factor self-correcting to > 0.95
• Frequency 60.0 ±2.5 Hz
• Input voltage tolerance +10% to -15%
• Input harmonics < 8% THD
Output
• Solid-state PWM inverter with sine wave output
• Output voltage regulation ±3% of nominal at full load
• Output frequency 60 Hz ±0.2%
• Load power factor capability is 0.6 lagging to unity Overload rating: 125% for 10 minutes
• Efficiency: 82% to 86%
Charger
Low voltage disconnect (L
VD)
• 3 amp, 2-stage
Rechar
ge time: UL 924 compliant
Options
FSU = Start-up Service EXT = Extended Warranty (with FSUonly)
ob Inf
J
ob Name:
J Cat. No.:
ormation Type:
.lightolier
Lightolier a Genlyte Company
www
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
ve the right to change details of design, materials and finish.
eser
e r
W © 2006 Genlyte Gr
oup LLC (Lightolier Division) •
C0406
.com
LUPS Series Uninterruptible Power Supplies LUPS
Page 2 of 2 550 - 1,500 VA Sine Wave UPS System
NPUT (Select One) OUTPUT (Select One)
I
MODEL CAPACITY AC INPUT INPUT AVAILABLE OUTPUT VOLTAGES/ BREAKERS
OLTAGES AMPS
V
LUPS550
LUPS1000 1,000 VA 120 11.5 8.3 3.6 3
LUPS1500 1,500 VA 120 17.2 12.5 5.4 3
NOTES:
Maximum input current
1
550 VA 120 6.5 4.6 2.0 1
277 2.0 4.6 2.0 1
277 5.0 8.3 3.6 3
277 7.4 12.5 5.4 3
Warranty
Electronics: 1 year Battery: 1 year full, 9 years pro-rata Extended warranty options available
1
AX. LOAD AMPS INCLUDED
M
120 V 277 V
System One-Line Diagram
Listed to
UL 924 and
UL 924
Auxiliar
Equipment
y
Job Information Type:
.lightolier
Lightolier a Genlyte Company
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
ve the right to change details of design, materials and finish.
eser
e r
W © 2005 Genlyte Gr
oup LLC (Lightolier Division) •
B0505
www
.com
Loading...