Lightolier LP User Manual

LP Series LED Steplight LP
Page 1 of 2 Normal AC and/or Emergency Low Level Applications
The LP Series is designed to support low-level illumination of stairwells, step landings, wheelchair ramps, exit corridors, theaters, restaurants and hospitals.
1.50”
2.75”
(6.99 cm)
4.50”
(11.4 cm)
Complete Fixture consists of luminaire. Select options and accessories below.
How to Specify: LP S WH
SERIES INPUT LENS FINISH VOLTAGE
LP = Low Level Emergency Lighting Product
1 = 12V AC, DC 2 = 120 AC
(3.8 cm)
S = Satin
3.25”
(8.25 cm)
WH = White BK = Black IV = Ivory
Features
1. Illumination: The LP Series LED engine utilizes three high per formance,
3500k white LEDs combined with a solid-state integral driver circuit. Incorporates a user selectable, three level intensity control.
2. Housing: Assembled from premium die cast aluminum components and is painted in a durable powder coat finish. Standard finishes include black, white and ivory. Assembled as a one-piece device that includes the LED light engine, integral power supply, three level intensity control and a single gang junction box mounting plate. All LED and electrical components are pro­tected by both a frosted acrylic lens and high impact power supply case that will be located within the junction box.
3. Electronics: Designed with all solid-state components and is rated for 10 years of continuous “normally on” use. Standard product incorporates dip switches on rear of product allowing three levels of intensity.
4. Versatile Applications: “Normally On” remote power supplies are available from 100VA to 500VA in 12 VAC. Power supplies (120 VAC input) conform to UL 1598 and are rated as Class 2 Distribution systems. All power supplies are furnished in a UL type 3R enclosure and are provided with thermal type secondary output circuit protection. (Suggested for use with Lightolier’s LPS Series)
“Normally Off/Emergency” remote power can be provided by any
Lightolier 12V emergency lighting product with additional remote capacity. (Suggested for use with Lightolier catalog No. C3250 or C3275.)
“Normally On/Emergency” remote power can be provided by Lightolier
LM emergency power system. The LM system will support up to 14 LP Series luminaires operating in both continuous duty and emergency operation for 90 minutes.
5. Electrical Specifications: 12 VDC input: 0.47 amps; 12 VAC input: 0.72 amps; 120 VAC input: 0.09 amps
6. Installation: LP is designed for installation in a single gang metallic or die cast junction box. When installing the LP in an outdoor damp or wet location, a single gang rectangular-st yle junction box will be required by
most local electrical codes.
7. Operating Temperature Range: -40°F (-40°C) to 122°F (50°C)
8. Warranty: Five-year full electronics warranty.
Code Compliance
UL 1598 listed. NFPA, BOCA and OSHA illumination standards. Meets ADA specifications for wall mounted lighting fixtures. UL listed for wet
locations.
Job Information Type:
Job Name:
Cat. No.:
Lamp(s):
Notes:
Lightolier is a Philips group brand
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
www.lightolier.com © 2009 Philips Group • E0109
LP Series LED Steplight LP
Page 2 of 2 Normal AC and/or Emergency Low Level Applications
Multiple Luminaries Single Luminaire
18” AFF
.1
Note #1: Photometry based on clear lens. Please consult factory for frosted/white lens IES files.
Luminaire #1
1.0
.5
.3
.2
8’ x 3’ Path (Shown Above)
Illuminance Values (Fc) Average = 1.07 Maximum = 1.80 Minimum = 0.50 Avg/Min Ratio = 2.14 Max/Min Ratio = 3.60
See Note #1
Luminaire #2
3’
8’
8’ x 4’ Path
Illuminance Values (Fc) Average = 1.04 Maximum = 3.10 Minimum = 0.30 Avg/Min Ratio = 3.47 Max/Min Ratio = 10.33
See Note #1
18” AFF
1.0
3’
.3
.2
.1
3’ x 6’ Area (Shown Above)
Calc. Rep Entrance Area Illuminance Values (Fc) Average = 1.38 Maximum = 4.70 Minimum = 0.30 Avg/Min Ratio = 4.60 Max/Min Ratio = 15.67
See Note #1
.5
LPS Series “Normally On / Non-Emergency Application” Non-Emergency Power Supply Selection
• 12 VAC applications
A
• 120 VAC Input Versions rated as Class II Distribution Systems
• UL 3R Enclosures
• Thermal secondary output circuit protection
• Convenient bottom access wiring compartment with terminal lugs
No. of LP Series Input Output Catalog Dimensions
Luminaries Required Voltage Wattage Number A B C 10 120 100 LPS100-12-1 4.88” 6.75” 4.63” 15 120 150 LPS150-12-1 4.88” 6.75” 4.63” 25 120 250 LPS250-12-1 4.88” 6.75” 4.63” 30 120 300 LPS300-12-1 4.88” 6.75” 4.63” 30 277 300 LPS300-12-2 4.88” 6.75” 4.63” 50 120 500 LPS500-12-1 5.63” 8.25” 5.25” 50 277 500 LPS500-12-2 5.63” 8.25” 5.25”
C
B
8’
C3 Series “Normally Off / Emergency” Application
• 12 VDC Applications
• Maintenance-free, sealed lead calcium battery
• 50 watt can operate maximum 8 LP Luminaire
• 75 watt can operate maximum 13 LP luminaires
C3 2 L
SERIES DC OUTPUT BATTERY TRIM COVER VOLTAGE WATTAGE FINISH
C3 = C3 Series Power Module
See C3 spec sheet for full details
2 = 12 Volt
50 = 50 Watts 75 = 75 Watts
LM Series “Normally On / Emergency” Application
• NEMA 1 Enclosure
• Maintenance-free, sealed lead calcium battery
• Can operate 14 LP luminaires
LM
Serie s In put/Ou tput Vol tages Mou nting Co nfigura tion LM = Mini - Interruptible 1 = 120V/120V w/o Light Switch Option CM = Ceiling Plenum Installation*
Power Supplies 2 = 120V/120V w/ Light Switch Option SM = Surface Wall Mount 3 = 277V/277V w/o Light Switch Option RM = Recessed Wall Mount** 4 = 277V/277V w/ Light Switch Option 5 = 120V/12V w/o Light Switch Option 6 = 120V/12V w/ Light Switch Option 7 = 277V/12V w/o Light Switch Option 8 = 277V/12V w/ Light Switch Option
Lightolier is a Philips group brand
L = Sealed Lead Calcium
NOTES:
* (1) MICKIT and (1) MIRDIS accessories included ** Drywall Opening Dimensions: 14.5” W x 24.0” L
5.63”
(14.3 cm)
5.75”
(14.6 cm)
9.5”
(24.1 cm)
W = White B = Black
14.4”
3.5”
8.89 cm
36.6 cm
24.0”
60.96 cm
150 VA
Total Unit 50 lbs. w/ Battery (22.7 kg)
See LM spec sheet for full details
Job Information Type:
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.