Lightolier LOT User Manual

LOT Series
1.5-4.2 KVA SINGLE PHASE UPS
Page 1 of 2
LOT
Width (A)
Depth (B)
Height (C)
1.5-3.5 kVA 36"
24"
72"
Overall Characteristics
Features: 90% throughput
efficiency with 85% emergency
efficiency. Operating
temperature range 32ºF
(0ºC) to 104ºF (40ºC). Fault
current rating of 42 kAIC.
Audible noise less than 50 dB
at 3 ft on “A” weighted scale.
Automatic low battery voltage
disconnect. Double conversion
with no interruption. Solid
state pulse width modulated
inverter. Internal, make before
break maintenance by-pass.
Standard UL 924 compliant,
90 minute battery back up.
UL 924 auxiliary equipment
10 and 20 minute back up
available. Microprocessor
control and diagnostic system.
B
C
4.2 kVA 36"
24"
80"
LED array system status panel.
Fault annunciating audible
alarm. Current limiting start
sequence. Optional output
circuit breakers (OCB) and
circuit breakers with trip alarm
(OCBA). Optional normally
off load (NOL) energizes only
during power outage, normally
off load with time delay (TDT)
also available. Free standing
NEMA 1 enclosure. Lockable
control access panel. Seismic
anchoring compatible.
Application: The solid state
pulse width modulated (PWM)
inverter offers enhanced load
compatibility. It operates
incandescent, magnetic, and
electronic ballast fluorescent,
high power factor compact
fluorescent and high intensity
discharge (HID) luminaries.
Provides conditioned,
uninterruptible power for
other types of critical loads.
Consult factory for non-lighting
load applications.
Input: Input power factor
correcting to 0.99. Frequency
range 60 Hz, ±2.5 Hz. Input
harmonic current distortion
< 5%THD. UL1449, ANSI/IEEE
C62.41 surge suppression.
Job Information Type:
Job Name:
Cat. No.:
Notes:
Output: Sine wave output.
Voltage regulation ±2%.
Frequency regulation is
synchronized to utility and free
running 60 Hz, ±0.5%. Output
voltage distortion maximum
3% THD with linear load. Load
power factor capability 0.7 lead
to 0.7 lag. Overload capability
125% for 10 seconds.
Code Compliance
UL 924 and UL 924 auxiliary
equipment listed.
Warranty
Lightolier will provide parts
and on-site labor for the first
12 months following start-
up of the product, and parts
only for an additional 12
months. If factory start-up is
not executed within 120 days
of shipment, Lightolier will
provide a parts warranty for
12 months from the date of
shipment. Consult factory for
extended warranty and service
option.
Ordering Information
Q
Q
LOT
Series
LOT = Single Phase U PS System for Emergency Lighting Applications
Input Voltage
A = 120 V G = 120/240 V J = 277 V L = 120/208 V
Output Voltage
A = 120 V G = 120/240 V J = 277 V L = 120/208 V Y = 120/277 V
Unit Size
1.5 = 1.5 kVA
2.2 = 2.2 kVA
3.0 = 3.0 kVA
3.5 = 3.5 kVA
4.2 = 4.2 kVA
System Input/Output Ratings
System Rating (kW/kVA)
Input Volt. (V) : Input Curr. (A)
Output Volt. : Output Current*
OCB Pole S paces Available Without Trip Alarm With Trip Alarm Heat Rejection (btu/hr) Weight (lbs) Electronics 90 Min B atter y 20 Min Battery 10 Min Battery
* Multi -voltage total loads not to exceed system rating.
1.5
120 : 22.1
120/240 : N/A
277 : 9.8
120/208 : N/A
120 : 12.5
120/240 : N/A
277 : 5.4
120/208 : N/A
120/277 : 12.5/5.4
20 10
716
650 445
90 60
120/277 : 18.3/7.9
System One-Line Diagram
Input
Circuit
AC
Breaker
Input
Hardwired
Rectif ier
Fuse
2.2
120 : 26.7
120/240 : N/A
277 : 11.9
120/208 : N/A
120 : 18.3
120/240 : N/A
277 : 7.9
120/208 : N/A
20 10
1050
650 445 195
90
P F
C
LOT Series
1.5-4.2 KVA SINGLE PHASE UPS
Battery Time
S = 90 Min X = 10 Min Y = 20 Min
120 : 39.4
120/240 : 19.1
277 : 17.1
120/208 : 22.1
120 : 25.0
120/240 : 25/12.5
277 : 10.8 120/208 : 25/14.4 120/277 : 25/10.8
Inverter
DC
Fuse
Nol
0 = None 1 = Yes T = Nol w/
TDT
3.0
20 10
1432
640 610 330 195
ty Circuit
Breakers
00X = H ardwire 01X = 1 OCB 02X = 2 OCB 03X = 3 OCB 04X = 4 OCB . . 20X = 20 OCB
01A = 1 OCBA 02A = 2 OCBA 03A = 3 OCBA . . 10A = 10 OCBA
(max. pole spaces 20)
3.5
120 : 45.0
120/240 : 21.8
277 : 19.5
120/208 : 25.2
120 : 29.2
120/240 : 29.2/14.6
277 : 12.6 120/208 : 29.2/16.8 120/277 : 29.2/12.6
20 10
1670
640 610 330 195
Bypass
SS
SS
Inverter
Output Circuit
Breaker
Breakers On 2nd Voltage 00 = 2nd Voltage Hardwire or No 2nd Voltage
01 02 03 . . 19
4.2
120 : 47.0
120/240 : 23.5
277 : 20.3
120/208 : 27.0
120 : 35.0
120/240 : 35/17. 5
277 : 15.2 120/208 : 35/20.2 120/277 : 35/15.2
20 10
2005
840 760 350 230
On Bus w/ Optional
# Nol Circuit Breakers
A = 1 B = 2 C = 3 D = 4 E = 5 F = 6 G = 7 H = 8 I = 9 J = 10 K = 11 L = 12 M = 13 N = 14 O = 15 P = 16 Q = 17 R = 18 S = 19 T = 20 Z = No Nol
Optional Off/
Timed O ff Bus w/
Distribution
Output Hardwired (Standard)
Distribution
Nol Voltage
1 = First 2 = Second 3 = Both 0 = No Nol
Page 2 of 2
ty Nol 2nd
Voltage
A = 1 B = 2 C = 3 D = 4 E = 5 F = 6 G = 7 H = 8 I = 9 J = 10 K = 11 L = 12 M = 13 N = 14 O = 15 P = 16 Q = 17 R = 18 S = 19 Z = No Nol
Battery
Pack
Philips Lightolier e: lol.webmaster@philips.com t: (508) 679-8131 w: www.lightolier.com
LOT Series - 1.5-4.2 September 7, 2011
Specifications are subject to change without notice. © Koninklijke Philips Electronics N.V., 2011. All rights reserved.
Job Information Type:
Loading...